8. Operation Range
Defrosting correction factor
The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while
the defrosting operation is in progress.
The capacity values, which take these factors into account, in other words, the integrated heating capacity values,
can be calculated as follows :
Formula : A = B × C
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation (kW) = C
Outdoor temperature (°C, DB/WB) -10/-10.4 -8/-8.5 -6/-6.5 -4/-4.6 -2/-2.7
Capacity coefficient
1.05
0.99
1.00
0.95
0.90
0.85
0.80
0.75
-10
On heating operation, frost can be formed on heat exchanger according to outdoor temperature.
(Frost on heat exchanger results in decreasing the performance.)
To remove frost on heat exchanger of outdoor unit, defrost operation is carried out periodically.
During defrost operation, capacity of outdoor unit may decrease.
The decrement is not considered to the individual capacity tables.
This figure shows an effect of intelligence defrost operation
It is actually the frost occurrence section from 0 ℃ or less.
Since the outdoor temperature over 0 ℃, the heating performance is the same before and after applying intelligence
defrost operation
In outdoor conditions below 0 ℃, frost conditions reflect the actual entering the defrost opration because heating
performance is improved
0.99
0.98
Capacity coefficient of outdoor unit on defrost operation
0.98
0.96
0.95
-8
-6
-4
Outdoor temperature ( C)
0.96
0.95
0.91
0.91
0.88
0.86
-2
0
2
0/-0.7
2/1.2
5/4.1
0.88
0.86
0.91
1.05
1.00
1.00
0.95
0.91
0.90
0.85
0.80
0.75
5
7
7/6
1.00