Global Fire Equipment ZEOS-AD-S Manual

Analogue algorithmic addressable fire detector

Advertisement

Quick Links

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560
Email: info@globalfire-equipment.com | Technical Support: techs@globalfire-equipment.com | www.globalfire-equipment.com
SUPPLY VOLTAGE
CURRENT - QUIESCENT / SURGE
CURRENT - DEVICE IN ALARM
SENSITIVITY / CABLE SIZE
RESET/START-UP TIMES
COLOUR / CASE MATERIAL / MAX. HUMIDITY
NORMAL / TRANSIENT OPER. TEMPERATURE
DIMENSIONS / WEIGHT
ORDER CODE
ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR
ZEOS-AD-S
ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR
ZEOS-AD-H
ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR
ZEOS-AD-SH
ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR WITH ISOLATOR
ZEOS-AD-SI
ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR WITH ISOLATOR
ZEOS-AD-HI
ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR WITH ISOLATOR
ZEOS-AD-SHI
INSTALLING THE BASE - To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat against terminals and
fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard electrical junction boxes.
INSTALLING THE HEAD - Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on base. Fit the
detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit and activate the detection loop. Test the detectors as
described below.
TESTING - All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at the conclusion of testing.
SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector's smoke chamber for at least 10 seconds. When sufficient smoke has entered, the detector will
signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make sure to clear smoke out of the chamber before resetting in order to keep the detector at
its current sensitivity setting.
HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can be met by some domestic hair dryers.
Switch on the warm airflow and check that the temperature is correct and stable. From a distance of several cms, direct the airflow at the guard protecting the thermistor. The
detector should alarm within 60 seconds. Upon alarm immediately remove the heat source and check that the Red LEDs of the detector are illuminated. If a detector fails to
activate within 60 seconds, confirm connections and programming.If necessary, replace the unit.
NOTE: After testing, check that the system is returned to normal operation.Notify the appropriate authorities that the testing procedure has been completed and the system is
active again.
MAINTENANCE - The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low power
vacuum cleaner.
ZEOS-AD
ANALOGUE ALGORITHMIC
ADDRESSABLE FIRE DETECTOR
GLOBAL FIRE EQUIPMENT S.A.
TECHNICAL SPECIFICATIONS
Loop Powered - 17V to 30V DC
450uA max.
4 mA - Alarm LED illuminated
According to EN54-5 and EN54-7 / 0.5-2.5 mm²
20 seconds max.
White / ABS / 95% RH Non-Condensing
0°C to 50°C / -10°C to 85°C
100 (D) x 50 (H) mm included base / 92g without base & 144g inc. base
For EN54-13 compliance, please check the control panel manual specifications.
DESCRIPTION
INSTALLATION
DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR.
DETECTOR BASE - LOOP CONNECTIONS
MANUAL 210729
MADE IN PORTUGAL - EU
CERTIFICATE
1328-CPR-0521
1328-CPR-0520
1328-CPR-0519
1328-CPR-0607
1328-CPR-0610
1328-CPR-0492
NOTE:
Positive terminal
of remote indicator
should be connected
to terminal 4
(+ Loop IN/OUT).

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZEOS-AD-S and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Global Fire Equipment ZEOS-AD-S

  • Page 1 ADDRESSABLE FIRE DETECTOR MADE IN PORTUGAL - EU GLOBAL FIRE EQUIPMENT S.A. Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560 Email: info@globalfire-equipment.com | Technical Support: techs@globalfire-equipment.com | www.globalfire-equipment.com...
  • Page 2 MECHANICAL SPECIFICATION BASE LOCK To unlock detector from its base push provided unlock key through hole available on the base side wall as shown. D.I.L. SWITCHES CONFIGURATION Address Switches binary weights Switches 1-7 1 ON =1 4 ON =8 7 ON =64 Used to configure the module’s address.

This manual is also suitable for:

Zeos-ad-hZeos-ad-shZeos-ad-siZeos-ad-hiZeos-ad-shi