Download Print this page

EMS FireCell FC-171-001 Installation Manual page 2

Advertisement

Configuration continued
Beacon flash rate (Set on beacon)
Switch 2 on the two way switch is used to
configure the beacon flash rate. Switch 1 is
not used on this product.
Default setting: 1 Hz flash rate
Audio monitoring (Set on wireless module)
The device has an audio self test feature which
is not used on this version of product.
Both switches should be OFF as shown.
Default setting: Audio monitoring disabled
Specification
Operating
temperature
-10 to +55 °C
Storage
temperature
5 to 30 °C
Humidity
0 to 95% non-condensing
Supply
3x AA alkaline (Panasonic LR6AD Powerline / Varta
4006 Industrial) 3x C alkaline (Panasonic LR14AD
Powerline / Varta 4014 Industrial)
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
IP rating
IP54
Operating
frequency
868 MHz
Output
transmitter
power
Auto adjusting 0 to 14 dBm (0 to 25 mW)
Beacon element
voltage
17 to 60 VDC operating at 18 VDC
Beacon element
current max.
40 mA at 1 Hz flash rate
Flash rate
0.5 Hz / 1 Hz (selectable)
Beacon coverage
C-3-15 (ceiling mounted variant)
W-3.1-11.3 (wall mounted variant)
Dimensions (Ø x D)
120 x 145 mm
Weight
0.65 kg
Location
Type A: For indoor use
©2021 EMS Ltd. All rights reserved
SWITCH 1 = NOT USED
SWITCH
2
ON
2
1
2
OFF
2
SWITCHES 1 & 2 = NOT USED
1
2
2
Regulatory information
Manufacturer
Year of
manufacture
Certification
Certification
body
CPR DoP
Approved to
European Union
directives
Page 2 of 2
FLASH
RATE
Beacon
1Hz
ON
1
2
0.5Hz
www.emsgroup.co.uk
Wireless Module
IDENT
PRESS HERE TO
LOG ON
Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa
24. 39-100 Ropczyce, Poland
See devices serial number label
14
0905
0359-CPR-00292
See part listing for associated products:
EN54-23:2010. Fire detection and fire alarm
systems. Part 23: Fire alarm devices. Visual alarm
devices.
[1]
EN54-25:2008.
Incorporating
September 2010 and March 2012. Fire detection
and fire alarm systems.
Part 25: Components using radio links.
EMS declares that this device is in compliance with
Directive 2014/53/EU. The full text of the EU
declaration of conformity is available at the following
internet address: www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
TSD068-99 Iss 8 24/11/2021