Standard electrical control panel
Table of Contents

Advertisement

c. Set
the
amp
scale to at least 2 times
the pump motor full
load current.
d. Place the H-O-A switch
in the Hand position to
start the pump.
e. The meter should read
ap prox i mate ly 2 times
full load current during
starting.
f. After the motor has
started
(within
sec ond)
the
should drop to a value
much less than full load
cur rent.
6
meter
5. Motor voltage check:
Component
Main Winding
Main Winding
Start Winding
Start Winding
one
cur rent
Typical
Motor
Lead
Mode
Black to
Start
White
Black to
Run
White
Black to
Start
Red
Black to
Run
Red
Voltage
Reading
Line Voltage
Line Voltage
Line Voltage
120%
Line Voltage