ABB SPAF 140 C User Manual And Technical Description page 25

Frequency relay
Table of Contents

Advertisement

Switchgroup SGF6
Switchgroup SGF7
Selection of the output signal controlling the
TRIP indicator on the front panel. When the
switch linked to a certain signal is in position 1,
the TRIP indicator is lit once the signal is acti-
Switch
Function
SGF6/1
The SS1 signal activates the TRIP indicator and starts the recovery
function.
SGF6/2
The TS1 signal activates the TRIP indicator and starts the recovery
function.
SGF6/3
The SS2 signal activates the TRIP indicator and starts the recovery
function.
SGF6/4
The TS2 signal activates the TRIP indicator and starts the recovery
function.
SGF6/5
The SS3 signal activates the TRIP indicator and starts the recovery
function.
SGF6/6
The TS3 signal activates the TRIP indicator and starts the recovery
function.
SGF6/7
The SS4 signal activates the TRIP indicator and starts the recovery
function.
SGF6/8
The TS4 signal activates the TRIP indicator and starts the recovery
function.
∑ SGF6
The switchgroup SGF7 is used for selecting the
rated voltage of the relay module.
Switch
100 V
SGF7/1
0
SGF7/2
0
SGF7/3
When the switch is in position 1,
the selected rated voltage is divided by √3.
Then the following voltages are received:
57.7 V
SGF7/4...8
Not in use
∑ SGF7
vated. At the same time the concerned signal
starts the recovery function, provided the recov-
ery output is in use (selected with SGR9/_ ).
Rated voltage
110 V
115 V
1
0
0
1
63.5 V
66.4 V
Factory
setting
0
1
0
1
0
0
0
0
10
Factory
120 V
setting
1
0
1
0
0
69.3 V
0
0
11