Carrier 50PG03-16 Installation Instructions Manual page 21

Single−package rooftop units electric heater and single point box accessories

Advertisement

Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet
VOLTAGE
COMPRESSOR
NOMINAL
RANGE
(EA)
UNIT
POWER SUPPLY
50PG
MA
VOLTS-PH-HZ
MIN
RLA
X
03
208/230-1-60
187 253
12.8
208/230-1-60
187 253
15.4
04
208/230-3-60
187 253
11.5
LEGEND
FLA
− Full Load Amps
HACR − Heating, Air Conditioning and Refrigeration
IFM
− Indoor − Fan Motor
LRA
− Locked Rotor Amps
MCA
− Minimum Circuit Amps
MOCP − Maximum Overcurrent Protection
NEC
− National Electrical Code
OFM
− Outdoor−Fan Motor
RLA
− Rated Load Amps
*
Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percentage of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
POWER
OFM
IFM
IFM
EXHAUST
FLA
FLA
TYPE
CRHEATER
FLA
LRA
PART NO.
Low
High
60
0.9
4.9
Low
1.4
High
Low
High
83
0.9
4.9
Low
1.4
High
Low
77
0.9
4.9
High
average voltage
ELECTRIC HEAT
POWER SUPPLY
NOMINAL
FLA
MCA
KW*
/
27.8/27.8
200A00
10.8/12.5
2.3/3.0
27.8/27.8
201A00
17.3/20.0
3.8/5.0
32.8/36.1
202A00
26.0/30.0
5.6/7.5
43.6/48.6
203A00
34.7/40.0
7.5/10.0
54.5/61.1
/
27.8/27.8
200A00
10.8/12.5
2.3/3.0
27.8/27.8
201A00
17.3/20.0
3.8/5.0
32.8/36.1
202A00
26.0/30.0
5.6/7.5
43.6/48.6
203A00
34.7/40.0
7.5/10.0
54.5/61.1
/
29.2/29.2
200A00
10.8/12.5
2.3/3.0
29.2/29.2
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
203A00
34.7/40.0
7.5/10.0
56.2/62.9
/
29.2/29.2
200A00
10.8/12.5
2.3/ 3.0
29.2/29.2
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
203A00
34.7/40.0
7.5/10.0
56.2/62.9
/
31.0/31.0
200A00
10.8/12.5
2.3/ 3.0
31.0/31.0
201A00
17.3/20.0
3.8/ 5.0
32.8/36.1
202A00
26.0/30.0
5.6/ 7.5
43.6/48.6
203A00
34.7/40.0
7.5/10.0
54.5/61.1
204A00
52.0/60.0
11.3/15.0
76.1/86.1
/
31.0/31.0
200A00
10.8/12.5
2.3/ 3.0
31.0/31.0
201A00
17.3/20.0
3.8/ 5.0
32.8/36.1
202A00
26.0/30.0
5.6/ 7.5
43.6/48.6
203A00
34.7/40.0
7.5/10.0
54.5/61.1
204A00
52.0/60.0
11.3/15.0
76.1/86.1
/
32.4/32.4
200A00
10.8/12.5
2.3/ 3.0
32.4/32.4
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
203A00
34.7/40.0
7.5/10.0
56.2/62.9
204A00
52.0/60.0
11.3/15.0
77.9/87.9
/
32.4/32.4
200A00
10.8/12.5
2.3/ 3.0
32.4/32.4
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
203A00
34.7/40.0
7.5/10.0
56.2/62.9
204A00
52.0/60.0
11.3/15.0
77.9/87.9
/
25.0/25.0
207A00
6.3/ 7.2
2.3/ 3.0
25.0/25.0
208A00
10.0/11.5
3.8/ 5.0
25.0/26.0
209A00
15.0/17.3
5.6/ 7.5
30.9/33.2
210A00
20.0/23.1
7.5/10.0
37.2/40.4
211A00
30.0/34.6
11.3/15.0
49.7/54.9
/
25.0/25.0
207A00
6.3/ 7.2
2.3/ 3.0
25.0/25.0
208A00
10.0/11.5
3.8/ 5.0
25.0/26.0
209A00
15.0/17.3
5.6/ 7.5
30.9/33.2
210A00
20.0/23.1
7.5/10.0
37.2/40.4
211A00
30.0/34.6
11.3/15.0
49.7/54.9
Example: Supply voltage is 460-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if
field−supplied pressure connectors are used.
21
DISCONNECT SIZE
CRSINGLE
PART NO.
(NOTE3)
MOCP†
FLA
LRA
30/30
27/27
78/78
30/30
028A00
27/27
78/78
35/40
028A00
31/34
78/78
45/50
028A00
41/46
78/78
60/70
028A00
51/57
78/78
30/30
27/27
78/78
30/30
028A00
27/27
78/78
35/40
028A00
31/34
78/78
45/50
028A00
41/46
78/78
60/70
028A00
51/57
78/78
40/40
29/29
80/80
40/40
028A00
29/29
80/80
40/40
028A00
33/36
80/80
50/60
028A00
43/47
80/80
60/70
028A00
53/59
80/80
40/40
29/29
80/80
40/40
028A00
29/29
80/80
40/40
028A00
33/36
80/80
50/60
028A00
43/47
80/80
60/70
028A00
53/59
80/80
45/45
30/30
101/101
45/45
028A00
30/30
101/101
45/45
028A00
31/34
101/101
45/50
028A00
41/46
101/101
60/70
028A00
51/57
101/101
80/90
029A00
71/80
101/101
45/45
30/30
101/101
45/45
028A00
30/30
101/101
45/45
028A00
31/34
101/101
45/50
028A00
41/46
101/101
60/70
028A00
51/57
101/101
80/90
029A00
71/80
101/101
45/45
32/32
103/103
45/45
028A00
32/32
103/103
45/45
028A00
33/36
103/103
50/60
028A00
43/47
103/103
60/70
028A00
53/59
103/103
80/90
029A00
73/82
103/103
45/45
32/32
103/103
45/45
028A00
32/32
103/103
45/45
028A00
33/36
103/103
50/60
028A00
43/47
103/103
60/70
028A00
53/59
103/103
80/90
029A00
73/82
103/103
30/30
25/25
95/95
30/30
030A00
25/25
95/95
30/30
030A00
25/25
95/95
35/35
030A00
28/31
95/95
40/45
030A00
34/38
95/95
50/60
030A00
46/51
95/95
30/30
25/25
95/95
30/30
030A00
25/25
95/95
30/30
030A00
25/25
95/95
35/35
030A00
28/31
95/95
40/45
030A00
34/38
95/95
50/60
030A00
46/51
95/95
224 + 231 + 226
3
681
=
3
=
227
4
= 100 x
227
= 1.76%
WIRING
FIG. NO.
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
14
13
13
13
13
14
13
13
13
13
14
13
13
13
13
14
15
15
15
15
15
15
15
15
15
15

Advertisement

loading