Planning wire topology to meet EN 54-2 requirements on integrity of transmission paths... 7 ....................... 7 HYSICAL MOUNTING INSTRUCTIONS 4.2.1 Panel assembly ..........................7 4.2.2 Assembly of JBE-P2L1-EXLP (Draco 2nd Loop Card) ................ 7 4.2.3 Assembly of JBE-PRT (Draco Printer) ....................8 4.2.4 Assembly of JBE-BAT (Draco battery box) ..................8 4.2.5 Mounting to the wall ........................
Page 4
Field device state signal value ........................29 5.5.4.7 View advanced programming ........................29 5.5.4.8 View addresses linked to a zone ....................... 29 5.5.4.9 View addresses used in a loop ........................29 Page ii JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 5
& R 2) ..................47 PERATE EPORT MENUS SER ACCESS LEVEL & I 3) ................... 48 DJUST NSTALL MENUS SER ACCESS LEVEL LIST OF FIGURES ..........................49 Page iii JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Introduction This manual contains the information and instructions necessary to install, commission, operate and maintain the JBE-P2L1 (Draco) fire control panel. Only qualified professional technicians should install this panel. Incorrect installation may not provide the expected performance of fire safety devices.
Page 7
Three sensitivity profiles (Day, Night and Special) can be programmed and assigned to the weekly time periods. This allows selecting the most convenient sensitivity for each detector in each moment of the week. Page 2 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
C. Tarragona, 157. 08014 Barcelona (Spain) DoP-0370-CPR-3813-1 EN 54-2, EN 54-4 JBE-P2L1 Draco Fire Control Panel Technical file: see TF-JBE-P2L1-10 provided by the manufacturer. Jade Bird Fire Alarm International (Europe), S.L. C. Tarragona, 157. 08014 Barcelona (España) www.jadebird.eu.com Page 3 JBE-P2L1 Panel Manual V1.2 EN...
3.5.1 Second loop card (JBE-P2L1-EXLP) The second loop card (JBE-P2L1-EXLP) can be added to the main loop card to expand the panel into a two (2) loop panel. The second loop has the same capabilities as the first loop in the number of devices and power limits.
440 x 120 x 126 mm Weight 1 kg Draco Battery Box Dimensions (WxHxD) 440 x 250 x 126 mm Weight (including 17 Ah batteries) 14 kg Page 6 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
4.2.2 Assembly of JBE-P2L1-EXLP (Draco 2nd Loop Card) 1. While the panel is unpowered, open the fire panel’s cabinet using the provided key. 2. Align the connectors in the JBE-P2L1-EXLP expansion board with the connectors J2 and J4 of the main loop card (JBE-P2L1-LOOP) and push firmly.
5. Use the 2x provided nuts to fasten the printer to the panel’s main housing. Tighten firmly. 6. Route the provided flat ribbon cable through to the opening between the panel and the printer. 7. Connect the flat ribbon cable to connector J3 in the panel’s display board (PCB JBE-P2L1 DP) and to the printer.
Thanks to this screw, the operation can be performed by a single operator Figure 2: First screw for center keyhole Page 9 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
When manipulating the panel interior and wires, be aware of the risk electric shock and electric voltage. Ensure proper lock out / tag out procedures are followed before manipulating the panel or its wiring. Page 10 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 16
3. With the panel secure, run the mains power line into the panel and secure it to the provided mains terminal block. Figure 5: Mains Connections This equipment must always be earthed Page 11 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Do not mix different battery capacities. Observe the battery manufacturer’s recommendation on shelf life and expected service life. Note that batteries pose severe hazards. Read the safety manual of the batteries before handling them. Page 12 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 18
3. Insert again the battery holder brackets. Tighten screws thoroughly. 4. Connect the battery cable terminals 5. Verify the temperature sensor is placed near the batteries to provide adequate temperature feedback to the charging circuit. Page 13 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
After auto-registration, all devices will have been assigned to zone 1. Use this menu to select the desired detection zone for each initiating device (see 4.5.1.3). Page 14 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Advanced Installation menu (see 4.5.1.6). 4.3.6 Change passwords Select the desired passwords for user access level 2 and user access level 3. Page 15 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
The following figure and table detail the information on the definitions of the panel LED indicators. The Draco panel features a simple, icon-based method to communicate the key events of the panel as illustrated in Figure 11 Figure 10: LED Indicators Page 16 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 22
There is a fault affecting FR Blinking outputs The CIE is supplied with power Power ON Green Steady ON (from mains or from the battery) Page 17 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
3. Contextual display area. This area is where the navigation menus will be displayed. In addition, where the alarm, fault, test and cancellation events will be presented. Figure 11: Quiescent screen Page 18 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
The Draco panel features soft buttons and alphanumeric keys which allow users to navigate the system directly from the keypad, even when they are wearing work gloves. Figure 12: Control keys and alphanumeric keyboard Figure 13: Function Keys Page 19 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Fast beep: The buzzer sounds 3 times per second The panel is in fire alarm condition Slow beep: The buzzer beeps once per second The panel is in the fault condition Page 20 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Users can review all previous and ongoing event information from the View menu by pressing either control keys (refer to Figure 12) or function keys (refer to Figure 13). Page 21 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
(if the optional printer is attached), press F4 to return to the previous page, press F5 scroll down to the next page, and press F6 to exit the current interface. Page 22 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Press F1 to return to the first page, press F2 to view previous page, press F3 to view next page, press F4 to page up, press F5 to page down, press F6 to exit. Page 23 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
To exit the current interface, press F6. 5.4.2.8 Product serial numbers Press the Home key and then F1, press 8 to access the Serial Number menu. Page 24 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
1. Test zone 2. Test output group 3. Keyboard test 4. Indicators test 5. Disable zone 6. Disable output group 7. Disable device 8. Set time and date Page 25 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
(sounder group, fire routing group) from the main sub-menu by entering in a 1 for yes using the directional keys and the numeric keypad. A programmable group or field devices can be selected by pressing F2 or F3. Page 26 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Enter the Set time menu to adjust the date and time of the panel by using the numeric and directional keypads, press F1 to clear the data, F5 to confirm and F6 to exit. Page 27 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
This menu shows the status information of the current type of the selected device of the designated loop. By pressing F2 or F3, the user can change the address of the device to consult. Page 28 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
A new zone number can be assigned to each device by changing the number under the Set column and pressing F5 to confirm the changes. Page 30 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Note that local regulations may require that no more than 32 devices are lost in case of a single wiring fault. Therefore, class B wiring topology may only be used in smaller installations. Page 31 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 37
Class A is the most robust wiring topology and thus the recommended topology for all installations. Figure 14: Topology Classes Page 32 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
The screen to configure the schedule divides the week in up to 14 time periods. Each time period will also be assigned one of the following 3 profiles: L1 – “Day” profile L2 – “Night” profile L3 – “Special” profile Page 33 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 39
Push “F3” to configure the desired sensitivity level of each detector for each profile. Refer to the detector’s datasheet to understand the details of each sensitivity level. Figure 16: Detector Sensitivity Selection Page 34 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
From this sub-menu, users can change/setup both the operator and installer password. 5.6.2.4 Set language From this sub-menu, users can select the system language from the list of languages available on the panel. Page 35 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
1 Detectors from zone 001 OR 1 Detector from zone 002 AND 1 MCP from zone 002 OR 1 Input from zone 003 Page 36 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 42
Warning: EN54 does not allow automatic muting of siren groups or FR outputs. Activation groups 001 and 002 must remain active until the manual intervention of the user. Page 37 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 43
That is: Scenarios S(x,y,z) are considered to return “1” if they are met and “0” otherwise. All output groups at the rightmost hand side of the “=” sign will be activated if the calculation of input functions returns “1". Page 38 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 44
One detector AND one MCP in any zone. Please note that this setup requires sirens to unlink from zones. See section 5.6.1.4 for more information on unlinking SND outputs from panel default operation. Page 39 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
5.6.3 Online Configuration Tool All JBE-P2L1 Draco panel configurations can be done thanks to its intuitive user interface. However, you can also create, edit or store your own configuration by registering on our Web site. Loading or downloading settings to and from the panel can be done using an USB.
From this submenu, the users can upgrade the panel FW version. Languages / image From this submenu, the users can update the languages available on the panel. Page 41 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
The rest of menus can be accessed normally, but the fire alarm screen will be presented again within 30 seconds of no activity in the user interface. Page 42 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Therefore, the system will immediately enter again into alarm status if fire stimulus (from detectors and/or manual call points) are still present. Page 43 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
When a common device fault is reverted (i.e. a removed detector is connected again), the panel will clear this fault indication and return to the quiescent functional condition. The event log will keep record of all faults detected. Figure 21: Fault Screen Page 44 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
System faults are not expected to appear during normal operation. The system should not be considered reliable while it is indicating a system fault. Contact your maintenance company or technical support if a system fault is present in your system. Page 45 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Make sure the interior and exterior of the control panel is free from dirt. Perform periodic basic cleaning by using a cloth to dust the exterior. Do not use chemical products to clean the panel. Page 46 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
6. Field device data report 7. Field device state signal value 8. View advanced programming 9. View addresses linked to a zone 0. View addresses used in a loop Page 47 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
6. Enter advanced programming 1. Clear descriptions 2. Clear all zone info 7. Clear 3. Clear Advanced programming 4. Load a factory setting 8. System configuration Page 48 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Figure 18: Example Output Action ........................ 38 Figure 19: Advanced Programming Example ....................39 Figure 20: The alarm screen ......................... 43 Figure 21: Fault Screen ..........................44 --END OF DOCUMENT— Page 49 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...
Page 55
- Blank page - Page 50 JBE-P2L1 Panel Manual V1.2 EN Rev 01 Release Date: January 5, 2021...