Record R 62 User Manual page 23

Service display
Hide thumbs Also See for R 62:
Table of Contents

Advertisement

→ ALARMING
→ General
→ PAutoReset
→ TTechAlarmDelay
→ TLedIntervall
→ TMatAlarmDelay
→ PEntranceFlash
→ TPubOpenDelayTech
→ TSecOpenDelayTech
→ Buzzer
→ TTechAlarm
→ TOnTime
→ Public door
→TWrongPos
→ TNotOpNotCl
→ TForcedOpen
→ Secure door
→TwrongPos
→ TNotOpNotCl
→ TForcedOpen
→ LIGHT
→ PPowerSave
→ TPowerSave
→ TOffDelay
BAL_SD_R62_EN_2V3_BLA_121-006454377
ON
Selection to switch automatic reset ON or OFF when
alarm is no longer active
30 (sec)
Delay time to active alarming in case of a technical
alarm
1 (ds)
Traffic lights blinking interval during alarm
60 (sec)
Delay time when alarm is from door drives or faulty
sensor
0
Flashing light on the entrance indicates the type of
alarm:
0 = all alarms
1 = intrusion
2 = tailgaiting
3 = technical alarm
4 = sabotage
5 (ds)
Delay time opening public door in case of technical
alarm
5 (ds)
Delay time opening secure door in case of technical
alarm
10 (min.)
Time between repeating signaling with the buzzer when
technical alarm is still active
5 (ds)
Time the buzzer is on
30 (sec)
Delay time alarming public door does not open or close
10 (sec)
Delay time alarming while public door is between open
and closed position
10 (ds)
Delay time for alarming when the public door is closed
and is no longer sending an opening impulse to the PLC
30 (sec)
Delay time alarming secure door does not open or close
10 (sec)
Delay time alarming while secure door is between open
and closed position
10 (ds)
Delay time alarming when the secure door is closed and
is no longer sending an opening impulse to the PLC
ON
Power save mode activated ON or deactivated OFF
30 (min.)
Delay time before light is switched off when door is not
used
20 (ds)
Delay time to switch off the lights (when changing the
operating mode)
Commissioning
23 / 30