Wireless Input Output Unit
Installation Guide
1 Pre Installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if
mounting the device on to a metal surface.
Do NOT Press the Log On button on a pre-programmed
device, as this will cause communication with the Control
Panel to be lost. Should this happen, delete the device from
the system and add it back on.
3 Remove Cable Entry Points
Drill the cable entry
points as necessary.
Cable glands should
be used.
DO
NOT
leave
excess cable in the
device.
5 Input Wiring
Two resistor monitored inputs are
available.
Both inputs monitor; closed (alarm),
open and short circuit conditions.
Each input is factory fitted with an
end of line 20kΩ resistor.
To
connect
inputs
to
devices, wire as shown below. I.e.
Input 1, using the resistor pack
provided.
If an input is not being used, leave
the 20kΩ resistor as factory fitted.
©2015 EMS Security Group Ltd. All rights reserved
All manuals and user guides at all-guides.com
FC-610-001
DUAL I/O UNIT
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
Do Not Use
Available
Cable Entry
Points
INPUT 1
INPUT 2
IP-
IP+
IP-
IP+
Note: Max
Cable Length
of 10m
20k
4k7
external
Resistor
N/O
C
Remote Monitored Device
Part No
Product Description
FC-610-001
Wireless Dual Input/Output Unit
2 Components
1
4x Lid Fixing Screws
4 Fix to the Wall
Use all four circled
fixing
positions
ensure a firm fixing.
=
Use suitable fasteners
and fixings.
=
Fixing position
location within
cavity
6 Output Wiring
Two outputs are also available.
Both outputs are voltage
free and rated 2A @ 24Vdc.
!
WARNING. DO NOT CONNECT TO MAINS.
EOL
Setup
Page 2 of 2
1
2
3
IDENT REV DATE
2
Front Lid
3
to
LOGON
KEEP CABLES AWAY FROM THIS AREA
0
1
1
2
4
8
16
32
64
CLOSED
F-SAFE
LED
ENABLE
FAULT
INPUT 1 INPUT 2
IP- IP+ IP- IP+
OUTPUT 1
N/O COM N/C N/O COM N/C
TSD050 Iss 12 09/02/2016
Back Box
ANTENNA
012ABC
EXPAN1
EXPAN2
OUTPUT 1
OUTPUT
2
3VDC SET RST
3VDC SET RST
N/O COM N/C
N/O COM N/C
OUTPUT 2
AJM