Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)
VOLTAGE
COMPRESSOR
NOMINAL
RANGE
(EA)
UNIT
POWER
50PG
SUPPLY
MIN
MAX
RLA
VOLTS-PH-HZ
208/230-3-60
187
253
14.6
(cont)
460-3-60
414
506
7.1
05
(cont)
575-3-60
518
632
5.0
06
208/230-1-60
187
253
26.9
LEGEND
FLA
− Full Load Amps
HACR − Heating, Air Conditioning and Refrigeration
IFM
− Indoor − Fan Motor
LRA
− Locked Rotor Amps
MCA
− Minimum Circuit Amps
MOCP − Maximum Overcurrent Protection
NEC
− National Electrical Code
OFM
− Outdoor−Fan Motor
RLA
− Rated Load Amps
*
Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percentage of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
POWER
OFM
IFM
IFM
EXHAUST
FLA
FLA
TYPE
CRHEATER
LRA
FLA
PART NO.
208A00
209A00
4.9
Low
210A00
211A00
212A00
91
0.9
1.4
208A00
209A00
5.2
High
210A00
211A00
212A00
215A00
216A00
2.1
Low
217A00
218A00
219A00
215A00
216A00
2.6
High
217A00
218A00
219A00
46
0.5
215A00
216A00
2.1
Low
217A00
218A00
219A00
0.6
215A00
216A00
2.6
High
217A00
218A00
219A00
221A00
Low
222A00
223A00
221A00
High
222A00
223A00
34.0
0.4
2.0
221A00
Low
222A00
223A00
1.4
221A00
High
222A00
223A00
201A00
202A00
203A00
4.9
Low
204A00
205A00
206A00
145
1.5
201A00
202A00
7.0
High
203A00
204A00
205A00
206A00
average voltage
ELECTRIC HEAT
POWER SUPPLY
NOMINAL
FLA
MCA
MOCP†
KW*
/
30.2/30.2
10.0/11.5
3.8/ 5.0
30.2/30.2
15.0/17.3
5.6/ 7.5
32.6/35.0
20.0/23.1
7.5/10.0
38.9/42.2
30.0/34.6
11.3/15.0
51.4/56.6
40.0/46.2
15.0/20.0
63.9/71.0
/
30.5/30.5
10.0/11.5
3.8/ 5.0
30.5/30.5
15.0/17.3
5.6/ 7.5
33.0/35.3
20.0/23.1
7.5/10.0
39.3/42.6
30.0/34.6
11.3/15.0
51.8/57.0
40.0/46.2
15.0/20.0
64.3/71.4
13.6
5.8
5.0
13.6
8.7
7.5
16.2
11.5
10.0
19.8
17.3
15.0
27.0
23.1
20.0
34.2
14.1
5.8
5.0
14.1
8.7
7.5
16.8
11.5
10.0
20.4
17.3
15.0
27.6
23.1
20.0
34.8
14.2
5.8
5.0
14.2
8.7
7.5
16.9
11.5
10.0
20.5
17.3
15.0
27.7
23.1
20.0
35.0
14.7
5.8
5.0
14.7
8.7
7.5
17.5
11.5
10.0
21.2
17.3
15.0
28.4
23.1
20.0
35.6
10.7
9.2
10.0
16.3
13.9
15.0
22.1
18.5
20.0
27.9
10.6
9.2
10.0
16.1
13.9
15.0
22.0
18.5
20.0
27.8
12.1
9.2
10.0
18.0
13.9
15.0
23.9
18.5
20.0
29.6
12.0
9.2
10.0
17.9
13.9
15.0
23.8
18.5
20.0
29.5
/
46.1/ 46.1
17.3/ 20.0
3.8/ 5.0
46.1/ 46.1
26.0/ 30.0
5.6/ 7.5
46.1/ 48.6
34.7/ 40.0
7.5/10.0
54.5/ 61.1
52.0/ 60.0
11.3/15.0
76.1/ 86.1
69.3/ 80.0
15.0/20.0
97.8/111.1
100/125
86.7/100.0
18.8/25.0
119.4/136.1
125/150
/
48.2/ 48.2
17.3/ 20.0
3.8/ 5.0
48.2/ 48.2
26.0/ 30.0
5.6/ 7.5
48.2/ 51.3
34.7/ 40.0
7.5/10.0
57.1/ 63.8
52.0/ 60.0
11.3/15.0
78.7/ 88.8
69.3/ 80.0
15.0/20.0
100.4/113.8
110/125
86.7/100.0
18.8/25.0
122.1/138.8
125/150
Example: Supply voltage is 460-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if
field−supplied pressure connectors are used.
23
DISCONNECT SIZE
CRSINGLE
PART NO.
(NOTE3)
FLA
LRA
40/40
31/31
111/111
40/40
030A00
31/31
111/111
40/40
030A00
31/33
111/111
40/45
030A00
36/39
111/111
60/60
030A00
47/53
111/111
70/80
031A00
59/66
111/111
45/45
31/31
130/130
45/45
030A00
31/31
130/130
45/45
030A00
31/33
130/130
45/45
030A00
36/40
130/130
60/60
030A00
48/53
130/130
70/80
031A00
59/66
130/130
20
14
55
20
030A00
14
55
20
030A00
15
55
20
030A00
18
55
30
030A00
25
55
35
030A00
31
55
20
14
64
20
030A00
14
64
20
030A00
15
64
25
030A00
19
64
30
030A00
25
64
35
030A00
32
64
20
14
56
20
030A00
14
56
20
030A00
16
56
25
030A00
19
56
30
030A00
26
56
40
030A00
32
56
20
15
65
20
030A00
15
65
20
030A00
16
65
25
030A00
19
65
30
030A00
26
65
40
030A00
33
65
15
11
42
20
030A00
15
42
25
030A00
20
42
30
030A00
26
42
15
11
48
20
030A00
15
48
25
030A00
20
48
30
030A00
26
48
15
12
44
20
030A00
17
44
25
030A00
22
44
30
030A00
27
44
15
12
50
20
030A00
16
50
25
030A00
22
50
30
030A00
27
50
60/ 60
44/ 44
164/164
60/ 60
028A00
44/ 44
164/164
60/ 60
028A00
44/ 46
164/164
60/ 70
028A00
51/ 57
164/164
80/ 90
029A00
71/ 80
164/164
029A00
91/103
164/164
029A00
111/126
164/164
60/ 60
46/ 46
190/190
60/ 60
028A00
46/ 46
190/190
60/ 60
028A00
46/ 48
190/190
60/ 70
028A00
53/ 60
190/190
80/ 90
029A00
73/ 83
190/190
029A00
93/106
190/190
029A00
113/129
190/190
224 + 231 + 226
3
681
=
3
=
227
4
227
WIRING
FIG. NO.
15
15
15
15
16
15
15
15
15
16
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
13
13
13
14
14
14
13
13
13
14
14
14

Advertisement

loading