2.1.3

Connect Office Ground

This procedure establishes a ground connection between the chassis and the office ground
connection. A frame ground termination screw is provided on the chassis, for frame ground
connection. This connection must be made in accordance with all local and national electrical
codes.
1. Obtain the following:
• Ground braid
2. Connect one end of the ground braid to the ground stud on the chassis and tighten the nut
securely.
3. Connect the other end of the ground braid to the office ground conductor. Ensure this
connection is made using methods and hardware that meets all applicable local and
national electrical codes.
After installing Power Supply Card connect male connector to female connector on chassis rear
as shown in
Page 6
© 2001, ADC Telecommunications, Inc.
~3/16 IN.
18-22 AWG
RTN
Figure 6. –48Vdc Input Power Connector, Wiring
Figure
7.
Figure 7. –48Vdc Input Power Connector, Male-to-Female Connection
-48V
TURN SCREWS
CLOCKWISE TO
SECURE WIRE
16872-A
16871-A