Durablade Economizer Troubleshooting - Carrier 48TFD008-014 Installation And Service Instructions Manual

Single-package rooftop heating/cooling units 50 hz
Table of Contents

Advertisement

PROBLEM
Damper does not
Indoor (evaporator) fan is off.
open.
No power to economizer motor.
Economizer motor failure.
Economizer
OAT or EC set too high.
operation
limited to minimum
position.
Verify economizer control board is
correctly wired and works properly.
Check SAT.
Damper does not
Incorrect wiring of economizer.
close.
Verify economizer control board is
functioning properly.
Check SAT.
Economizer motor failure.
Economizer damper
Verify that close-on-power-loss and
does not close on
economizer control board are func-
power loss.
tioning properly.
LEGEND
C1 — Common Power
EC — Enthalpy Control
IFC — Indoor (Evaporator) Fan Contactor
IFO — Indoor (Evaporator) Fan On
Table 30 — Durablade Economizer Troubleshooting
CAUSE
1. Check to ensure that 24 vac is present at terminal C1 on the IFC or
that 24 vac is present at the IFO terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
2. Check proper thermostat connection to G on the connection board.
1. Check that SW3 is properly making contact with the damper
blade. Check that SW1 is in the NC (normally closed) position.
2. Check diode D1. If diode is not functioning properly, replace D1.
3. Confirm that the economizer control board is grounded properly at
PL6-4 (brown wire) and at brown terminal of the economizer control
board (brown wire). The economizer motor must also be grounded
properly at the negative motor terminal (brown wire).
4. Verify SW1 and SW3 are working and wired properly (see unit label
diagram).
5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black
wire). If 24 vac not present, check unit wiring (see unit label dia-
gram). If 24 vac is found in both places, check for 24 vac at the
yellow terminal of the economizer control board (yellow wire). If
24 vac power is not present, replace the economizer control board.
If the indoor (evaporator) fan and economizer motor are energized,
verify that there is a minimum of 18 vdc at the positive motor
terminal. If the motor is not operating, replace the motor.
1. Set at correct temperature (1.7 C [3 F] below indoor space
temperature).
2. Check OAT or EC by setting above outdoor temperature or humidity
level. If the OAT or EC switches do not close, replace OAT or EC.
1. Perform the following tests when OAT or EC is closed, Y1 is called
for and damper is at minimum position. Confirm 24 vac on gray ter-
minal of the economizer control board (gray wire). If 24 vac is not
present, check wiring (see unit label diagram).
2. Verify that SW1 and SW3 are wired correctly and working properly
(see unit label diagram).
3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If
24 vac is not present, check wiring (see unit wiring label diagram).
4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not
present, replace economizer control board.
1. After verifying that the OAT and EC settings and the economizer
control board wiring are correct, check to ensure that the 24 vac
terminal of the SAT has 24 vac (white wire). If OAT, EC, and control
board are functioning and wired properly and no 24 vac exists,
check wiring (see unit label diagram).
2. If supply-air temperature is greater than 14 C (57 F), 24 vac should
be found at terminal T2 on the SAT (pink wire). If 24 vac is not
present, replace SAT.
1. Verify that SW2 and SW4 are wired and working properly (see unit
label diagram).
2. Check diode D2. If diode is not functioning properly, replace D2.
1. After verifying that the wiring is correct, modulate the damper to the
minimum position. Remove the call for G (evaporator fan).
2. If the damper does not move, check for 24 vac at PL6-1 (red wire).
If 24 vac is not present, check wiring (see unit label diagram).
3. If damper still does not move, check for 24 vac at blue terminal of
economizer control board (blue wire). If 24 vac is not present,
replace the economizer circuit board.
1. After verifying that the wiring is correct and the economizer control
board is functioning properly, place the OAT or EC switch in the
closed position. Place a call for Y1 and open the damper to the fully
open position. Confirm that the 24 vac terminal of the SAT has
24 vac (white wire). If 24 vac is not present, check wiring (see unit
label diagram).
2. If supply-air temperature is less than 11 C (52 F), 24 vac should be
found at terminal T1 on the SAT (violet wire). If 24 vac not found,
replace SAT.
If economizer control board and SAT are functioning properly, verify
that there is a minimum of 18 vdc at the positive motor terminal. If a
minimum if 18 vdc is present and the motor is still not operating,
replace the motor.
1. Check voltage potential across batteries. If lower than 14 vdc,
replace close-on-power-loss power supply (9-v alkaline batteries). It
is recommended that you check this emergency power supply on a
regular basis or whenever the filters are changed.
2. If the close-on-power-loss and economizer control board are func-
tioning properly, check for 14 vdc or higher at the blue terminal of
the economizer control board (blue wire) when power is discon-
nected from unit. If 14 vdc is not present, replace the control board.
OAT — Outdoor-Air Thermostat
PL
— Plug
SAT — Supply-Air Thermostat
SW — Economizer Position Switch
REMEDY
45