EC (Refrigerant Leakage Detec�on diagnosis and solu�on)
Descrip�on: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.
In the beginning 5 minutes a�er the compressor starts up, if T2<Tcool-2°C does not keep con�nuous 4 seconds and this
situa�on happens 3 �mes, the display area will show "EC" and AC will turn off.
Recommended parts to prepare:
• Faulty T2 sensor
• Faulty
iIndoor PCB
• System problems, such as leakage or blockages
Troubleshoo�ng and
repair:
Power off, then restart the unit 2 minutes later.
Does a problem remain?
Put your hands in front of the
air blowing out from
indoor air outlet?
Check system for leakages.
Are any leakages
Check System for blockages and
clear blockages if present.
YES
indoor air outlet.
Is there cool
NO
NO
present?
NO
YES
Check the T2 sensor.
Is it securely
a�ached?
Repair the leakage and
YES
recharge the refrigerant.
Replace the
YES
indoor PCB
Page 75