EVCO S.p.A. | EVJ LCD | Instruction sheet ver. 1.0 | Code 104JLCDA103 | Page 1 of 2 | PT 50/16
EVJ LCD
EN
ENGLISH
-
12 VAC/DC power supply not insulated
-
alarm buzzer
-
models with incorporated Bluetooth Low Energy sensor
-
models with incorporated temperature and humidity sensor
-
INTRABUS port
-
device for indoor rooms.
Purchasing code
incorporated Bluetooth
Low Energy sensor
EVJD900N2VWIX
no
EVJD900N2VWIV
yes
EVJD920N2VWIX
no
EVJD920N2VWIV
yes
1

MEASUREMENTS AND INSTALLATION

Measurements in mm (inches).
Wall mounting (with bolts and fastening screws) or in 502E or 503E flush mounting box (with
fastening screws).
1.
Unhook the back shell from the front through a screwdriver and the proper seat.
2.1
In case of wall mounting:
2.1.1
Lean the back shell against the wall in a position suitable to get the connecting
cable to pass through the proper opening.
2.1.2
Use the slots of the back shell as template to drill 4 holes having a diameter
suitable to the bolt.
5.0 mm (3/16 in) diameter bolts are suggested.
2.1.3
Insert the bolts in the holes drilled in the wall.
2.1.4
Fasten the back shell at the wall with 4 screws.
Countersunk head screws are suggested.
2.2
In case of 502E or 503E flush mounting box, fasten the back shell at the box with 4
screws.
Countersunk head screws are suggested.
3.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
4.
Fasten the front of the device at the back shell.

INSTALLATION PRECAUTIONS

-
Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section
Do not install the device close to heat sources, equipment with a strong magnetic field,
-
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks
-
In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2

ELECTRICAL CONNECTION

N.B.
- Use cables of an adequate section for the current running through them
- Connect to a INTRABUS network by using a twisted pair.
2.1
Connectors and parts
Description.
Connector 1
No.
DESCRIPTION
1
reference INTRABUS port
2
signal INTRABUS port
3
device power supply (12 VAC/DC). If the device is fed by DC power, connect terminal
minus
4
device power supply (12 VAC/DC). If the device is fed by DC power, connect terminal
plus
5
reserved
6
reserved
Connector 2
USB port.
Bluetooth Low Energy sensor
Only available in EVJD900N2VWIV and EVJD920N2VWIV.
Temperature and humidity sensor
Only available in EVJD920N2VWIX and EVJD920N2VWIV.
Connector 2
No.
DESCRIPTION
1
signal + CAN port
2
signal - CAN port
3
reference (GND)
2.2
Electrical connection
Example of electrical connection.
2.3

Pre-setting for the programming

incorporated temperature
To pre-set the device for the programming, place micro-switch 1 in position ON.
and humidity sensor
no
no
yes
yes

PRECAUTIONS FOR ELECTRICAL CONNECTION

If using an electrical or pneumatic screwdriver, adjust the tightening torque
-
-
If the device has been moved from a cold to a warm place, the humidity may have
caused condensation to form inside. Wait about an hour before switching on the power
Make sure that the supply voltage, electrical frequency and power are within the set
-
limits. See the section TECHNICAL SPECIFICATIONS
Disconnect the power supply before doing any type of maintenance
-
-
Do not use the device as safety device
-
For repairs and for further information, contact the EVCO sales network; possible re-
turns without back shell will not be accepted.
3

USER INTERFACE

3.1

Device configuration

N.B.
Turn off the power after changing the configuration.
Accessing the procedure.
1.
The display will show:
Upper line
Lower line
Accessing the menu.
2.
The display will show:
Upper line
Lower line
3.
The display will show:
Upper line
Lower line
Setting configuration parameters of menu "PAr".
3.
The display will show:
Upper line
Lower line
4.
The display will show:
Upper line
Lower line
5.
6.
7.
The display will show:
Upper line
Lower line
8.
The display will show:
Upper line
Lower line
9.
10.
Returning to the previous displays.
11.
Remote user interfaces
Touch the DOWN key for 7 s.
Menu
InFo
Touch the UP or DOWN key to select a menu.
Menu
menu name.
Touch the SET key.
the parameter
the parameter value
Touch the SET key.
PSU
0000
Touch the SET key again.
PUSU
a value flashing
Touch the UP or DOWN key to set "-019".
Touch the SET key.
Touch the UP or DOWN key to select a parameter.
the parameter
the parameter value
Touch the SET key.
the parameter
the parameter value flashing
Touch the UP or DOWN key to set the value.
Touch the SET key.
Touch the ON/STAND-BY key a few times.
4

CONFIGURATION PARAMETERS

N.
PAR.
DEF.
"InFo" MENU (READ ONLY)
1
Prn
-
project number
2
Pru
-
project version
3
Prr
-
project revision
4
FUu
-
firmware version
5
FUr
-
firmware revision
6
FUS
-
firmware subversion
7
HUu
-
hardware version
8
HUr
-
hardware revision
N.
PAR.
DEF.
"PAr" MENU
9
BKIL
10
backlight intensity
10
BKIt
241
backlight timeout
11
EU3C
OFF
enable compatibility with Vled 3
N.
PAR.
DEF.
"nEt > IbuS" MENU (READ ONLY)
12
nOdE
4
INTRABUS node
13
StAt
-
INTRABUS status communication
14
n_rH
-
number of received INTRABUS
packages
15
n_tH
-
number of transmitted INTRA-
BUS packages
16
nErr
-
number of INTRABUS receipts in
error
17
BAud
-
INTRABUS baud rate
18
StPB
1
INTRABUS bit stop number
19
PrtY
2
INTRABUS parity
N.
PAR.
DEF.
"nEt > bLE" MENU (READ ONLY;
AVAILABLE IN EVJD900N2VWIV
AND EVJD920N2VWIV)
20
n_rH
-
number of BLE packages re-
ceived
21
n_tH
-
number of BLE transmitted re-
ceived
22
nErr
-
number of intercepted BLE er-
rors
23
BAud
-
BLE baud rate
24
StPB
1
BLE bit stop number
25
PrtY
2
BLE parity
N.
PAR.
DEF.
"diAG" MENU (READ ONLY)
26
MEm
-
EEPROM memory status
27
PSU
-
power supply voltage status
N.
PAR.
DEF.
"dEb" MENU
28
PSU
-
power supply voltage value
29
AI1
-
reserved
30
AI2
-
reserved
31
AI3
-
reserved
32
AI4
-
reserved
33
tI2C
-
incorporated sensor temperature
value
34
HI2C
-
incorporated sensor humidity va-
lue
N.
PAR.
DEF.
"dEb > un" MENU
35
dO1
-
reserved
36
AI1t
-
reserved
N.
PAR.
DEF.
"ConF" MENU
37
PSU
-
reserved
5

TECHNICAL SPECIFICATIONS

Purpose of the control device:
Function controller.
Construction of the control device:
Built-in electronic device.
Container:
White, self-extinguishing.
Category of heat and fire resistance:
D.
Measurements:
111.4 x 76.4 x 18.5 mm (4 3/8 x 3 x 3/4 in).
Mounting methods for the control device:
Wall mounting (with bolts and fastening
screws) or in 502E or 503E flush mounting
box (with fastening screws).
Degree of protection provided by the cover-
IP30.
ing:
Connection method:
Fixed screw terminal blocks for wires up to
Female Micro USB connector.
1 mm²
Maximum permitted length for connection cables:
Power supply: 10 m (32.8 ft)
USB port: 1 m (3.28 ft)
INTRABUS port: 10 m (32.8 ft).
Operating temperature:
From 0 to 40 °C (from 32 to 104 °F).
Storage temperature:
From -20 to 70 °C (from -4 to 158 °F).
Operating humidity:
Relative humidity without condensate from 5
to 95%.
Pollution status of the control device:
2.
Compliance:
RoHS 2011/65/EC
WEEE 2012/19/EU
REACH (EC) Regulation no. 1907/2006
EMC 2014/30/UE
Power supply:
12 VAC/DC
12 VAC (±15%), 50/60 Hz (±3 Hz), max.
10 VA not insulated
12 VDC (±15%), max. 10 W not insulated.
Earthing methods for the control device:
None.
Rated impulse-withstand voltage:
4 KV.
Over-voltage category:
III.
Software class and structure:
A.
Displays:
Two rows and function icons LCD display.
Alarm buzzer:
Built-in.
Incorporated sensors:
Bluetooth
Low
Energy
(only
in
temperature
EVJD900N2VWIV and EVJD920N2VWIV)
EVJD920N2VWIX and EVJD920N2VWIV).
Working range incorporated temperature and humidity sensor:
0... 40 °C (32... 104 °F)
10... 90 % of relative humidity.
Communications ports:
1 INTRABUS port
1 USB port.
MIN... MAX.
-
-
-
-
-
-
-
-
MIN... MAX.
0... 100
15
uneditable
in
EVJD920N2VWIX
and
EVJD920N2VWIV
0... 241 s
241 = always lit
30
uneditable
in
EVJD920N2VWIX
and
EVJD920N2VWIV
On... OFF
MIN... MAX.
1... 127
if EU3C = On, nOdE = 3
OK... Err
0... 999
0... 999
0... 999
19200
0... 2
0... 2
MIN... MAX.
0... 999
0... 999
0... 999
19200
0... 2
0... 2
MIN... MAX.
OK... Err
OK... Err
MIN... MAX.
-
-
-
-
-
-
-
MIN... MAX.
-
-
MIN... MAX.
-
R&TTE 1999/5/CE.
and
humidity
(only
in

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EVJD900N2VWIX and is the answer not in the manual?

Questions and answers

Summary of Contents for Evco EVJD900N2VWIX

  • Page 1 EVCO S.p.A. | EVJ LCD | Instruction sheet ver. 1.0 | Code 104JLCDA103 | Page 1 of 2 | PT 50/16 EVJ LCD Remote user interfaces Electrical connection CONFIGURATION PARAMETERS Example of electrical connection. PAR. DEF. “InFo” MENU (READ ONLY) MIN...
  • Page 2 EVCO S.p.A. | EVJ LCD | Instruction sheet ver. 1.0 | Code 104JLCDA103 | Page 2 of 2 | PT 50/16 ITALIANO Predisposizione per la programmazione PARAMETRI DI CONFIGURAZIONE alimentazione 12 VAC/DC non isolata Per predisporre il dispositivo per la programmazione, posizionare il micro switch 1 in ON.