Troubleshooting
Error
No.
Code
Heating operation restricted at outdoor temperature over
20
E440
Theat_high value (default:30°C)
Cooling operation restricted at outdoor temperature below
21
E441
Tcool_low value (default:0°C)
22
E458
Fan speed error
23
E461
Error due to operation failure of inverter compressor
24
E462
System stop due to full current control
25
E463
Over current trip / PFC over current error
26
E464
IPM Over Current(O.C)
27
E465
Comp. Over load error
28
E466
DC-Link voltage under/over error
Error due to abnormal rotation of the compressor or
29
E467
unconnected wire of compressor
30
E468
Error on current sensor (Short or Open)
31
E469
Error on DC-Link voltage sensor (Short or Open)
32
E470
Outdoor unit EEPROM Read/Write error (Option)
33
E471
Outdoor unit EEPROM Read/Write error (H/W)
34
E474
Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
35
E475
Error on inverter fan 2
36
E483
AC Input voltage is over-voltage error
37
E484
PFC Overload (Over current) Error
38
E485
Error on input current sensor of inverter 1 (Short or Open)
39
E488
Error on AC Input voltage sensor (Short or Open)
40
E500
IPM over heat error on inverter 1
41
E508
Smart install is not installed
42
E554
Gas leak detected
Error due to mismatching capacity of indoor and outdoor
43
E556
unit
44
E557
DPM remote controller option error
45
E590
Inverter EEPROM Checksum error
46
E660
Inverter Boot Code error
34 English
Meaning
Remarks
1. Check the range of temperature limited for heating
operation
2.Check the outdoor temperature sensor
1. Check the range of temperature limited for cooling
operation
2.Check the outdoor temperature sensor
FAN1 ERROR
-
-
Check OLP sensor
1.Check if the service valve is open
2.Check the state of refrigerant
3.Check if connecting wire and the pipe are OK
4.Check the compressor
-
Check AC Power and DC Link Voltage
Check Comp wire
Check Outdoor Inverter PBA.
-
Check Outdoor EEPROM Data
Check Outdoor EEPROM PBA
Check Outdoor Inverter PBA.
FAN2 ERROR
Check AC Power
Check Outdoor Inverter PBA.
Check Outdoor EEPROM PBA
Check Outdoor Inverter PBA.
Check Outdoor Inverter PBA.
-
Check the refrigerant
Check the indoor and outdoor unit capacity
Check the indoor option code
-
-