Complying with and enforcing the regulations applying to installations where our products are destined to be used is the responsibility of the installer and the customer. AKO Electromecànica accepts no liability for damage which may occur due to failure to comply with these regulations.
Using the equipment without following the manufacturer's instructions may affect the device's safety requirements. To ensure that the device operates correctly, only probes supplied by AKO should be used. Between -40 ºC and +20 ºC, if the NTC probe is extended up to 1,000 m with minimum 0.5 mm² wire, the maximum deviation will be 0.25 ºC (Wire for probe extension ref.
1763H532 Ed.02 3.- Recommendations Disconnect the voltage before carrying out any operations inside the electrical panel. All wiring should be according to current standards and should be carried out by authorised staff. Only carry out the wiring foreseen in the wiring diagrams.
1763H532 Ed.02 4.- Description Temperature Stand-by active mode Alarm active Compressor active (If P26=1) Defrosting in progress Condenser fans Evaporator fans active active Solenoid active Display Stand-by key Set Point key Defrost key Menu key 4.1.- Key function Pressing it for 5 seconds activates the Stand-By Pressing for 5 seconds accesses the quick mode.
1763H532 Ed.02 4.2- Messages Flashing 0: Access code (Password) request You must enter the access code configured on L5 to execute the requested function (p. 15). VSee also parameter P2 (p. 20) Probe 1 or 2 faulty (open circuit, crossover or temperature outside the probe limits; NTC: -50 To 99 ºC).
5.- Component location ATTENTION: Make sure to turn of the equipment's power supply before handling it, as different areas may be energised. IMPORTANT: The availability of the elements described depends on the panel model. AKO-17635-1, AKO-17635-2 Protection F1, FM Motor guard...
1763H532 Ed.02 6.- Quick configuration The quick configuration menu allows the unit to be configured for the most common applications. Press the for 5 seconds to access it. If the access code is activated, a 2 digit code is requested (See p. 15), if the code entered is not correct the unit will not enter programming.
1763H532 Ed.02 7.- Operation 7.1.- Compressor control probe 1 reaches the set NORMAL OPERATION When the temperature in probe 1 reaches the set differential of the probe point value (SP) plus the differential of the probe COMP. (C1), the compressor and solenoid are activated and the temperature drops.
Page 10
1763H532 Ed.02 COMPRESSOR PROTECTION DELAY There are three types of delay, selectable by parameter C4, to protect the compressor. These delays prevent continuous compressor starts and stops due to sudden changes in temperature. OFF-ON (C4=0): Minimum compressor OFF time before each start-up. OFF-ON / ON-OFF (C4=1): Minimum time during which the compressor will remain ON and OFF in every cycle.
1763H532 Ed.02 7.2.- Defrost control Max. d1 FAN START DELAY “DEF” MESSAGE DRIP CONTROL DEFROST CONTROL CONTROL DEFROST TIME ºC SP+C1 time Defrost start-up Defrost is initiated if: -Time scheduled in parameter d0 has passed since the beginning of last defrost. -The N key is pressed for 5 seconds.
1763H532 Ed.02 Other parameters Parameter d5 allows users to specify if the unit will (d5=1) or will not (d5=0) defrost when powered up (initial start-up or after a power failure). In case of choosing option YES (d5=1), the defrost will start after the delay time specified in d6.
1763H532 Ed.02 7.5.- Pump down function This function prevents compressor problems caused by movement of the refrigerant, using a stop/start technique of the unit controlled by liquid solenoid, the low pressure switch and the compressor. For this function to be active, it must be configured in parameter P26= 1. PARO When the temperature in probe 1 reaches the set point (SP) value, the liquid solenoid closes.
1763H532 Ed.02 7.6.- Alarms The unit warns the user by displaying an on-screen message when the programmed criteria are met. Max/Min Temperature Alarm Shows the AH or AL message when the temperature in probe 1 reaches the value set in the A1 (maximum temperature) or A2 (low temperature) parameters.
1763H532 Ed.02 Pump down malfunction error (Start up) Displays the LP message if a malfunction is detected when the installation is started up using the pump down manoeuvre. (See page 13). Compressor safety chain alarm The ASC message is displayed if any component in the compressor's safety chain is triggered (compressor motor guard, thermistors or high pressure controller).
1763H532 Ed.02 8.- Parameter transfer This function allows transferring the programmed parameters from one device to others, using the AKO-D14918 programming key. This will save a lot of time when configuring similar devices. Transfer parameters from the equipment to the key Connect the programming key in the parameter server connector.
1763H532 Ed.02 9.- Advanced configuration Using the advanced configuration menu, you can set ALL the equipment's parameters. The parameters are grouped into 6 sections depending on their function. To access it, press the SE key for 10 seconds. If the access code is activated, a 2 digit code is requested (See page 15), if the code entered is incorrect the unit will not enter programming mode.
1763H532 Ed.02 9.3.- Parameters The parameters are grouped into 6 sections depending on their function. To access it, press the key for 10 seconds. The Def. column shows factory-set default parameters. Temperature values are expressed in ºC. (Equivalent temperature in ºF) Level 1.- REGULATION AND CONTROL Description Units...
Page 19
1763H532 Ed.02 Level 1.- DEFROST CONTROL Description Units Max. (h.) d0 Defrost frequency (Time between two starts) (Page 11) d1 Maximum defrost duration (0=defrost deactivated) (Page 11) (min.) Type of message during defrost: (Page 11) 0=Current temperature; 1=Temperature at start of defrost; 2=Display dEF message (min.) Maximum duration of message (Time added at the end of the defrost process) (Page 11)
Page 20
1763H532 Ed.02 Level 1.- ALARM CONTROL Description Units Max. A0 Configuration of temperature alarms (Page 14): 0=Relative to SP 1=Absolute A1 Maximum alarm probe 1 (must be greater than SP) (Page 14) (ºC/ºF) 99,0 99,0 A2 Minimum alarm probe 1 (must be greater than SP) (Page 14) (min.) A3 Temperature alarm delay during start-up (Page 15) (min.)
Page 21
1763H532 Ed.02 Description Units Max. Configuring digital input 1 0= Off 1= Door contact 2= External alarm 3= Severe external alarm 4= Change Set Point 5=Remote defrost Configuring digital input 2 0= Off 1= Door contact 2= External alarm 3= Severe external alarm 4= Change Set Point 5=Remote defrost Digital input polarity 1...