LG LAN181CNW, LAU181CNW, LA180CPI, LA180CPO Service Manual page 55

Lg room air conditioner service manual
Hide thumbs Also See for LAN181CNW, LAU181CNW, LA180CPI, LA180CPO:
Table of Contents

Advertisement

2. Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Check the voltage of power(About AC 208V/AC230V, 60Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting
cable
• Check PWB Ass'y(Outdoor unit)
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
• Connector related to CN-POWER
• Connector related to CN-FAN
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Ass'y Check
• Connector related to CN-DC/DC
Items
• Power Transformer
(Outdoor unit)
- Input Voltage
- Output Voltage
• IC01D(7812) Output
(Indoor/Outdoor unit)
• IC02D(7805) Output (Indoor unit)
IC04D(7805) Output (Outdoor unit)
• IC01A(KIA7036, Reset IC)
OSC01B(4MHz)
(Indoor/Outdoor unit)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
NO
PCB Board Operation Check
- About AC 208V/AC 230V ± 10%
- Check the power voltage
- About DC15V ± 3
• DC + 12V
• DC + 5V
• Voltage of Outdoor unit Micom No. 18,
Voltage of Indoor unit Micom No. 43 and
soldering condition
(After 20 seconds)
Primarily, the operating condition of Micom is OK.
Check each load(Indoor/Outdoor Fan Motor, Com-
pressor,
Stepping
condition of related connector(including connecting
cable of Indoor/Outdoor Unit)
Content
Cycle Troubleshooting Guide
YES
Motor)
and
contacting
Remedy
• Replace SMPS Mod-
ule
• Replace IC01D
• Replace
IC02D(Indoor unit)
IC04D(Outdoor unit)
• Replace faulty parts
Service Manual 55