Emerson Copeland Scroll ZH04K1P Manual page 34

Hide thumbs Also See for Copeland Scroll ZH04K1P:
Table of Contents

Advertisement

Condition
System design
load too small
Low suction
Inadequate
pressure
refrigerant
going to the
evaporator
Noise during shut-
Anti-reverse
off
device
C6.2.26/1013-1116/E
Cause
If the compressor is running in a tandem or in parallel,
modulate the running process.
Lower normal discharge pressure values can lead to
insufficient refrigerant flow to the system.
This can also be verified by checking the evaporator
outlet superheat, if it is found unusually high. Check the
selection of the expansion valve (likely undersized).
This does not have any effect on the durability of the
compressor, no action is necessary.
Corrective action
31