Download Print this page

Janus PAD100-SB Quick Start Manual

Addressable sounder base

Advertisement

Quick Links

PAD100-SB
Addressable Sounder Base
Description
The Addressable Sounder Base 6" (PAD100-SB) is a sounder base that may be utilized in a variety of
applications. The base has a locking feature for the sensor that may be used or removed in the field.
Once the head is removed, the sounder is accessible in the bottom of the unit.
The base has an independent sounder module that may be programmed as a single station, zone or
all call sounder. The PAD100-SB passes through the sound pattern sent to the sounder, therefore it
may reproduce in any pattern the power supply provides.
The panel will support any combination of sensors or modules on the SLC. The PAD100-SB does not
consume an address on the loop and is fully programmable to operate with any input. Once activated
the sounder will also follow the input from the power source and deactivate accordingly.
Detector Base Mounting
PAD100-SB should be mounted directly on the electrical box. The mounting holes are configured for
a single gang, double gang, octagon or 4" square box.
DS1348
Revised: 20-Aug-2019
P/N 97674
Using the two included
screws, attached the
detector base to detector
bracket.
© 2017 Janus Fire Systems. All rights reserved (5/2017) Janus Fire Systems® is a registered trademark of Janus Fire Systems.
Features
Integrated Sounder in base
75 dB (UL 464 Listed) sounder output
Sounder independent of sensor, allows for a single
station, grouped or all-call
May be mapped to any device connected to the
control panel
Terminals accept 22 to 12 AWG wire sizes
Supports Class A, Class X and Class B wiring
Does not require SLC Loop address
UUKL Listed for Smoke Control
Specifications
Working Range for SLC: 24 VDC
Working voltage range for PWR: 16 - 33 VDC
Active current for PWR: 30 ma
Sound pressure level: 75dB/10ft (min.) as per UL464
Installation temperature range: 32°F to 120°F (0°C to 49°C)
Operating relative humidity range: 0% to 93% (Non-condensing)
Start-up time: Max. 1 sec.
Maximum number of devices per zone: 127
Color: Eggshell White
Height: 0.75 in (19 mm)
Diameter: 6.3 in (166 mm)
Alignment Features
Mount the detector
bracket to the back box
using the mounting
screws.

Advertisement

loading

Summary of Contents for Janus PAD100-SB

  • Page 1 Mount the detector bracket to the back box using the mounting screws. © 2017 Janus Fire Systems. All rights reserved (5/2017) Janus Fire Systems® is a registered trademark of Janus Fire Systems. DS1348 Revised: 20-Aug-2019...
  • Page 2 Locking Feature PAD100-SB include a locking feature that prevents removal of the detector and removal of the base cover without using a tool. 1. To eliminate this feature, break off the locking tab and then install the detector. Break off tab (gray area) in image to disable locking feature.