Alternate Vertical Concentric Venting - Lochinvar Knight XL 100 Series Installation & Operation Manual

Hide thumbs Also See for Knight XL 100 Series:
Table of Contents

Advertisement

5
Vertical direct venting

Alternate vertical concentric venting

This appliance may be installed with a concentric vent
arrangement where the vent pipe is routed through an
existing unused venting system; or by using the existing
unused venting system as a chase for vent and combustion
air routing.
Concentric Venting Arrangement
The venting is to be vertical through the roof. The annular
space between the O.D. of the vent pipe and the I.D. of the
existing unused venting system is utilized for the combustion
air source.
The minimum size of the existing vent system required to
achieve enough annular space for combustion air can be
found in Table 5A.
The upper and lower termination as well as any other unsealed
joints in the existing vent system must be sealed to ensure that
all combustion air is drawn from under the vent cap as shown
in FIG.'s 5-8 and 5-9.
Approved venting materials must be used as specified in
Table 3H.
Follow all vent / air termination and clearance requirements
per this section to the appropriate example. Installation must
comply with local requirements and with the National Fuel
Gas Code.
The maximum allowable equivalent vent and air intake
lengths for this venting arrangement are to be determined
from the General Venting Section.
If an existing unused venting system is converted for use
with this method of concentric venting, the installer must
ensure that the existing venting system is clean and free from
particulate contamination that will harm this appliance and
cause increased nuisance calls or maintenance. See Table 1A
for a list of corrosive contaminants and sources.
Two example scenarios of a concentric venting arrangement
are shown for illustrative purposes in FIG.'s 5-8 and 5-9.
Table 5A Alternate Vertical Concentric Vent / Chase Sizes
Vent / Air
Model
Inlet Size
400 - 500
4"
650 - 1000
6"
34
Minimum Existing
Vent / Chase Size
7"
10"
Installation & Operation Manual
Figure 5-8 Concentric Vent Example 1
AIR INLET
W/ SCREEN
12"
MIN.
*For concept illustration only. Individual installations
may vary due to job site specific equipment.
Figure 5-9 Concentric Vent Example 2
SEAL
AIR INLET
W/ SCREEN
SEAL
*For concept illustration only. Individual installations
may vary due to job site specific equipment.
FLUE EXHAUST
SEAL
COMBUSTION AIR
EXISTING
SEAL
SEALED
CAP
FLUE OUTLET
DIR #2000585169 00
FLUE EXHAUST
COMBUSTION AIR
EXISTING
SEALED
SEAL
CAP
FLUE OUTLET
DIR #2000585169 00