MDT KNX Smart 55 BE-JTA5504.01 Technical Manual page 54

Blind push button
Table of Contents

Advertisement

Technical Manual
Blind Push Button Smart 55
The following table shows the available settings:
ETS-Text
Request logic objects after
reset
Setting Logic A - H
Object type for logic
output
Sending condition
Invert output
Scene number
1Byte Value
Percent value
Input logic 1 – 4
Table 36: Settings – Logic A-H
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
54
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
BE-JTA5504.01
Dynamic range
[Default value]
not active
active
not active
AND
OR
XOR
switch
scene
value
percent value
not automatic
input telegram
change of output
change of output only
value 1
change of output only
value 0
no
yes
1 – 64
[2]
0 – 255
[0]
0% – 100%
[0%]
not active
active normal
active inverted
Comment
Setting whether the logic objects are to
be automatically requested after
restarting the unit.
Setting the logical operation
Setting the object type for the output
object
Setting when the value of the output is
sent.
Only available with object type for
logic output "switch".
Reverses the output when activated
(0  1, 1  0)
Only available with object type for
logic output "switch".
Setting which scene is sent when the
logic function is fulfilled.
Only for the output object type
"scene".
Setting which value is sent when the
logic function is fulfilled.
Only for the output object type
"value".
Setting which percentage value is sent
when the logic function is fulfilled.
Only for the output object type
"percent value".
Setting how an input is to be included in
the evaluation