Connection Sizes; Figure 29: Connection Ports On Suction & Liquid Lines - Emerson Copeland OMTE-76D Application Manuallines

Large outdoor refrigeration units
Table of Contents

Advertisement

1/200 to 1/250. Upper and lower oil traps, double risers and reduced pipe diameters may be required
f or suction lines where long vertical risers cannot be avoided.
All pipes should be adequately supported to prevent sagging which can create oil traps. The
recommended pipe clamp support distance is shown in Table 21 below:
Max distance between
Tube size
1/2" (12.7 mm)
5/8" (16.0 mm)
7/8" (22.0 mm)
1 1/8" (28.5 mm)
Table 21: Maximum distance between 2 clamp supports
NOTE: It is strongly recommended to insulate both the suction and liquid interconnecting
piping between the OLTE unit and the evaporator.
3.2.2

Connection sizes

Figure 29: Connection ports on suction & liquid lines
Unit
OMTE-76D
& OMTE-90D
OLE-49
OMTE-152D
& OLTE-82D
Table 22: Suction & liquid line diameters
AGL_Unit_LOCU_EN_Rev00
2 clamp supports
1.20 m
1.50 m
1.85 m
2.20 m
Suction inlet
1 3/8" (34.925 mm)
1 3/8" (34.925 mm)
1 5/8" (41.275 mm)
Liquid outlet
5/8" (15.875 mm)
1/2" (12.7 mm)
7/8" (22.23 mm)
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Copeland omte-152dCopeland ole-49Copeland olte-82d

Table of Contents