Mitsubishi Electric CITY MULTI PEFY-W20VMA-A Technical & Service Manual page 19

Hide thumbs Also See for CITY MULTI PEFY-W20VMA-A:
Table of Contents

Advertisement

[ III Specifications ]
Component
Room temperature
thermistor
Water inlet pipe
thermistor
Water outlet pipe
thermistor
Fuse
Fan motor
Pressure sensor
(inner water)
Pressure sensor
(outlet water)
Flow control valve
Power supply terminal
block
Transmission terminal
block
Drain pump
Drain float switch
HWE18200
Sym-
bol
TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
F01
F02
PS1
PS2
FCV
TB2
TB5
TB15
DP
DS
PEFY-W100/125VMA(L)-A
PEFY-W50/63/71/80/100/125VMA2-A
AC250V 6.3A
DC400V 3A
8-pole, Output 300W ZWB378
Pressure
PS1
0~1.0 MPa [145psi]
Vout 0.5~4.5V
3 2 1
0.392V/0.098 MPa [14psi]
Pressure [MPa]
Connector
=0.25 x Vout [V] - 0.125
Pressure [psi]
=(0.25 x Vout [V] - 0.125) x 145
GND (Black)
1
2
Vout (White)
3
Vcc (DC5V) (Red)
12V DC stepping motor (0~770 pulse)
(L, N,
) 250V 20A
(1, 2) 250V 15A, (M1, M2, S) 250V 20A
PMD-12D 13ME
INPUT 3W (DC 13V) 24L/Hr
Open/short detection
Initial contact resistance 500 mΩ or less
- 14 -
GB

Advertisement

Table of Contents
loading

Table of Contents