(5) Auto vane control
Auto vane position is set to 30 degrees airflow at the start-up of COOL operation. It can then be changed by the remote
controller.
(a) Stop mode (fixed operation)
( i ) At start-up of COOL operation, the auto vane is set to 30 degrees airflow direction.
( ii ) Discharge direction can be changed with
1
1 Horizontal airflow 30°
2 Downward airflow 45°
3 Downward airflow 55°
(b) SWING mode
( i ) The vane motor turns ON when the SWING mode is selected. The vane motor is continuously ON during SWING mode.
<VANE POSITION>
1 Fan speed : LOW / MED.
30°
1
2 Fan speed : HIGH
30°
2
3
4 Downward airflow 70°
5 Swing
45°
55°
2
3
AUTO
RETURN
45°
55°
button.
4
5
70°
If you select 2 or 3 or 4 when the fan speed is LOW
or MED. the airconditioner will switch automatically to
4
Horizontal airflow 1 mode after one hour.
70°
48