Mitsubishi Electric VL-250CZPVU-R-E Installation Manual page 20

Lossnay heat recovery ventilator (residential use)
Hide thumbs Also See for VL-250CZPVU-R-E:
Table of Contents

Advertisement

fig 1
+ - + -
1
2
TM200
0-10 V sensor
The unit can be operated by the DC power supply input
from external devices.
Note
- Misconnection may cause malfunction of external
device.
- Make sure to confirm the polarity.
- Make sure to connect electric wires correctly.
- Terminal block has a seal attached on No.2. When using
No.2, remove the seal.
fig 3
Air conditioner
Slim-Lossnay
connection cable
(included)
Mr. slim
Controller
You can control the product by Mr.Slim's remote controller.
Extend the Slim-Lossnay interlocking cable connected to
Slim. Please attach to TM2 of the product.
When interlocked with Mr. Slim, signals from Mr. Slim operate/
stop Lossnay. (The product stops regardless of the Enable off
button setting.)
Note
- Make sure to check the setting of Mr. Slim in line with the
following.
- At the selection of the remote controller functions of Mr.
Slim, check that the Lossnay connectivity setting is set to
Not supported.
- This use method limits the function as below.
- Other external input functions cannot be used together.
- Interlocking commands from Mr. Slim do not operate the
boost/purge modes.
Lossnay
TM2
Controller
Cable
(Field supply)
fig 2
1 2 3 4
TM201
Bypass
Volt-free a contact
Volt-free a contact
Contact ON (closed) becomes input, and contact OFF
(open) becomes OFF.
Note
- Since the circuit ensures 1 mA when the switch is turned
on, the maximum number of switches that can be used
for Volt-Free contact input is one when the minimum
load capacity is 1 mA.
Lossnay external
control input TM2
1
2
3
CN2
Mr. slim PCB
Eng-20
Switch
Rating: DC 15 V, 0.1 A
Minimum applicable load: 1mA
Sensor
TM2
Please extend it
Slim-Lossnay interlocking
cable (Included)