Emerson Copeland OMTE-76D Application Manuallines page 53

Large outdoor refrigeration units
Table of Contents

Advertisement

Code
Description
E82
Probe configuration error
E83
DI conf iguration error
E84
Compressor configuration error
E85
Injection probe configuration error
E86
EEPROM R/W error (manual)
E87
Fan f ailure
Table 26: Alarm code overview
48
Cause
Action
Dif ferent probes (P3,
P4, P5, P6, P7) have
the same configuration.
For example,
Correct the configuration
A13 = Ambient temp
(NTC 10 K),
A15 = Ambient temp
(NTC 10 K)
Dif ferent digital inputs
DI (DI1, DI2, DI3) have
the same configuration.
Correct the configuration
For example,
R04 = Door switch,
R07 = Door switch
Case 0: digital
compressor relay is
conf igured, no digital
solenoid configuration;
Case 1: digital
compressor relay is
conf igured, no digital
solenoid configuration;
Correct the configuration
Case 2: no digital
compressor relay
conf iguration, digital
solenoid is configured;
Case 3: C05 = 3, digital
compressor relay and
digital solenoid are
conf igured
Not used
HW problem in the
Change the board
board
Fan alarm contact
Check reason for fan alarm contact
(digital input DI7) open
opening (mechanical issue, electrical
F6(F7)
issue)
Reset
Board must be reset
Board must be reset
Board must be reset
Automatically: as soon the alarm contact closes
again
AGL_Unit_LOCU_EN_Rev00