EVCO S.p.A. | EVJ LCD | Instruction sheet ver. 3.0 | Code 104VJLCDE303 | Page 1 of 2 | PT 16/18
EVJ LCD
EN
ENGLISH
-
wall mounting with or without back-slot for in-wall box (according to the model)
-
12 VAC/DC power supply not insulated or 115... 230 VAC power supply (according to the model)
-
one or two NTC external analog inputs (according to the model)
-
two digital outputs rated 1 res. A @ 250 VAC (according to the model)
-
alarm buzzer
-
incorporated temperature and humidity sensor (according to the model)
-
incorporated Bluetooth Low Energy sensor (according to the model)
-
INTRABUS port
-
device for indoor applications.
Purchasing codes
Installation
Power
External
mode
supply
analog
inputs
EVJD900N2VW
1
EVJD900N2VWIV
1
wall
12 VAC/DC
EVJD920N2VW
mounted
1
EVJD920N2VWIV
1
EVJD902N9VP
2
wall mounted
EVJD902N9VPIV
with back-slot
115... 230
2
EVJD922N9VP
for flush
VAC
2
mounting box
EVJD922N9VPIV
2
1
MEASUREMENTS AND INSTALLATION | Measurements in mm (in)
1.1
Models for wall mounting
Wall mounting (with bolts and fastening screws) or in the most common flush mounting boxes
(with fastening screws).
1.
Unhook the back shell from the front through a screwdriver and the proper seat.
2.1
In case of wall mounting:
2.1.1
Lean the back shell against the wall in a position suitable to get the connecting
cable to pass through the proper opening.
2.1.2
Use the slots of the back shell as template to drill 4 holes having a diameter
suitable to the bolt.
5.0 mm (3/16 in) diameter bolts are suggested.
2.1.3
Insert the bolts in the holes drilled in the wall.
2.1.4
Fasten the back shell at the wall with 4 screws.
Countersunk head screws are suggested.
2.2
In case of flush mounting box, fasten the back shell at the box with 4 screws.
Countersunk head screws are suggested.
3.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
4.
Fasten the front of the device at the back shell.
1.2
Models for wall mounting with back-slot for in-wall box
Wall mounting in the most common flush mounting boxes (with fastening screws).
1.
Unhook the back shell from the front through a screwdriver and the proper seat.
2.
Fasten the back shell at the box with 4 screws.
Countersunk head screws are suggested.
3.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
4.
Fasten the front of the device at the back shell.
Remote user interfaces (with INTRABUS port)
INSTALLATION PRECAUTIONS
Ensure that the working conditions are within the limits stated in the TECHNICAL
-
SPECIFICATIONS section
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks
In compliance with safety regulations, the device must be installed properly to ensure
-
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
N.B.
- Use cables of an adequate section for the current running through them
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables and connect to an INTRABUS network by using a
twisted pair.
2.1
Models for wall mounting
2.1.1
Connectors and parts
Digital
Incorporated
Incorporated
outputs
temperature
Bluetooth
and humidity
Low Energy
sensor
sensor
no
no
no
no
yes
no
no
yes
no
yes
Connector 1
2
no
no
No.
DESCRIPTION
2
yes
2
no
1
INTRABUS port reference (GND)
yes
2
INTRABUS port data (IB)
2
yes
3
device power supply (12 VAC/DC). If the device is fed by DC power, connect terminal
minus
4
device power supply (12 VAC/DC). If the device is fed by DC power, connect terminal
plus
5
AI4 analog input (NTC)
6
AI4 analog input reference (GND)
Connector 2: reserved.
Micro-switch: reserved.
Temperature (AI3) and humidity (AI5) sensor: according to the model.
Bluetooth Low Energy sensor: according to the model.
2.1.2
Electrical connection with independent power supply
N.B.
- Do not supply another device with the same transformer
- The maximum permitted length for connection cables of the INTRABUS port is
30 m (98.4 ft).
2.1.3
Electrical connection with device powered by a controller (for example
c-pro 3 OEM)
N.B.
- Make sure that the current supplied by the controller is within the limits stated in
the TECHNICAL SPECIFICATIONS section
- The maximum permitted length for connection cables of the INTRABUS port is
10 m (32.8 ft).
2.2
Models for wall mounting with back-slot for in-wall box
2.2.1
Connectors and parts
Connector 1
No.
DESCRIPTION
1
device power supply (115... 230 VAC)
2
device power supply (115... 230 VAC)
3
DO2 digital output normally open contact (1 A res. @ 250 VAC)
4
DO1 digital output normally open contact (1 A res. @ 250 VAC)
5
DO1 and DO2 digital outputs common contact (max. 2 A)
Connector 2
No.
DESCRIPTION
6
AI2 analog input (NTC)
7
AI1 analog input (NTC)
8
AI1 and AI2 analog inputs reference (GND)
9
INTRABUS port data (IB)
10
INTRABUS port reference (GND)
Temperature (AI3) and humidity (AI5) sensor: according to the model.
Bluetooth Low Energy sensor: according to the model.
2.2.2
Electrical connection
PRECAUTIONS FOR ELECTRICAL CONNECTION
If using an electrical or pneumatic screwdriver, adjust the tightening torque
-
If the device has been moved from a cold to a warm place, the humidity may have
-
caused condensation to form inside. Wait about an hour before switching on the power
-
Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS
Disconnect the power supply before doing any type of maintenance
-
Do not use the device as safety device
-
-
For repairs and for further information, contact the EVCO sales network; possible re-
turns without back shell will not be accepted.
3
USER INTERFACE
3.1
Device configuration
N.B.
Turn off the power after changing the configuration.
Accessing the procedure.
1.
Touch the SET key for 7 s.
The display will show:
Upper line
Mnu
Lower line
InF
Accessing the menu.
2.
Touch the UP or DOWN key to select a menu.
The display will show:
Upper line
Mnu
Lower line
menu name.
3.
Touch the SET key.
The display will show:
Upper line
the parameter
Lower line
the parameter value
Setting configuration parameters of menu "PAr".
3.
Touch the SET key.
The display will show:
Upper line
PSU
Lower line
0000
4.
Touch the SET key again.
The display will show:
Upper line
PSU
Lower line
a value flashing
5.
Touch the UP or DOWN key to set "-019".
6.
Touch the SET key.
7.
Touch the UP or DOWN key to select a parameter.
The display will show:
Upper line
the parameter
Lower line
the parameter value
8.
Touch the SET key.
The display will show:
Upper line
the parameter
Lower line
the parameter value flashing
Need help?
Do you have a question about the EVJD900N2VW and is the answer not in the manual?
Questions and answers