IV. Procedure for using Milliammeter for DROPOUT TESTING.
Attach proper cables and set meter selector switch as designated by chart.
Turn adjuster knob to get a full scale reading and reset control by pressing
in reset button firmly.
Turn adjuster knob slowly to left until Baso Power Unit releases. The Mliii-
ampere reading at the moment of release is the dropout point of the Baso
Power Unit. Take two more readings by the same process, and average out
readings. Milliampere dropout point must lie within the high and low
range
given in Table II.
CABLES AND
ADAPTERS FOR
DROPOUT
TESTING
Black
White
Fits 800 Series Baso, Basotrol, Actrol, and Basoid Controls.
With Adapter 3, Fits 960 Series.
With Adapter 1, Fits 300 and 500 Series, B Series Basoid.
Fits Basotron Series.