Carrier 38BYC Installation And Start-Up Instructions Manual page 7

12 seer split system heat pump
Table of Contents

Advertisement

OF2
OF1
O
R
T2
Y
TI DFT
O
R
W2
Y
C
CES0110063,
CES0130024
Table 3—Defrost Control Speedup-
Timing Sequence
MINIMUM
PARAMETER
(MINUTES)
30–minute cycle
27
50–minute cycle
45
90–minute cycle
81
10–minute cycle
9
5 minutes
4.5
Fig. 10—Defrost Control
6. When you hear reversing valve change position, remove
screwdriver immediately; otherwise, control will terminate
normal 10-minute defrost cycle in approximately 2 sec.
NOTE: Length of defrost cycle is dependent upon length of time
it takes to remove screwdriver from test pins after reversing valve
has shifted.
7. Unit will remain in defrost for remainder of defrost-cycle time
or until defrost thermostat reopens at approximately 80°F coil
temperature of liquid line.
8. Turn off power to outdoor unit and reconnect fan motor lead
to OF2 on control board. (See Fig. 10.)
Step 14—Check Charge
Factory charge is shown on unit rating plate. To check charge in
cooling mode, refer to Cooling Only Procedure. To check charge
in heating mode, refer to Heating Check Chart Procedure.
COOLING-ONLY PROCEDURE
NOTE: If superheat- or subcooling-charging conditions are not
favorable, charge must be weighed in accordance with unit rating
plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft
respectively.
C
TEST 30 50 90
W1
A91444
MAXIMUM
SPEEDUP
(MINUTES)
(NOMINAL)
33
7 sec
55
12 sec
99
21 sec
11
2 sec
5.5
1 sec
EXAMPLE:
To calculate additional charge required for a 25–ft line set:
25 ft – 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge
Units installed with cooling mode TXV require charging with the
subcooling method.
1. Operate unit a minimum of 10 minutes before checking
charge.
2. Measure liquid service-valve pressure by attaching an accurate
gage to service port.
3. Measure liquid-line temperature by attaching an accurate
thermistor type or electronic thermometer to liquid line near
outdoor coil.
4. Refer to unit rating plate for required subcooling temperature.
5. Refer to Table 4. Find the point where required subcooling
temperature intersects measured liquid service-valve pressure.
6. To obtain required subcooling temperature at a specific
liquid-line pressure, add refrigerant if liquid-line temperature
is higher than indicated or reclaim refrigerant if temperature is
lower. Allow a tolerance of ± 3°F.
Table 4—Required Liquid-Line Temperature (°F)
LIQUID
PRESSURE AT
SERVICE VALVE
(PSIG)
134
141
148
156
163
171
179
187
196
205
214
223
233
243
253
264
274
285
297
309
321
331
346
359
HEATING CHECK CHART PROCEDURE
To check system operation during heating cycle, refer to the
Heating Check Chart on outdoor unit. This chart indicates whether
a correct relationship exists between system operating pressure and
air temperature entering indoor and outdoor units. If pressure and
temperature do not match on chart, system refrigerant charge may
not be correct. Do not use chart to adjust refrigerant charge.
7
REQUIRED SUBCOOLING
TEMPERATURE (°F)
5
10
15
71
66
61
74
69
64
77
72
67
80
75
70
83
78
73
86
81
76
89
84
79
92
87
82
95
90
85
98
93
88
101
96
91
104
99
94
107
102
97
110
105
100
113
108
103
116
111
106
119
114
109
122
117
112
125
120
115
128
123
118
131
126
121
134
129
124
137
132
127
140
135
130
20
56
59
62
65
68
71
74
77
80
83
86
89
92
95
98
101
104
107
110
113
116
119
122
125

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38byg25hbb25hbc25hcd

Table of Contents