Summary of Contents for GÜDE Expert Power Control 8001

  • Page 1 Manual Expert Power Control 8001 © 2022 GUDE Systems GmbH Manual Ver. 1.0.1 from Firmware Ver. 1.0...
  • Page 2 Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 3: Table Of Contents

    Clock ..........................38 3.4.1 NTP ......................... 38 3.4.2 Timer ........................39 3.4.3 Timer Configuration ....................39 Sensors .......................... 46 3.5.1 Port Switching ......................47 E-Mail ..........................49 Front Panel ........................50 Specifications Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 4 4.9.1 Sensor Tables ......................86 4.10 MQTT ..........................87 4.10.1 Example HiveMQ ....................89 Support Data Security ........................ 92 Contact .......................... 92 Declaration of Conformity ..................93 FAQ ..........................93 Index Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 5 Device Description...
  • Page 6: Device Description Security Advice

    · Expert Power Control 8001 · Quick Start Guide Description The Expert Power Control 8001 can switch 5 load outputs (PCB terminal, max. 16 A), that are fed from a mains connection (IEC C20, max. 16A) . The device has the following features: ·...
  • Page 7: Installation

    · Firmware update during operation via Ethernet possible · Encrypted e-mails (SSL, STARTTLS) · Access protection through IP access control · Low own consumption · Developed and produced in Germany Installation Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 8: Technical Specifications

    Load outputs 5 x load outputs (PCB terminal, max. 16 A) Network connection 10/100 MBit/s 10baseT Ethernet Power supply internal power supply (100-240 V AC / -15% / +10%, 50-60 hz) Environment Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 9: Electrical Measurement

    Apparent power 0 - 4000 < 1.5% Power factor 0 - 1 0.01 < 3% Energy Counter Active Energy 9.999.999,999 0.001 < 1.5% (total) Active Energy 9.999.999,999 0.001 < 1.5% (resettable) Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 10: Sensor

    Device Description Sensor Two external sensors can be connected to the Expert Power Control 8001. The follow- ing sensors are currently available Product Name 7101 7104-1 7105-1 7106-1 Calibrated 7104-2 7105-2 7106-2 Sensor Cable length Connector RJ45 RJ45 RJ45 RJ45 temperature range -20°C to +80°C at...
  • Page 11 A click on the link in the "Name" column opens the display of the Min and Max values. The values in a column can be reset using the "Reset" button. The "Reset" button in the name column deletes all stored Min and Max values. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 12: Operating

    Operating...
  • Page 13: Operating The Device Directly

    · green: The device is connected to the Ethernet and the TCP/IP settings are allocated. · periodic blinking: The device is in Bootloader mode. Control Panel Access the web interface: http://"IP-address" and log-in. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 14 An activated Watchdog is represented by an eye icon. An "X" means, that the address that should be observed, could not be resolved. Two circular arrows show a booting status. In addition to the panel, the Expert Power Control 8001 shows the measured values of the selected port: Expert Power Control 8001...
  • Page 15: Maintenance

    Only now, pressing the "Apply" button will permanently update the data, or abort with "Cancel". Only one upload function can be initiated with a reboot, eg. you cannot transmit firm- ware and configuration at the same time. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 16 The GBL_Conf.exe program is available free of charge on our website www.gude.info and can also be found on the enclosed CD-ROM. Interface GBL_Conf Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 17: Maintenance Page

    If a unit is set to factory defaults, an uploaded certificate or updated firmware will be preserved. 2.3.1 Maintenance Page This section provides access to important functions such as Firmware Update or Restart Device. It is advisable to set an HTTP password for this reason. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 18 Enter Bootloader Mode: Jumps into bootloader mode, where additional settings can be made with GBL_Conf.exe. Flush DNS Cache: All entries in the DNS cache are discarded and address resolutions Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 19: Configuration Management

    It may be desirable to make the changes relative to the current configuration, and not out of the factory state. Then the "system fabsettings" should be removed. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 20: Bootloader Activation

    · Hold down the "Select" button. If the push button is recessed, use a pin or paper clip · Connect the operating voltage 3) by Software: · Start the "GBL_Conf.exe" program · Do a network search with the "Search" menu action Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 21 If the push button is recessed, use a pin or paper clip · The status LED will blink in a fast rhythm, please wait until the LED blinks slowly (about 5 seconds) Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 22 · In menu "Program Device" activate the item "Reset to Fab Settings" · The status LED will blink in a fast rhythm, please wait until the LED blinks slowly (about 5 seconds) Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 23: Configuration

    Configuration...
  • Page 24: Power Ports

    Initialization delay: Here can be configured how long the port should wait to switch to its defined state after the device is turned on. The delay may last up to 8191 seconds. This Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 25: Watchdog

    You can monitor devices on your own network, as well as devices on an external net- work, e.g. the operating status of a router. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 26 If this option is activated, a watchdog is also triggered if the Ethernet link is down. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 27: Ethernet

    During this time the IP-address is not accessible! It is therefore essential to deactivate DHCP for a static IP addresses! Use IPv6 Protocol: Activates IPv6 usage. Use IPv6 Router Advertisement: The Router Advertisement communicates with the router Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 28 The input fields for the manual setting of IPv6 addresses allow you to configure the prefix of four additional IPv6 device addresses, and to set two DNS addresses, and a gateway. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 29: Ip Acl

    If you choose a wrong IP ACL setting and locked yourself out, please activate the Bootloader Mode and use GBL_Conf.exe to deactivate the IP ACL. Alternatively, you can reset the device to factory default. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 30: Http

    Users can log in by entering the user password in order to query the status information and initiate switching operations. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 31: Protocols

    SHA2-256 hash. If you want to change a password, the complete password must always be re-entered. If you have forgotten your password, please activate the bootloader mode and then turn off the password prompt in GBL_Conf.exe. Protocols 3.3.1 Console Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 32: Syslog

    Enable Syslog: Enables the usage of Syslog Messages. Syslog Server: If you have enabled Syslog Messages, enter the IP address of the server to which the syslog information should be transmitted. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 33: Snmp

    Because of security issues, it is advisable to use only SNMP v3, and to disable SNMP v2. Accesses to SNMP v2 are always insecure. Community public: The community password for SNMP GET requests. Community private: The community password for SNMP SET requests. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 34 MIB table: The download link to the text file with the MIB table for the device. More information about SNMP settings are available from our support or can be found on the Internet at www.gude.info/wiki. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 35: Radius

    Backup Server: Name or IP address of the Radius Backup server. Shared secret: Radius Shared Secret. For compatibility reasons, only use ASCII charac- ters. Timeout: How long (in seconds) will be waited for a response from an Authentication Request. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 36: Modbus Tcp

    The "Test Radius Server" function allows you to check whether a combination of User- name and Password is accepted by the configured Radius Servers. 3.3.5 Modbus TCP Enable Modbus TCP: Enables Modbus TCP support. Modus TCP port: The TCP/IP port number for Modbus TCP. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 37: Mqtt

    [mac] and [host] symbolize the MAC address or the hostname of the device. Permit CLI commands: Enables the execution of console commands. Publish device data summary interval: Time interval in which messages with the global status of the device are sent. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 38: Clock

    Primary NTP server: IP address of the first NTP server. Backup NTP server: IP address of the second NTP server. Used when the first NTP server does not respond. Timezone: The set time zone for the local time. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 39: Timer

    This instruction chapter applies to all Gude devices. For devices without switchable ports you can only create a complex timer. For an action there is only the register "Ac- tion CLI" available, and not the register "Action PortSwitch". Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 40 "Save" saves this rule. We have now created 2 rules, one for when the port is turned on and the second for when it is turned off. Creating a complex timer Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 41 Ports are switched as action mode, alternatively a console command (CLI Cmd) can be executed. After changes to existing timers, the "Rule Name" may no longer be meaningful. To keep the overview, it may be useful to adjust the name. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 42 9:30 and 17:10 in a single timer rule. You need a second rule for this. If you set the hours 9 and 17, as well as the minutes 10 and 30, then the four times 9:10, 9:30, Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 43 In this example, port 1 and port 5 are enabled and disabled after 90 minutes by batch mode. A popup on the mouse pointer shows the port number of the field. Console Commands Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 44 Switch port 3 on every day at 9:25, and off again at 17:30. You save. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 45 The jitter of 1800 seconds means that the action is executed randomly in a period between 30 minutes before and 30 minutes after the programmed time. The probability (Random Trigger Probability) of execution here is 100%. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 46: Sensors

    E-Mail. Hysteresis: This describes the margin of when an event is generated after the measured value has crossed the chosen limit. Message channels: Enables the generation of messages on different channels. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 47: Port Switching

    Example with "Maximum value" of 65 °C, "Minimum value" of 25 °C and hysteresis of 3 ° C. The dotted line shows the hysteresis. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 48 Only the switching operations for which actions have been defined, are triggered. If no "On" or "Off" action is defined for a port, the port can never reach this state by ex- ceeding sensor values. Unless it is the initial state. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 49: E-Mail

    If you want to change a password, the complete password must always be re-entered. E-Mail Logs: Logging of E-Mail system messages. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 50: Front Panel

    Button Lock: Disables the front buttons (activates the key lock) with the exception of the bootloader activation. Allow switching all ports: Allows to switch all ports on or off with the front panel buttons. Display 1 default: Selects what sensor is displayed in the display. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 51: Specifications

    Specifications...
  • Page 52: Automated Access

    JSON data is explained in more detail in our Wiki article: http://wiki.gude.info/EPC_HTTP_Interface Messages Depending on adjustable events, various messages can be sent from the device. The fol- lowing message types are supported: Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 53 Syslog Email Global Device started Switch port Port watchdog status Syslog switched on/off MQTT connection established MQTT connection lost Value-Threshold external sensors Current Time-Interval external sensors Current Value-Delta external sensors Current Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 54: Ip Acl

    PCs, the device is not completely transparent. Due to technical restraints, a TCP/IP connection will be accepted at first, but then rejected directly. Examples: Entry in the IP ACL Meaning 192.168.0.123 the PC with IP Address "192.168.0.123" can access the device Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 55: Ipv6

    If the local password and RADIUS are enabled at the same time, the system is first checking locally, and then in the event of a failure the Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 56: Snmp

    (subtree name). The device's MIB table can be displayed as a text file by clicking on the link "MIB table" on the SNMP configuration page in the browser. SNMP v1 and v2c Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 57 Otherwise the device could be accessed with it. · If only authentication is used, then the new "HMAC-SHA-2" methods are superior to the MD5 or SHA-1 hashing algorithms. Since only SHA-256 is accelerated in hard- Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 58 OID: snmpwalk -v2c -mALL -c public 192.168.1.232 1.3.6.1.4.1.28507 NET-SNMP Examples Query Power Port 1 switching state: snmpget -v2c -mALL -c public 192.168.1.232 epc822XPortState.1 Switch on Power Port 1: snmpset -v2c -mALL -c private 192.168.1.232 epc822XPortState.1 integer 1 Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 59: Device Mib 8001

    .100.1.5.1.2.1.6.x Gauge32 Actual Voltage on Pow er Channel epc8001Frequency .100.1.5.1.2.1.7.x Gauge32 Frequency of Pow er Channel epc8001Pow erFactor .100.1.5.1.2.1.8.x Integer32 Pow er Factor of Channel betw een -1.0 and 1.00 Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 60 Pow er Factor of Channel betw een -1.0 and 1.00 epc8001spPangle .100.1.5.5.2.1.9.x Integer32 Phase Angle betw een Voltage and L Line Current betw een -180.0 and 180.0 epc8001spPow erApparent .100.1.5.5.2.1.10.x Integer32 L Line Mean Apparent Pow er Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 61 PointDiff .100.1.6.1.1.7.x Integer32 difference betw een dew point and actual temperature (Temp - Dew Point) epc8001ExtSensorName .100.1.6.1.1.32.x OCTETS A textual string containing name of a external Sensor Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 62: Ssl

    The server keys should be created with "openssl genrsa". The Gude device pro- cesses keys in the traditional PKCS#1 format. This can be recognized by the fact that the generated key file starts with "-----BEGIN RSA PRIVATE KEY-----". If the file starts Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 63: Console

    Raw Mode a simple TCP/IP connection is sufficient to send commands. The communication can also be performed automated (e.g. via scripting languages). The console features are configured through the web interface Command Set Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 64 0 and 5 can be set. In the help, this can be recognized by the fact that the values are not separated by the "|" character, but by commas. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 65 Telnet server will be returned. Normally the client begins with the IAC negotiation. If this is not the case with the client, the device configuration "Active negotiation" should be turned on. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 66 This command outputs all line sensor values in one line. A list of all fields (according to the energy sensor table) is transferred as parameter. In this example these are the fields Absolute Active Energy (0), Power Active (1), Voltage (2), Current (3) and Reset Time Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 67: Ssh

    The "login" must be enabled for SSH. Users and passwords can be stored locally or retrieved via a radius server. If you want to use SSH in a terminal, Activ- ate echo should be enabled. Public Keys Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 68 Here is an example to generate an ECDSA 384 key. ssh-keygen -t ecdsa -b 384 -f ssh.key In the file ssh.pub is then the private key, the content of ssh.key.pub is inserted into the field "Upload SSH public key:". Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 69: Console Cmd 8001

    {OFF=0|ON=1} enables SSH console ssh enabled show show s if SSH enabled console ssh port set {ip_port} sets SSH port console ssh port show show s SSH port Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 70 {CONTINOUS=0| sets beeper tone INTERMITTENT=1} extsensor {port_num} {sen_type} {sen_field} show s beeper tone events beeper mode show extsensor {port_num} {sen_type} {sen_field} sets maximum value for sensor maxval set {num} Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 71 {OFF=0|ON=1} enables login for RADIUS on/off http passw d radius show show s if RADIUS login enabled Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 72 {line_num} {energy_sensor} events enables events on/off set {OFF=0|ON=1} linesensor {line_num} {energy_sensor} events show s if events are enabled show linesensor {line_num} {energy_sensor} events type set enables different event types "{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5}" Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 73 {line_num} hyst show LEGACY - show s hysterese value for line meter linesensor {line_num} {BELOWMIN=0| LEGACY - sets Port for Pow er Port Sw itching ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} port actions set {port_num} Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 74 {port_num} label set "{name}" sets port label name port {port_num} label show show s port label name port {port_num} initstate coldstart set {OFF=0| sets port coldstart initialization ON=1|REMEMBER=2} Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 75 {port_num} {energy_sensor} maxval show s maximum value for sensor show portsensor {port_num} {energy_sensor} minval sets minimum value for sensor set {num} portsensor {port_num} {energy_sensor} minval show s minimum value for sensor show Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 76 LEGACY - show s state for sensor values action state show radius enters cmd group "radius" radius {PRIMARY=0|SECONDARY=1} enabled set enables radius client <off=0/on=1> radius {PRIMARY=0|SECONDARY=1} enabled show if radius client enabled show Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 77 SNMP trap receiver snmp trap receiver {trap_num} set "{dns_name}" {trap_num} show address and port of SNMP trap receiver snmp trap receiver {trap_num} show {trap_num} syslog enters cmd group "syslog" Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 78 {rule_num} trigger jitter set {0..65535} sets jitter for rule timer {rule_num} trigger jitter show show jitter of rule timer {rule_num} trigger random set {0..100} sets probability for rule Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 79 Power Reactive Forward Active Energy Resettable Forward Reactive Energy VARh Forward Reactive Energy Resettable VARh Reset Time - sec. since last Energy Counter Reset Reverse Active Energy Reverse Reactive Energy VARh Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 80: Modbus Tcp

    Address range overview: Device Resource Start Modbus Data Type Power/Output/eFuse Ports 0x000 0x3ff Coils DC Inputs 0x400 0x7ff Discrete Inputs Stop Condition active 0x800 0x800 Discrete Inputs Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 81 Function when set DC Inputs 0x400 0x7ff Input logically 1 Stop Condition active 0x800 0x800 Stop Input active POE active 0x801 0x801 POE active Status Power Sources 0x1000 0x100f Power Source active Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 82 16-bit (signed) Bank Energy Sensors 0x8240 to 0x827f 16-bit (signed) Power Source Energy Sensors 0x8280 to 0x82cf 16-bit (signed) Residual Current Monitor CPU Sensor Values Offset Sensor Field Unit Vsystem 0.01 V Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 83 "Voltage" for 2nd line sensor and single phase device: 0x400 + 1 * 0x120 + 2 * 2 = 0x524 "Power Angle" for 4th port sensor and single phase device: 0x3a00 + 3 * 0x120 + 6 * 2 = 0x3d6c Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 84 "Voltage" at third bank: 0x8200 + 2 * 2 + 0 = 0x8204 "Current" at first PowerSrc: 0x8240 + 0 * 2 + 1 = 0x8241 Offset Sensor Field Unit Voltage 0.01 V Current Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 85 MEI Type 1 Byte 0x0e Read Dev ID code 1 Byte 0x01 Conformity Level 1 Byte 0x01 More Follows 1 Byte 0x00 NextObjectID 1 Byte 0x00 Number of Objects 1 Byte 0x03 Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 86: Sensor Tables

    Absolute Reactive Energy Resettable 0x416 Reset Time - sec. since Reset 0x418 Forward Active Energy 0x41a Forward Reactive Energy 0x41c Forward Active Energy Resettable 0x41e Forward Reactive Energy Resettable 0x420 Reverse Active Energy 0x422 Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 87: 4.10 Mqtt

    The device can be controlled remotely via MQTT using console commands. A list of all commands can be found in the Console chapter. Depending on the topic, the com- mands are accepted in different formats. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 88 Topic: en/gudesystems/epc/00:19:32:01:16:41/device/telemetry Message: "type": "telemetry", "portstates": [{ "port": "1", "name": "Power Port", "state": 1 }, { "port": "2", Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 89: Example Hivemq

    "unit": "deg C" "ts": 210520 4.10.1 Example HiveMQ What does an MQTT configuration look like using HiveMQ as an example? Create a free or commercial account at www.hivemq.com and create a new cluster. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 90 In the MQTT configuration of the Gude device, transfer the hostname of the HiveMQ broker, as well as username and password. Additionally activate TLS and set the correct port. Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 91: Support

    Support...
  • Page 92: Data Security

    · If possible, place the device behind a firewall. Contact GUDE Systems GmbH Von-der-Wettern-Straße 23 51149 Cologne Germany Phone: +49-221-912 90 97 Fax: +49-221-912 90 98 E-Mail: mail@gude.info Internet: www.gude.info shop.gude.info Managing Director: Dr.-Ing. Michael Gude Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 93: Declaration Of Conformity

    Value added tax identification number (VAT): DE 122778228 Declaration of Conformity This product Expert Power Control 8001 series is in conformity with the European dir- ectives for CE marking applicable to this product. The complete CE declaration of con- formity for this product can be found on the website www.gude.info in the download sec- tion of the product.
  • Page 94 (e.g. from the Maintenance Page 9. Disable switching events · You can set the sending of syslog, emails etc. when switching ports (only concerns Gude devices with relays) under "System" in the sensor configuration Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 95: Index

    Firmware Upload - S - Firmware-Update Security Advice - G - Select button Sensors 10, 46 GBL_Conf.exe SNMP 33, 56 - H - Start-up the device HTTP Status LED HTTPS Status-LED Syslog Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 96 Index - T - Technical Specifications Timer Timer Configuration - W - Watchdog Expert Power Control 8001 © 2022 GUDE Systems GmbH...
  • Page 97 Expert Pow er Control 8001 © 2022 GUDE Systems GmbH 3/16/2022 Expert Power Control 8001 © 2022 GUDE Systems GmbH...