Wireless Input Output Unit
Installation Guide
1 Pre installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if
mounting the device on to a metal surface.
Do NOT Press the Log On button on a pre-programmed
device, as this will cause communication with the Control
Panel to be lost. Should this happen, delete the device from
the system and add it back on.
This device contains electronics that may be susceptible to
damage from Electrostatic Discharge (ESD). Take appropriate
precautions when handling electronic boards.
3 Remove cable entry points
Drill the cable entry
points as necessary.
Cable glands should
be used.
DO
NOT
leave
excess cable in the
device.
5 Input wiring
Two resistor monitored inputs are
available.
Both inputs monitor; closed (alarm),
open and short circuit conditions.
Each input is factory fitted with an
end of line 20 kΩ resistor.
To
connect
inputs
devices, wire as shown below. I.e.
Input 1, using the resistor pack
provided.
If an input is not being used, leave
the 20 kΩ resistor as factory fitted.
©2021 EMS Ltd. All rights reserved
FC-610-001
DUAL I/O UNIT
Do Not Use
Cable Entry
INPUT 1
INPUT 2
IP-
IP+
IP-
20k
4k7
to
external
C
N/O
Remote Monitored Device
Part no
FC-610-001
2 Components
1
4x lid fixing screws
4 Fix to the wall
Use all four circled
fixing
ensure a firm fixing.
=
Use suitable fasteners
and fixings.
=
Available
Points
Fixing position
location within
cavity
6 Output wiring
Two outputs are also available.
IP+
Both outputs are voltage
Note: Max
free and rated 2 A at 24 VDC.
Cable Length
of 10m
WARNING. DO NOT CONNECT TO MAINS.
!
EOL
Resistor
Setup
Page 1 of 2
Product description
Wireless Dual Input/Output Unit
1
2
2
Front lid
positions
to
N/O COM N/C N/O COM N/C
TSD050-99 Iss 15 23/11/2021
3
IDENT REV DATE
3
Back box
LOGON
ANTENNA
012ABC
KEEP CABLES AWAY FROM THIS AREA
0
1
1
2
4
8
16
32
64
CLOSED
F-SAFE
LED
ENABLE
FAULT
INPUT 1 INPUT 2
EXPAN1
EXPAN2
OUTPUT 1
OUTPUT
2
IP- IP+ IP- IP+
3VDC SET RST
3VDC SET RST
N/O COM N/C
N/O COM N/C
OUTPUT 1
OUTPUT 2
AJM

Advertisement

loading

Summary of Contents for EMS FireCell FC-610-001

  • Page 1 Input 1, using the resistor pack Setup provided. If an input is not being used, leave Remote Monitored Device the 20 kΩ resistor as factory fitted. ©2021 EMS Ltd. All rights reserved Page 1 of 2 TSD050-99 Iss 15 23/11/2021...
  • Page 2 IP rating IP65 radio links. Operating frequency 868 MHz European Union EMS declares that this device is in compliance with directives Directive 2014/53/EU. The full text of the EU Output transmitter declaration of conformity is available at the following power Auto adjusting 0 to 14 dBm (0 to 25 mW) internet address: www.emsgroup.co.uk...