LOCATION AND MOUNTING CALIFORNIA PROPOSITION 65 WARNING: OUTDOOR USE The control box may be mounted at the location of This product and related the pump and basin or may be mounted in a remote accessories contain chemicals known to the location.
Page 3
CONNECTING PUMPS AND FLOATS TO CONTROL BOX PUMP CORD should be connected to the terminal strip in the Run the wires from both pumps to the bottom of control box. See wiring diagram for the proper the control box by means of one of the methods terminal connections.
Page 4
CHECKING PUMP CURRENT DRAW 1 PHASE PUMPS 3. If you get a reading of 0, make sure there is voltage to the motor leads. Push the overload 1. Use an amprobe to check the amperage of the reset button on the overload relay in the control pump.
Page 5
TESTING COMPONENTS IN CONTROL BOX WARNING 3. With an ohmmeter on the R x 1 scale touch terminals X2 and X1 (secondary), you should get To prevent electrical shock, disconnect power entering a reading of approximately 3.6 ohms for Simplex the control box and turn the circuit breaker in the panels and 1.6 ohms for Duplex panels.
Page 6
TESTING COMPONENTS IN CONTROL BOX should be on pin 3, and the “red” lead should be on and touch the other lead to the other capacitor pin 5. You should have a reading of approximately terminal. If the capacitor is good, the needle will go 920-1020 ohms.
Warranty is effective only if Pentair Myers authorized control panels are used. All seal fail and heat sensing devices must be hooked up, functional and monitored or this warranty will be void. Pentair Myers will cover only the lower seal and labor thereof for all dual seal pumps. under no circumstance will Pentair Myers be responsible for the cost of field labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from the factory or an authorized Pentair Myers service facility.