Mitsubishi Electric SLH Series Technical & Service Manual page 49

Split-type, heat pump air conditioners, ceiling cassettes, indoor unit
Hide thumbs Also See for SLH Series:
Table of Contents

Advertisement

2. DRY operation
ON/OFF
ON/OFF
TOO
TOO
WARM
COOL
FAN
SELECT
COOL
AUTO COOL
VANE
TIME
FAN
DRY
HEAT
DRY
MODE
MODE
RESET
SLH-1AR
SL-1AR
SLH-1.6AR
SL-1.6AR
SLH-2AR
SL-2AR
<DRY operation time chart>
OFF
Thermostat
Indoor fan
OFF
Outdoor fan
OFF
compressor
(1) Setting temperature
Follow the right chart with according to the initial room temperature. When
the room temperature is 13: or under, dry operation does not work.
(2) ON/OFF control
When the room temperature is 23°C or over:
Compressor operates by temperature control and time control.
1 Set temperature is controlled to fall 2°C above from initial set temperature.
2 When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
(3) Coil frost prevention
The operation is same as that of coil frost prevention during COOL mode.
However the indoor fan speed becomes the set speed or Low.
<How to operate>
1 Press POWER ON / OFF button.
2 Press MODE SELECT button to set operation mode to DRY.
TOO
TOO
WARM
COOL
Each time the MODE SELECT button is pressed the display " " on the remote
FAN
SELECT
controller moves.
VANE
TIME
NOTE : Temperature can not be in DRY operation.
RESET
In case of the room temperature of 23: and above.
1st ON
ON
ON
OFF
ON
ON
OFF
3min.
8min.
OFF
ON
OFF
ON
OFF
.
1min
4min.
49
ON