ABB SPAF 140 C User Manual And Technical Description page 26

Frequency relay
Table of Contents

Advertisement

Switchgroups
SGB1...6
12
The switchgroups SGB1...6 are used for confi-
guring the control signals BS1...BS5. The ma-
trix below can be used for the programming.
The control signals and the desired functions
are linked to each other, for instance, by circling
the intersection of the lines. Each intersection
t 1
t 1 '
BS1
1
BS2
1
BS3
1
BS4
1
BS5
1
undervoltage
blocking
1
weighting
value
1
Fig. 4. Control signal matrix for relay module SPCF 1D15
Switch
Function
SGB_/1...4
Blockings to be applied to the separate protection stages using
control signals BS1...BS6.
When a switch is in position 1, tripping by the concerned protection
stage will be blocked, when the control signal is activated.
SGB_/5
Blockings to be applied to the recovery stage using control signals
BS1...BS6
SGB_/6
Switching between main settings and second settings
If an external control input is used, the main setting values are active
when no control voltage is applied to the input, whereas the second
setting values are active, when the control input is energized.
SGB_/7
Resetting of front panel operation indicator
SGB_/8
Resetting of front panel operation indicator and registers
∑ SGB1
∑ SGB2
∑ SGB3
∑ SGB4
∑ SGB5
∑ SGB6
is marked with the number of the switch to be
used and the weighting factor of the switch is
given under the matrix. By adding the weight-
ing factors of the switches selected in each
switchgroup, the checksums shown to the right
of the matrix are received.
t 2
t 2 '
t 3
t 3 '
t 4
2
3
4
2
3
4
2
3
4
2
3
4
2
3
4
2
3
4
2
4
8
main
t 4 '
recovery
indicators
indicators
function
registers
second
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
16
32
64
128
Checksum
(Default setting)
Σ SGB1=
(Σ=1)
Σ SGB2=
(Σ=2)
Σ SGB3=
(Σ=4)
Σ SGB4=
(Σ=8)
Σ SGB5=
(Σ=0)
Σ SGB6=
(Σ=15)
Factory
setting
1
2
4
8
0
15