Page 1
DESIGN, INSTALLATION, OPERATION AND MAINTENANCE MANUAL DuraQuench™ WET PIPE SYSTEM WITH OH‐VSO NOZZLES FOR PROTECTION OF NON‐STORAGE OCCUPANCIES, HAZARD CATEGORY 1 (HC‐1) P/N 06‐791‐4 Rev. 4 SOLUTIONS Fire Protection Explosion Protection Overpressure Protection Pressure Activation ...
Page 2
You should install and use the Fike products described in this document within the range specified by Fike, especially with respect to the product application, maximum ratings, operating supply voltage range, installation and other product characteristics. Fike shall have no liability for malfunctions or damages arising out of the use of Fike products beyond such specified ranges. You should install and use the Fike products described in this document in compliance with all applicable laws, standards, and regulations. Fike assumes no liability for damages or losses occurring as a result of your noncompliance with applicable laws and regulations. It is the responsibility of the buyer or distributor of Fike products, who distributes, disposes of, or otherwise places the product with a third party, to notify such third party in advance of the contents and conditions set forth in this document. ...
Page 3
HANGE O INGER ALVE 9. ADDED ARIABLE REQUENCY RIVE ONTROLLER OPTION REORGANIZED SECTIONS THROUGH 4 2020 EVISED UMP KID ONFIGURATION O EFLECT ADDITION OF CIRCULATION ELIEF ALVE AND EBRUARY PDATED UMP KID RDERING NFORMATION P/N 06‐791‐4 (Rev. 4) Page I 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
1. INTRODUCTION 1.1. General DuraQuench is an FM Approved single fluid water mist system for the protection of non‐storage occupancies, Hazard Category 1 (HC‐1). The primary components of the DuraQuench Wet Pipe system consists of a fire pump skid, patented OH‐VSO fine water spray nozzles, ancillary FM Approved components (i.e., control valves, backflow preventers, isolation valves, etc.), and a reliable water source (i.e., public mains, gravity tanks or other suitable water sources). These components are connected together as a system to deliver water mist to the protected enclosure to control, suppress, or extinguish fires. With a minimum operating pressure of 116 psi (8 bar) and a maximum operating pressure of 232 psi (16 bar) at the system nozzles, the system is classified by NFPA 750, Standard on Water Mist Fire Protection Systems as an intermediate pressure system. 1.2. System Description When configured as a Wet Pipe System, DuraQuench is a fixed protection system in which the pipe system is filled with pressurized water up to the nozzles during normal standby operation. A system check valve serves to maintain system pressures in the piping network. Wet pipe systems may be installed in any structure that is reliably maintained above 40°F (4°C). Closed, heat‐sensitive, automatic nozzles located and spaced throughout the protected areas are used to detect a fire. Optional smoke detectors can be installed in the protected area to provide advanced notification of a fire event. Upon activation of a nozzle due to heat from the fire, water will begin to flow immediately from the open nozzle and will cause a drop in system pressure. Depending upon the system configuration, either the flow of water or the pressure ...
Both the WAC valve’s water flow sensor and the water flow switch have an adjustable time delay that inhibits the initiation of a water flow signal in order to reduce the possibility of false alarms and false activation of the pump that can be caused by pressure drops or fluctuations in the water supply. Figure 1 shows the typical components and arrangements that make up a DuraQuench Wet Pipe system with an Alarm Check Valve. Figure 1: Wet Pipe System 1. Suction isolation valve (monitored) 16. Riser stop valve (monitored) 2. Suction flange 17. Wet Alarm Check valve (WAC) 3. Suction basket strainer 17a. Drain valve (part of WAC valve) 4. Suction pressure gauge 17b. Water flow switch (part of WAC valve) 5. Circulation relief valve (opens at 275 psi/19 bar) 17c. Inlet pressure gauge (part of WAC valve) 6. Centrifugal pump and motor 17d. Outlet pressure gauge (part of WAC valve) 7. Test header isolation valve (monitored) ...
Section 3.11 for water supply requirements) be relatively free from pressure fluctuations and the pipe network be designed to provide the water flow required to trip the flow switches used for pump activation and alarm notification, based on the activation of a single OH‐VSO nozzle. Hydraulic calculations must be performed on the pipe network prior to installation to confirm that the water supply is capable of providing the pressure required to obtain the water flows required for pump activation. In addition, the installed system must be functionally tested using the remote test valve and an OH‐VSO orifice test fitting to verify pump activation based on the activation of a single nozzle. If the water supply is NOT capable of providing sufficient flow and pressure for pump activation, a pressure maintenance pump system, as detailed in Section 1.2.2, must be installed. Wet Pipe System with a Pressure Maintenance Pump NOTE ‐ DuraQuench systems configured with a pressure maintenance pump are not within the scope of the system’s FM Approval. This system configuration (see Figures 3 and 4) incorporates a pressure maintenance (jockey) pump into the DuraQuench system. The jockey pump can be mounted directly onto the pump skid or field installed off the pump skid. The jockey pump installation will include a separate jockey pump controller and its own independent pressure sensing line connection. The purpose of the jockey pump is two‐fold. The first purpose is to maintain a higher pressure on the system side of the Fike Wet Alarm Check Valve (WAC) than the standard water supply can reach. The higher pressure holds the clapper of the WAC valve and Water Flow switch closed even when the water supply pressure fluctuates. This eliminates false ...
As the water spray is converted to steam, it expands approximately 1,700 times forcing oxygen away from the vicinity of the droplet. This results in dilution of the air (oxygen) supply within the protected enclosure. If the amount of oxygen necessary to support combustion is reduced below a critical level (14% – 13%), the energy output of the oxidation process fails to become close to the energy input the fire requires to sustain the chemical fire process which will cause the fire to burn inefficiently making it easier to extinguish. Blocking of Radiant Heat As water mist is released into the protected enclosure, the fine water droplets block the radiant heat generated by the fire from getting to unignited fuel surfaces and reduces the radiant heat flux between the flame and the fuel surface. 1.4. Water Mist Versus Traditional Sprinkler System Water mist has several advantages over conventional sprinkler systems. One of the key benefits of the DuraQuench system is that it typically uses 75% less water than a sprinkler system. With a water mist system, the majority of the water droplets are evaporated by the heat and hot gases generated by the fire resulting in much less water damage to the protected property and a dramatic reduction in downtime for cleanup. In light hazard applications, the reduced downtime means that the facility will be able to resume normal operations very quickly after a fire event. In contrast, traditional sprinkler systems spread large water droplets over the protected enclosure to absorb heat and cool the room. Due to the large size and relatively small surface area of sprinkler water droplets, they will not absorb enough energy to evaporate and quickly fall to the floor as water. This results in limited cooling of the fire and greater water damage to the protected property causing a large increase in facility downtime due to the fire event. P/N 06‐791‐4 (Rev. 4) ...
1.5. Approvals The DuraQuench wet pipe water mist system is FM Approved to FM5560 Appendix G for the protection of non‐storage occupancies, Hazard Category 1 (HC‐1). Applications include but are not limited to the following: Apartments Meeting rooms in convention centers and hotels Atriums Metalworking shops with non‐hydraulic cutting operations Churches Mineral processing (i.e.: glass, cement, ore treating, gypsum processing, etc.) Concealed Spaces Museums Gymnasiums Nursing or convalescent homes Hospitals Offices Hotel rooms Restaurant seating areas Institutions Schools and university classrooms ...
2. EQUIPMENT The DuraQuench wet pipe water mist system consists of a number of OH‐VSO nozzles and wet pipe alarm check valve connected by a piping network to a continuous pressure pump skid unit, which is connected to a suitable water source (i.e., public mains, gravity tanks, reservoirs, etc.). This section provides a description of the components that can be used to construct the DuraQuench wet pipe water mist system. 2.1. Sourcing System Components The DuraQuench pump skid unit and the OH‐VSO nozzles are the only two components that must be purchased from Fike in order to maintain FM Approval. The remaining system components including wet alarm check valve, detection and control panel, control valves, piping, switches, etc. can be sourced from other suppliers. The operating pressure requirement of the DuraQuench system allows the use of traditional FM Approved sprinkler components and wet pipe system valves. Components selected for use on the DuraQuench system shall be FM Approved for use in wet pipe sprinkler systems. All system components should be a part of an FM Approval follow up service. It is very important to verify that the components are suitable for use in the DuraQuench system regarding: Component materials ...
Page 18
Ordering 02‐14870‐A‐B‐C‐D‐E A (Material): 1 = Brass; 2 = SST B (Threads): 1 = ½ NPT; 2 = ½ BSP C (Cover Plate): 1 = Chrome Plated; 2 = White (RAL 9010) D (Temperature): 1 = 57°C (135°F)*; 2 = 68°C (154°F); 3 = 79°C (174°F); 4 = 93°C (199°F) E (Drop Pipe Length)** FM Approved release temperature. Optional dry unit extension for use on wet pipe systems where pipe connections are exposed to a temperature below 32°F (0°C). NOT FM Approved for use with the DuraQuench wet pipe system protecting HC‐1 hazards. Refer to data sheet W.1.30.01 for details. Specifications General Weight 0.46 lbs. (0.211 kg ) Housing Material Brass (NiSn coating) Strainer Material Stainless Steel 316L Thread Type ½” NPT or ½” BSP Chrome or White Cover Plate Finish (other RAL colors available) Minimum Water Pressure 116 psi (8 bar) Maximum Working Pressure 232 psi (16 bar) 1.16 (gal/min/√psi) K‐factor 16.7 (l/min/√bar) Droplet Size < 300 μm FM Approved Nominal Release Temperature 135°F (57°C) Ambient Installation Temperature Range 40°F to 100°F (4°C to 38°C) Application Maximum Ceiling Height 16’‐5” (5 m) ...
OH‐VSO nozzle after the nozzles have been correctly fitted in the pipe system. Specifications 02‐14879‐1 (Stainless Steel Plating) Figure 8: OH‐Trim Ring 02‐14879‐2 (RAL 9010) Part Number 02‐14879‐3 (Stainless Steel Plating, lock screws) 02‐14879‐4 (RAL 9010, lock screws) Material 316 Stainless Steel Weight 0.39 oz (12 g) Finish Raw material or RAL‐9010 (other RAL colors available) Dimensional Information Figure 9: OH‐Trim Ring Dimensions 2.4. Spanner Wrench The spanner wrench is designed for fast, correct and safe installation of the OH‐VSO nozzle. The nozzle to be installed is placed in the spanner and is screwed into the pipe system. The nozzle is correctly positioned when the circular spanner mark is flush to the ceiling surface. The spanner requires an installation hole of 1 7/8” (48mm) Ø. Figure 10: Spanner Wrench Specifications Part Number 02‐15267 Materials DIN 2391 / C35 Chrome Plate Weight 17.7 oz (550 g) Dimensions 8.78” x 1.42” (223 mm x 36 mm) Page 12 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
2.5. Pump Skid The pump skid unit is the primary control center for Fike’s DuraQuench water mist system providing the necessary flow and pressure to the system pipe network and spray nozzles. The compact skid unit is factory assembled, pre‐wired, pre‐piped and functionally tested prior to shipment from the factory which reduces the time and labor required for field installation. The skid unit is designed to meet the requirements of NFPA 750, Standard on Water Mist Fire Protection Systems, NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and FM Datasheet 3‐7, Fire Protection Pumps. The primary components of the pump skid unit include a full service fire pump controller wired to an electric motor coupled to a centrifugal ...
11 Test Header Isolation Valve Allows the water supply from the fire pump to be routed to a connected test header (butterfly) for the purpose of measuring the system flow rate during acceptance testing and during annual testing. 12 Test Header Pipe Connection Pipe flange allows easy connection of test header piping to the pump skid. See System Piping Connections for flange sizes. 13 Pump Controller Provides a means to start the fire pump automatically or manually in response to a fire event. Provides remote alarm connections for fire pump monitoring (i.e., pump running, AC power failure, phase reversal, etc.). Controller can be activated via a normally closed remote contact from a releasing control panel (deluge system) or via a pressure sensing line connection (wet pipe system). 14 Motor Bracing Strap Provides bracing of pump motor. Pump Skid with Pressure Maintenance Pump Components For installations where a jockey pump is required, a pressure maintenance (jockey or make‐up) pump kit (P/N 02‐15270) can be ordered from Fike. The kit includes a jockey pump controller dual rated for 50/60 Hz and a 3.5 GPM centrifugal pump coupled to a 50/60 Hz motor. If initially ordered as part of the pump skid, the jockey pump and required check and isolation valves will be factory mounted onto the DuraQuench pump skid, as shown in Figure 13. The jockey pump controller (included with the kit) must be mounted off the pump skid. The pressure sensing line and pump motor control wiring connections form the jockey pump to the jockey pump contller must be filed installed in accordance with the requiremnts of NFPA 20. NOTE ‐ DuraQuench systems configured with a pressure maintenance pump are not within the scope of the DuraQuench FM approval. Figure 13: Pump Skid Configuration with Factory Installed Jockey Pump Page 14 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Page 23
Provides a path for continuous water flow through the pump when the pump is operating in churn (no flow) condition. 13 Relief Valve Allows the diversion of water through the recirculation loop to limit excess pressure in the system. 14 Test Header Isolation Valve Allows the water supply from the fire pump to be routed to a connected test header (butterfly) for the purpose of measuring the system flow rate during acceptance testing and during annual testing. 15 Test Header Pipe Connection Pipe flange allows easy connection of test header piping to the pump skid. See System Piping Connections for flange sizes. 16 Pump Controller Provides a means to start the fire pump automatically or manually in response to a fire event. Provides remote alarm connections for fire pump monitoring (i.e., pump running, AC power failure, phase reversal, etc.). Controller can be activated via a normally closed remote contact from a releasing control panel (deluge system) or via a pressure sensing line connection (wet pipe system). 17 Motor Bracing Strap Provides bracing of pump motor. 18 Jockey Pump Controller (not Provides a means to start and stop the jockey pump automatically in response to shown) a drop in pressure in the system piping. Jockey pump controller shall be located as close as practical to the pump skid. P/N 06‐791‐4 (Rev. 4) Page 15 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Page 24
Pump Skid Ordering Format The DuraQuench pump skid can be ordered with different pump controller and pump combinations. When ordering the pump skid, it is extremely important to verify the voltage and frequency (50/60 Hz) of the power feed supplying the pump skid before selecting the appropriate pump skid part number. The voltage and frequency of the pump controller and the pump selected must be compatible with the available power supply. The fire pump controller is available in the following configurations: 1) Standard single source pump controller provides across‐the‐line full voltage starting for the three phase motor driven pump. No transfer switch included. 2) Dual source pump controller incorporates a transfer switch directly into the standard pump controller enclosure. The transfer switch provides for automatic transferring of the pump load from one power source to another (self‐ acting). 3) Variable speed fire pump controller provides a variable frequency drive (VFD) built into the standard pump ...
Page 26
2,7 02‐14909‐5‐2‐22‐1 5 (133 gpm/503 lpm) 2 (50 Hz) 22 (208 V/ dual source) 1 (Standard) 2,4,6 02‐14909‐5‐2‐22‐2 5 (133 gpm/503 lpm) 2 (50 Hz) 22 (208 V/ dual source) 2 (Soft) 2,4,7 02‐14909‐5‐2‐27‐1 5 (133 gpm/503 lpm) 2 (50 Hz) 27 (400 V/ dual source) 1 (Standard) 2,6 02‐14909‐5‐2‐27‐2 5 (133 gpm/503 lpm) 2 (50 Hz) 27 (400 V/ dual source) 2 (Soft) 2,7 Notes: Single power source controller. Dual power source controller with integral automatic transfer switch. Variable frequency drive controller. Transfer switch, if required, must be ordered separately. Pump motor has been tested for operation at 208 V. Jockey pump, if required, must be ordered separately on all skids using P/N 02‐15270. Controller provides Standard Across the Line motor starting. Controller provides motor soft starter. Page 18 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Page 27
100 psi 100 psi 100 psi 100 psi 100 psi 100 psi Pressure*** (6.9 bar) (6.9 bar) (6.9 bar) (6.9 bar) (6.9 bar) (6.9 bar) ‐4 to +248 °F ‐4 to +248 °F ‐4 to +248 °F ‐4 to +194 °F ‐4 to +248 °F ‐4 to +248 °F Liquid Temp. Range (‐20 to +120 °C) (‐20 to +120 °C) (‐20 to +120 °C) (‐20 to +90 °C) (‐20 to +120 °C) (‐20 to +120 °C) *Usable at 208 Volts. **The motor’s inrush current, also known as locked‐rotor amps or LRA, can be calculated by inserting the KVA/HP value into the following formula: LRA = KVA/HP x Motor HP x 1000 / 1.732 x Motor Voltage ***Current inlet pressure + churn (no flow) pressure must always be lower than the maximum permissible system operating pressure to prevent potential damage to the bearing in the motor or reduced life of the shaft seal. ****Pump speed on which data is based. P/N 06‐791‐4 (Rev. 4) Page 19 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Page 28
Specific name plated Horsepower Rating Specific name plated motor horsepower rating motor horsepower rating Motor Service Factor 1.15 maximum 1.15 maximum Voltage free contacts rated for 2 amps (resistive) at 30 Remote Contacts NA VDC, or 1 amp (resistive) at 125 VAC Pressure Rating 300 PSI (20.7 bar) standard 300 PSI (20.7 bar) standard Pressure Sensing Line ½” nominal, brass ¼”‐18 NPT, brass Enclosure NEMA Type 2 with drip lip NEMA Type 2 with drip lip 122° F (50° C) provided input and output cable has a temperature rating of 221°F (105°C) Ambient Operating 104° F (40° C) provided input and output cable has a Temperature temperature rating of 194°F (90°C) No direct sunlight allowed on the enclosure. Electromagnetic Tested to comply with EN 61000‐6‐2 for immunity and Compatibility EN 6100‐6‐4 for emissions Page 20 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
2.6. Wet Alarm Check Valve (WAC) The Wet Alarm Check (WAC) valve is a clapper and wafer style check alarm valve designed to be installed in wet pipe water mist systems downstream from the system pump where the valve is fitted between two flanges. The valve is capable of detecting the small water flows which are common in the DuraQuench system. The valve has built in inlet and outlet pressure gauges, a drain valve, an inductive alarm sensor and Anti‐False Alarm (AFA) unit. The valve’s inductive alarm sensor provides an electrical means to detect water flow through the valve without direct contact with moving parts. The AFA is connected to the WAC valve and monitors the inductive alarm sensor for indication of water flow. The AFA provides a factory set time delay of 8 – 10 seconds, which reduces the risk of false alarms coming from pressure shocks in the pipe system. The unit provides a relay contact that provides a means to send a signal to the alarm panel for activation of a water flow alarm bell. The unit ...
2.7. Check Valve The ARGCO Check Valve is used in a DuraQuench system to prevent the reversal of water flow. In the fully‐open position the clapper is held tightly against the valve body, out of the flow stream, to provide maximum flow area and prevention of clapper flutter. The clapper design produces quick, non‐slam closure before flow reversal can occur while meeting FM requirements for anti‐water hammer valve rating. Each valve is hydrostatically tested for leak tightness to 500 PSI. Specifications 02‐14915‐1 (2”) 02‐14915‐2 (2 1/2”) Part Number Figure 17: Check Valve 02‐14915‐3 (3”) Working Pressure 300 psi (20.7 bar) Maximum Test Pressure 500 psi (34.5 bar) Working Temperature 250°F (120°C) maximum 8 lbs. (3.63 kg)(2” & 2 1/2”) Weight 11 lbs. (4.99 kg)(3”) ...
2.8. Control Valves The butterfly control valves are used on the DuraQuench water mist system for the following functions: Suction (supply) Isolation Control Valve, Test Header Isolation Valve, Discharge Isolation Control Valve, Riser Inlet Isolation Valve and Riser Outlet Isolation Valve. These valves are designed to be installed in any orientation and monitored to signal if the valve is opened or closed. The valves are designed to open and close slowly to prevent water hammer. They are FM Approved for Fire Protection Use. Each valve is equipped with a tamper switch assembly suitable for indoor or outdoor use. The tamper switch features two switches. Switch 1 can be used for connection to a supervisory circuit of a listed fire alarm control panel. ...
The VSR switches and retard device are enclosed in a general purpose, die‐cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. Figure 27: Pressure Switch Specifications 02‐15337‐1 (2”) Part Number 02‐15337‐2 (2 1/2”) 02‐15337‐3 (3”) Service Pressure 450 psi (31 bar) Flow Sensitivity Range for Signal 4‐10 gpm (15‐38 lpm) Maximum Surge 18 fps (5.5 m/s) 10.0 Amps at 125/250VAC Contact Ratings 2.0 Amps at 30VDC Resistive (Two sets of SPDT (Form C)) 10 mA min. at 24VDC Conduit Entrances Two knockouts provided for 1/2" conduit Enclosure Rating NEMA 4 / IP54 (indoor or outdoor) Temperature Range 40°F – 120°F, (4.5°C – 49°C) FM Approved UL Listed Listing / Approval LPCB Approved VdS Approved P/N 06‐791‐4 (Rev. 4) Page 29 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
2.13. Pressure Relief Valve The AGF Manufacturing Inc. Pressure Relief Valve is used in a DuraQuench system to relieve excess system pressure caused by surges or temperature changes. This valve complies with NFPA‐13 which stipulates that a pressure relief valve be installed on all gridded systems and downstream of all pressure reducing valves. This valve has a bronze body, stainless steel spring, and flushing handle to remove debris. Specifications 02‐14932‐1 (1/2”) Part Number 02‐14932‐2 (3/4”) 185 psi (12.8 bar) – ½” Pressure Rating 250 psi (17.24 bar) – ¾” Temperature Range 33° ‐ 140°F (1° ‐ 60°C) Figure 32: Relief Valve 1/2” MIPT Inlet & FIPT Outlet Connections 3/4" MIPT Inlet & FIPT Outlet MATERIALS Body Bronze Spring Stainless Steel Listing / Approval FM Approved Dimensions ...
Valve Size L A B C D Kv/Cv Kg/lb 2.30 mm 77.5 mm 155 mm 77 mm 120 mm 80 5 m 19.3 2”/DN50 [9.1 in.] [3 in.] [6.1 in.] [3.03 in.] [4.69 in.] [92] [16 ft.] [42.5 lb.] Notes: [1] Kv/Cv values given for a fully opened valve. [2] Leq (Equivalent Pipe Length) refers to a fully opened valve with turbulent flow in new steel pipe schedule 40. Values given for general consideration only. P/N 06‐791‐4 (Rev. 4) Page 33 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
These signs are manufactured from 0.020” white coated aluminum, screen printed with a fade‐resistant red ink and shipped with a clear protective coating to prevent scratching of finish during shipment and installation which can be removed after installation. DESCRIPTION PART NUMBER SIGN SIZE Drain Valve Sign 02‐15230 6” x 2” (152 x 51mm) Fire Alarm Sign 02‐15231 9” x 7” (229 x 178mm) Blank Sign 02‐15232 6” x 2” (152 x 51mm) Normally Open Sign 02‐15233 6” x 2” (152 x 51mm) Hydraulic System Sign 02‐15234 8 1/2” x 11” (216 x 279mm) Inspection Test Sign 02‐15235 6” x 2” (152 x 51mm) Page 34 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
A test connection shall be provided on all water mist system, as outlined in NFPA 750. Specifications Part Number 02‐14942 Material Polished Brass Inlet 2‐1/2” female NPT Outlet Male hose thread snoot with cap and chain Figure 37: Test Connection Lettering 8” plate “HYDRANT” Listing / Approval FM Approved Dimensions 8” 1 7/8” Figure 38: Test Connection Dimensions P/N 06‐791‐4 (Rev. 4) Page 35 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
ASTM B‐75/B‐88 Welded, Brazed, Flared, Compression CAUTION To prevent clogging of the system nozzles, it is prohibited to use components with black iron, hot galvanized or electro galvanized pipe and system components used in traditional sprinkler systems, because of corrosion and risk of loose zinc flakes. When using CPVC pipe on a wet pipe system, the pipe and fittings must be approved per FM 1635, Approval Standard for Plastic Pipe and Fittings for Automatic Sprinkler Systems. CPVC pipe is not permitted to be used in seismically active areas in accordance with FM Global Loss Prevention Data Sheet 2‐8. CPVC pipe must be shielded from the fire area by a non‐removable barrier having a fire rating equal to or greater than 1 hour. A pressure reducing valve (See Section 2.14) MUST be installed in the system pipe network just prior to transitioning to CPVC. The PRV is required to regulate the inlet pressure supplied to the CPVC distribution piping to a maximum service pressure of 175 psi (12 bar) in order to prevent over‐pressurization. Refer to FM Datasheet 3‐11 for the use of the PRV. NOTE: From this point forward, where the word pipe is used it shall imply tubing as well. Fittings Fittings shall have a minimum rated system design working pressure equal to or greater than the maximum operating pressure of the water mist system at 130°F (54°C) and shall have corrosion resistance at least equivalent to wrought copper fittings conforming to ASME/ANSI B16.22, Wrought Copper and Alloy Solder Joint Pressure Fittings. Galvanic Corrosion To avoid galvanic corrosion from occurring in the water mist system, all component materials incorporated into the system shall be compatible so no galvanic reaction can take place, or as a minimum be electrically insulated from the pipe materials to the satisfaction of FM Approval and the authorities having jurisdiction. P/N 06‐791‐4 (Rev. 4) Page 37 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
3. DESIGN This section details the steps necessary to design a DuraQuench water mist system for wet pipe operation. It is the responsibility of the system designer to ensure that the DuraQuench water mist system is: 1. Fully designed in accordance with the design guidelines of this manual as well as the applicable guidelines and requirements of FM Global, NFPA 750, NFPA 13, and the requirements of the authorities having jurisdiction. 2. Fully documented to the satisfaction of FM Global and the authorities having jurisdiction (AHJ). Design shall be reviewed and accepted by the authorities having jurisdiction prior to the installation. 3. Applied using system components of good quality and reliable products, which are accepted and approved by FM Global and the AHJ, and that are suitable for their particular use in the system. See Section 2.1. 4. Designed to fully match the location and application to be fire protected. 5. Hydraulically designed from water supply to water mist nozzles. The hydraulic design shall ensure that minimum requirements of water flow and water pressure on all nozzles meets the design criteria and is ...
All water mist system components (e.g., nozzles, piping, detectors, etc.) shall be located to maintain minimum clearances from unenclosed and uninsulated energized electrical components in accordance with NFPA 70, National Electrical Code. Refer to NFPA 750, Standard on Water Mist Fire Protection Systems for further information and clearance data. 3.3. Alarm Check Valve Fike recommends using the Wet Alarm Check (WAC) valve in conjunction with the DuraQuench system; however, any FM Approved wet alarm check valve can be used as long as it complies with the following criteria: 1. Valve must be capable of handling the maximum working pressure created by the DuraQuench system 232 psi (16 bar). 2. Valve must be capable of handling the water flow requirements required by the DuraQuench system. 3. Valve must be constructed of corrosion resistant materials in order to minimize the risks of clogging the water mist nozzles. 4. Friction losses associated with the valve must be compatible with the performance criteria of the system. 5. Valve must be FM Approved and be capable of sounding an alarm upon activation of one OH‐VSO nozzle. Where the WAC valve is used, refer to Fike document 06‐791‐5. Otherwise, refer to the documentation supplied with ...
If an existing detection system is used in a new water mist system, the detection system shall be evaluated for compliance with the standards identified above and the requirements outlined in this document. Detector Requirements The detector requirements for each DuraQuench water mist system will vary according to the specific hazard requirements. Selection of the type of detector to use for releasing of the system shall be based on a thorough review of the project requirements. ...
Planning shall include considerations for equipment access, heating, lighting, emergency lighting and ventilation. The pump room shall provide protection for both the pump operator and pumping equipment during a fire event. Consideration should be given to locating the pump room at grade level, with direct access to the exterior of the building, to provide quick and easy egress for the pump operator and access to the pumping equipment for fire department personnel. Where the pump room cannot be located on grade with direct access from the outside of the building, a fire rated and protected space must be provided. The space must be accessible through an enclosed passageway from an exterior exit from an enclosed stairway. 3.11. Water Supply The water supply source for the DuraQuench system shall meet the requirements of NFPA 750, NFPA 13, and FM Global, with exceptions to the water density, water flows, and pipe system materials described in this manual. The water supply source shall comply with the overall design of water supply systems for wet pipe sprinkler systems for fire protection of similar locations. Water Supply Source The water supply shall be supplied by one of the following sources: 1. A connection to a reliable waterworks system (public service main) capable of providing the necessary water flow, water pressure, and quantity of water needed for the operation of the water mist system. Adequacy and dependability of the water source shall be fully determined from a water flow test or other approved method ...
4. No additives allowed for an FM approved system. Water Supply Capacity The water supply, when operating under reasonable, anticipated, worst‐case conditions must be capable supplying 150% of the pump’s rated flow for the required duration of the water demand at the minimum inlet pressure (NPSHR) required by the pump in accordance with the requirements of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and FM Property Loss Prevention Data Sheet 3‐7, Fire Protection Pumps. The water supply must also be capable of maintaining a positive pump suction pressure at the pump inlet while providing the maximum fire protection system demand at residual pressure. Maintaining a positive suction pressure at the pump inlet helps to reduce the potential for cavitation within the pump, which can reduce the efficiency or even cause damage to the fire pump. If the water supply cannot provide 150% of the rated flow of the pump, but can provide the maximum flow demand of the system, it shall be deemed to be adequate; however, a sign shall be placed in the pump room indicating the minimum suction pressure that the fire pump is allowed to be tested at and also indicating the required flow rate. The minimum NPSHR for the pumps used on the DuraQuench system can be obtained from the pump curves provided in Annex C. The minimum NPSHR shall be selected at the highest flow the pump will be delivering plus a safety margin of 2.0 feet (0.61m). CAUTION Do not exceed the manufacturer’s set limits for the pump with regards to maximum inlet pressure and maximum operating pressure. See Motor and Pump Specifications on Page 19. The water supply capacity shall meet the hydraulically calculated design flow requirements and the minimum system flow duration requirements of the actual system as listed in the following table. Applicable Standard Minimum System Discharge Duration 30 minutes to the hydraulically most remote nine automatic nozzles or all automatic NFPA 750 (Light nozzles within a 1,500 ft (140 m...
3.12. Design Process The basic design principals of the DuraQuench wet pipe water mist system are identical to that of traditional sprinkler wet pipe systems. The following process shall be used to properly design a DuraQuench wet pipe water mist system for protection of non‐storage occupancies. Determine Nozzle Layout The OH‐VSO nozzles shall not be installed in locations containing materials which may produce violent reactions or significantly hazardous materials when reacting with water and should be installed in locations where the nozzle is not likely to sustain physical damage. The nozzles shall be installed within the protected enclosure in a homogenous grid covering the whole area of the enclosure. Spacing of the nozzles shall be in accordance with the requirements listed below. Maximum ceiling height 16.42 ft. (5 m) Minimum ceiling height 6.6 ft. (2 m) Maximum nozzle spacing 14.75 ft. x 14.75 ft. (4.5 m x 4.5 m) Minimum nozzle spacing 7.42 ft. x 7.42 ft. (2.25 m x 2.25 m) Maximum nozzle distance to wall 7.33 ft. (2.25 m) Minimum nozzle distance to wall 3.17 ft. (1.125 m) ...
Nozzle Obstructions Care should be given when installing the OH‐VSO nozzles adjacent to major obstructions. A major obstruction is defined shall be defined as an object which obstructs a significant portion of the spray from the OH‐VSO nozzle. If the area to be protected houses one or more major obstructions (i.e., beams, walkways, ductwork, etc.) additional nozzles shall be installed adjacent to the obstructions. If it is not possible to protect the area underneath or next to the obstruction, depending upon the elevation of the obstruction, additional OH‐VSO nozzles shall be installed beneath the obstruction in order to provide a homogenous distribution of the water mist in the enclosure. For more on obstructions, see Annex C. NOTE ‐ Systems with nozzles installed as described in this section are not part of the DuraQuench system FM Approval. Determine Nozzle Flow Rate Use the following formula to calculate the flow rate from each OH‐VSO nozzle using the given K‐factor for the nozzle (1.16 (gal/min/√psi or 16.7 (l/min/√bar). The K‐factor is a constant that gives the ratio between the flow rate and the pressure at the nozzle. System pressure (P) at the nozzle will vary between 116 to 232 psi (8 – 16 bar). The most favorable condition shall be considered. Q = K * P Where: Q = Flow from the nozzle (gal/min or l/min.) K = Nozzle K factor (gal/min/psi or l/min/bar) P = Pressure at the nozzle (psi or bar) Determine System Flow Rate The system shall be capable of supplying water to the hydraulically most remote nine nozzles or all nozzles within a 1,500 ft (140 m ) demand area, whichever is greater. If the demand area is less than 1,500 ft (140 m ) in area, the system shall be capable of supplying water to all nozzles in the protected area. To calculate the total flow rate for the system, multiply the calculated nozzle flow rate by the total number of nozzles serving the remote demand area. = Q * N Where: = Total flow for the demand area (gal/min or l/min.) Q = Flow from the nozzle (gal/min or l/min) = Total number of nozzles Page 44 P/N 06‐791‐4 (Rev. 4) ...
= Q / q PUMPS MAX Where: = Number of pumps PUMPS = Total flow for area (gal/min or l/min) + safety factor (10% NFPA or 20% FM) q = Flow rate output of selected pump unit NOTE ‐ Using the formula above, in most cases, will result in the selection of a fire pump that is oversized for the application. Hydraulic calculations shall be performed in order to determine the actual required capacity of the fire pump. P/N 06‐791‐4 (Rev. 4) Page 45 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Figure 40: Relationship between motor output (P ) and ambient temperature/altitude Example: From Figure 40 it appears that P2 must be reduced to 88% when a pump with NEMA premium efficiency ML motor (Fike pumps) is installed 15,584 feet above sea level. At an ambient temperature of 167°F, P2 of a standard efficiency motor must be reduced to 74% of rated output. In cases where both the maximum temperature and the maximum altitude are exceeded, the derating factors must be multiplied. Example: 0.89 x 0.89 = 0.79. Determine Distribution Piping Layout The piping system for the DuraQuench wet pipe water mist system shall be designed in accordance with the basic design principals used by traditional wet pipe sprinkler systems. The piping system must be sized to suit the application design in order to achieve the correct design parameters for both water flow and pressure drop. Hydraulic Calculations The pipe network shall be hydraulic pressure loss calculated in accordance with the requirements of NFPA 750 and the requirements and regulations adopted by the authority having jurisdiction using the following formulas. Hydraulic calculations for systems with working pressures not exceeding 175 psi (12 bar) shall be performed using the Hazen‐Williams calculation method. If the system working pressure exceeds 175 psi (12 bar) the system shall be hydraulic calculated using the Darcy‐Weisbach calculation method. The hydraulic design shall ensure the presence of the necessary water flow, water pressure and quantity of water needed for the full system operation time. For FM Approved installations, the system shall be hydraulic pressure loss calculated from the most remote nine ...
4. INSTALLATION This section provides installation instructions for the major components that make up the DuraQuench wet pipe water mist system. Each subsection provides detailed instructions on how to install a specific component of the system. All installation steps shall be completed before the applicable component can be considered installed and operational. The components shall be checked that they live up to the specifications listed in the system plans and to the requirements listed in this manual and component manuals and subsequent standards. When handling the components and pipes the handler shall be cautious not to compromise the components by dropping, bumping or otherwise ...
Mounting The pump skid is constructed with the following features that enable it to be easily maneuvered to its final installation location and secured in place. 1. The skid is equipped with fork lift slots at each end of the skid to allow it to be easily lifted using a standard forklift with adjustable forks. See Figure 41. 2. Two lifting eyes are provided at each end of the skid to allow it to be lifted using lifting devices such as a crane or hoist. See Figure 41. 3. Optional rolling casters (P/N 02‐15334) can be ordered and mounted to the skid in the field to allow the unit to be rolled into its mounting location. See Figure 42. Figure 41: Pump Skid Lifting and Mounting Points Figure 42: Pump Skid with Casters Installed Pump skid unit shall be installed and anchored on a suitable foundation (provided by others) using the four mounting holes provided on the pump skid. See Figure 41. Pump skid unit must be leveled and piping connection locations verified prior to installation of the skid to ensure piping mates up with the pump flanges without strain. Page 48 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
(NFPA 750; 6.9.2.2). However, power feed shall be arranged so that if the power supply within the protected facility itself must be disconnected during a fire, the power supply to the pump feeder circuit will not be interrupted (NFPA 750: 6.9.2.3). Power Supply Capacity Power supply shall be capable of carrying indefinitely the sum of the locked‐rotor current of the fire pump motor(s) and pressure maintenance pump motor(s) and the full‐load current of the associated fire pump accessory equipment. The following formula can be used to calculate the pump’s motor inrush current, also known as locked‐rotor amps or LRA. Simply insert the motor’s KVA/HP, HP rating, and Voltage values into the formula. LRA = (KVA/HP x Motor HP x 1000) / (1.732 x Motor Voltage) Detection and Releasing Panel Connections to Pump Controller The buyer is responsible for material and labor required to connect the detection and releasing panel to the pump skid controller for pump activation and monitoring purposes, where required. Refer to documentation supplied with the pump controller for connection requirements. Fike recommends that the fire detection control panel and associated control modules used to monitor and control the pump skid be located outside the water mist protected area so they are not subject to the effects of the fire, which could render them inoperable. Page 50 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Circulation Relief Valve Connection Each DuraQuench pump skid is equipped with a circulation relief valve. The valve is designed to provide cooling water when the pump is operating at churn (no flow) conditions. The valve is set to automatically open when the system pressure reaches 275 psi (19 bar). The valve provides a 1” NPT female outlet for connection of a drain pipe that must be routed outdoors or to a floor drain where the discharge can be observed by the pump operator. Water Supply Connection To facilitate easy connection of the DuraQuench pump skid to the system water supply, Fike provides the necessary components to install the required suction isolation valve and connect the water supply to the pump skid. The supplied components vary depending upon the inlet size of the pump skid. See Figures 44 and 45. Figure 44: 2” (DN50) Pump Skid Water Supply Connection Item Figure 45: 3” (DN80) Pump Skid No. Description P/N Water Supply Connection 1 Pump skid inlet flange N/A 2 2” NPT threaded flange 02‐17225* ...
In order to prevent water damage, the discharge from the test header connection shall be piped to a safe discharge location where there is adequate drainage for the pressurized water discharge. A flanged outlet and an isolation valve are provided on the DuraQuench pump skid to allow easy connection and isolation of the test header components. See Figure 46. ...
1. Where the system’s design pressure is less than or equal to 175 psi (12 bar), the FDC connection shall be made after the fire pump on the supply side of the pump skid, as shown in Figure 47. Installation of the FDC in this manner requires that a strainer or filter be installed in the FDC supply line. Figure 47: Fire Department Connection for System Design Pressure <= 175 psi (12 bar) 1. Suction flange 10. Discharge isolation valve (monitored) 2. Suction basket strainer 11. Discharge flange 3. Suction pressure gauge 12. Discharge check valve 4. Circulation relief valve (opens at 275 psi/19 bar) 13. Isolation valve 5. Centrifugal pump and motor 14. Strainer or filter 6. Pressure relief valve (opens at 245 psi/16.9 bar) 15. Check valve 7. Test header stop valve (monitored) 16. Drain valve (piped to drain) 8. Test header flange 17. Fire department connection 9. Discharge pressure gauge Page 54 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
2. Where the system’s design pressure is greater than 175 psi (12 bar), the FDC connection shall be made on the suction side of the fire pump, as shown in Figure 48. Figure 48: Fire Department Connection for System Design Pressure >175 psi (12 bar) 1. Suction flange 9. Discharge pressure gauge 2. Suction basket strainer 10. Discharge isolation valve (monitored) 3. Suction pressure gauge 11. Discharge flange 4. Circulation relief valve (opens at 275 psi/19 bar) 12. Supply isolation valve (monitored) 5. Centrifugal pump and motor 13. Check valve 6. Pressure relief valve (opens at 245 psi/16.9 bar) 14. Drain valve 7. Test header stop valve (monitored) 15. Fire department connection 8. Test header flange P/N 06‐791‐4 (Rev. 4) Page 55 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Pressure Maintenance (Jockey) Pump Connection When a jockey pump is utilized, a pressure sensing line connection to the pump controller is required for pump activation. This piping connection enables the pump controller to sense a pressure drop in the piping network due to the opening of a single nozzle triggering activation of the fire pump. There are two options for connecting a jockey pump to the DuraQuench pump skid as described below. Option 1: If initially ordered as part of the pump skid, the jockey pump and required isolation valves are factory‐installed onto the pump skid prior to shipment. See Figure 49. The jockey pump controller (item 22), pressure sensing line connection (item 23) and electrical connection between the jockey pump motor and the jockey pump controller (item 24) must be field installed. A pipe flange (item 20) is factory installed on the pump skid to facilitate easy connection of the field piping to the pump skid. Figure 49: Wet Pipe System with Pressure Maintenance Pump mounted on the Skid 1. Suction isolation valve (monitored) 13. Discharge pressure gauge 2. Suction flange 14. Discharge isolation valve (monitored) 3. Suction basket strainer 15. Discharge flange 4. Suction pressure gauge 16. Check Valve ...
All system components shall be secured to rigid construction elements using FM Approved, or FM accepted pipe hangers in accordance with the requirements of NFPA 13 and FM Global for sprinkler fire protection systems. CAUTION Pipe hangers for stainless steel pipes should be made of stainless steel, or steel material should be galvanically insulated from the stainless steel pipes. Page 58 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Water filled pipes and reservoirs located in locations with risks of frost shall be trace heated, and the trace heating system shall be monitored by an FM Approved alarm system. The pipes leading up to the water mist nozzles shall be installed in a frost free location. 4.3. Wet Alarm Control Valve The Wet Alarm Check valve (WAC) shall be installed as shown on the system design documentation, and in accordance with the manufacturer’s instructions. Where the WAC valve is used, refer to Fike document 06‐791‐3 for installation instructions. The valve shall be installed so it is accessible for operation, inspection, and maintenance, but shall not be installed where it will be subject to damage that would prevent proper operation. 4.4. Automatic Bypass Valve Every DuraQuench pump skid is equipped with an automatic bypass valve that ensures a continuous flow through the pump when running by diverting a portion or all of the pump discharge back to the pump suction based on the process flow. The bypass valve is closed when the process flow is greater than the control set point (that is, minimum flow rate required), opens gradually as the process flow is reduced and pressure increases, and is fully open when the process flow is reduced or stopped resulting in an increase in pressure greater than the bypass valve’s set point. NOTE: The bypass valve is factory set to begin opening when the inlet pressure to the valve reaches 250 psi (17.2 bar). Should the operating set point or opening and closing speed of the bypass valve need to be adjusted, refer to Appendix A for instructions. 4.5. Nozzles The OH‐VSO nozzles shall be installed in strict accordance with the design documentation prepared for the specific installation and in accordance with the following guidelines. Any required deviations must be approved prior to ...
Install permanently marked, weatherproof, metal or rigid plastic identification signs at all control, drain, and test connection valves. The signs shall be secured with corrosion resistant wire, chain, or other approved means. A system design information sign shall be attached to the pump skid and shall include the following information: 1. Location of the design area or areas 2. Design area of water application or volume of space protected. 3. Nozzle manufacturer and model number 4. Area per nozzle 5. Total number of nozzles in design area 6. Minimum rate of water application (density) 7. Total water requirement as calculated 8. Description of hazard protected 9. Description of any compartment or enclosure characteristics that are essential to system performance 10. Name of installing contractor and contact information Page 60 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
5. SYSTEM ACCEPTANCE AND COMMISSIONING The DuraQuench water mist system shall successfully meet all system acceptance and commissioning procedures and should be documented with copies provided to the system owner and manufacturer. All acceptance and commissioning procedures shall be reviewed by FM Global. FM Global can request changes prior to granting the approval. Refer to the following Fike documents for system Startup and Testing procedures: 1. 06‐814 – Centrifugal Fire Pump Acceptance Test Form 2. 06‐815 – Fire Pump Controller Start‐Up Form 3. 06‐816 – Water Mist System Acceptance Test Form 5.1. Commissioning Requirements Acceptance and commissioning testing should include the following: 1. Acceptance procedures shall be in accordance with: FM Global Property Loss Prevention Data Sheet Number 4‐2, Water Mist Systems; NFPA 750, Standard on Water Mist Fire Protection Systems; NFPA 25, Standard for the Inspection, Testing and Maintenance of Water‐Based Fire Protection Systems; or equivalent national code of the country of use. 2. An appropriate Authority having Jurisdiction representative should be given advance notice of such testing and be present for commissioning of the system. 3. A trained manufacturer’s representative should be present to properly test and reset the system following the ...
6. OPERATION Subject to the specific project requirements, the DuraQuench wet pipe water mist system will be arranged to operate automatically as described in this section. 6.1. Wet Pipe System with an Alarm Check Valve Upon activation of an OH‐VSO nozzle in response to a fire event, the following events shall occur: 1. Water will begin to flow through the activated OH‐VSO nozzle. 2. Water will begin to flow through the wet alarm check valve, activating the valve’s integral water flow sensor which is monitored by the fire detection and releasing panel. 3. Upon receipt of the water flow signal, the fire detection and releasing panel shall: Initiate a fire alarm signal to the fire brigade. b. Activate an exterior water flow alarm bell. Activate interior alarm notification appliances for building occupant notification. Upon activation of a water flow switch, the following events shall occur: 1. Initiate an electrical signal to the fire detection and releasing panel. 2. Upon receipt of the water flow signal, the fire detection and releasing panel shall: Initiate an electrical signal to the fire pump controller to initiate start‐up of the fire pump. 3. The system will discharge on a continuous basis through the pipe distribution system to the water spray nozzles until the fire pump is manually stopped at the fire pump controller. 6.2. Wet Pipe System with Maintained Excess Pressure Upon activation of an OH‐VSO nozzle in response to a fire event, the following events shall occur: 1. Water will begin to flow through the activated OH‐VSO nozzle. 2. Water will begin to flow through the wet alarm check valve, activating the valve’s integral water flow sensor which is monitored by the fire detection and releasing panel. 3. Upon receipt of the water flow signal, the fire detection and releasing panel shall: Initiate a fire alarm signal to the fire brigade. b. Activate an exterior water flow alarm bell. ...
7. INSPECTION AND TESTING The DuraQuench water mist system shall be inspected and tested in accordance with the requirements of the following documents and standards to verify that it functions as intended: FM Global Property Loss Prevention Data Sheet Number 4‐2, Water Mist Systems FM Global Property Loss Prevention Data Sheet Number 2‐8, Fire Protection System Inspection, Testing and Maintenance. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water‐Based Fire Protection Systems NFPA 750, Standard on Water Mist Fire Protection Systems Local code requirements 7.1. Nozzles Water mist nozzles shall be inspected from the floor level annually. Any nozzles that show signs of any of the following shall be replaced: 1. Leakage 2. Corrosion 3. Physical damage ...
Clean or replace as required After system operation System components should be maintained as follows: In accordance with the recommendations of the component manufacturer. System strainers should be emptied and cleaned after each pump system test. Water reservoir level control should be regularly checked and if necessary maintained. The DuraQuench system should be regularly maintained and when faults are found they should be rectified as soon as possible. Check for the presence of spare components. CAUTION When unscrewing system components for inspection or maintenance it is important to clean the inside connecting threads for sealants before refitting components to the female threads. This should be rigorously conducted to avoid introducing debris into the pipe network. 8.1. Maintenance of Surrounding Areas Should the area surrounding the OH‐VSO nozzles need maintenance, it is important to protect the nozzles from any ...
2. Notify remote monitoring entity and fire brigade that the water mist system is going to be taken out of service. 3. Power down the fire pump controller by closing the Circuit Breaker Switch and then the Isolating Switch. Verify loss of AC power to the controller is indicated on the Detection and Releasing panel. 4. For system equipped with a pressure maintenance (jockey) pump, power down the jockey pump by switching the selector switch on the jockey pump controller to the OFF position. 5. Close the isolation valve located on the water supply, suction side of the pump skid and verify that a supervisory signal is indicated at the Detection and Releasing panel. 6. Clean the pump skid strainer per the procedure outlined in Annex B. 7. The activated nozzles shall be removed and returned to FIKE, the thread sealant removed and new nozzles shall be installed in their place. It is recommended that activated nozzles be replaced by nozzles of same make and build as to make certain that the correct spacing and height of nozzle is achieved. 8. Nozzles in the adjacent areas of the activated zone/nozzles shall be visually inspected. This requires the nozzles to have intact bulbs with a sufficient amount of liquid within, no signs of any leakages and retaining a small spherical concentration of air within the liquid at room temperatures, i.e. 25° C ±5 (≈68° F ±10). Nozzles which do not comply with above mentioned requirements shall be returned to FIKE and new nozzles shall be installed in their place. Depending on the situation and circumstances which actuated the fire protection system, nozzles, which have not been activated, in the vicinity of the activated nozzles may have been contaminated or soiled as a result of fire or other chemical reactions in the vicinity of the nozzles. Because of the sensitive ...
Page 74
ANNEX A – AUTOMATIC LOW FLOW BYPASS VALVE ADJUSTMENTS The pressure relief valve on the DuraQuench pump skid is factory set to open when the inlet pressure reaches 245 psi (16.9 bar) to allow excess pressure in the system piping to be relieved to the pump suction inlet. When a variable frequency drive pump controller is used, the pressure set point of the relief valve must be field adjusted to a minimum of 10 psi (0.68 bar) above the set (operating) pressure of the variable speed frequency drive (VFD). CAUTION: Pressure relief valve adjustment is only to be performed by experienced personnel who understand the impact of adjusting the pressure relief setting and who take full responsibility for the relief setting. 1. Prime the pump following the procedure outlined in Appendix D.2. 2. Perform pump startup following the procedure outlined in Appendix D.3. 3. Confirm that the discharge isolating valve on the pump skid is closed. 4. Confirm that the test header isolating valve on the ...
The pump skid basket strainer must be cleaned as described below after activation of the fire pump. See Figure 55. 1) Close the Suction isolation valve and Supply isolation valve on the pump skid. 2) Loosen T‐bolt on top of strainer and swing yoke clear of cover. 3) Remove the strainer cover making sure O‐ring remains intact. 4) Lift strainer basket from the strainer body. 5) Invert the basket and wash out debris by directing a stream of air or water against the basket exterior. NOTE ‐ Do not allow basket contents to dry as this will make cleaning most difficult. 6) Inspect basket strainer at each cleaning for holes or tares and replace as required. 7) Place clean or new basket squarely on the basket seat. Be sure basket handle is sufficiently high to be compressed by strainer cover. 8) Inspect O‐ring and seal surface. Clean seat or replace O‐ring as necessary. 9) Replace strainer cover making sure O‐ring is in place. Figure 54: Basket Strainer 10) Swing the yoke over the cover and make full contact with the yoke stud. 11) Tighten the center T‐bolt. 12) Perform pump skid startup procedure. P/N 06‐791‐4 (Rev. 4) Page 67 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
If any uncertainty should arise regarding the placement of OH‐VSO nozzles adjacent to obstructions, the person or persons in charge shall consult the local authority having jurisdiction. Should the uncertainty remain after consulting the local authorities having jurisdiction, Fike shall be contacted for advice on the subject. In order to simplify the process of determining whether an object is an obstruction for the OH‐VSO, the subject of obstructions has been divided into two subdivisions; Ceiling‐fixed Obstructions and Pendent Obstructions. ...
) is not to exceed 25% of the area of the spray pattern at the top of the obstruction (A ). If the area of an obstruction (A ) exceeds 25% of the spray pattern area at the top of obstruction (A ), additional nozzles shall be installed beneath or adjacent to the obstruction so the obstruction is protected. Additional nozzles shall therefore be installed beneath or adjacent to the obstruction, if the following statement is true: (A / A ) ◦ 100 ≥ 25%. Figure 56: Obstructions of Single Pendent Nozzles Obstructions of Multiple Pendent Nozzles: Obstructions shall be exempted from the above mentioned requirements only if the obstructions are situated in the spray pattern of two or more nozzles and that they do not obstruct more than 30% of the spray pattern area at the top of the obstruction (A ) of each of the involved nozzles. Figure 57: Obstructions of Multiple Pendent Nozzles P/N 06‐791‐4 (Rev. 4) Page 69 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Page 78
π Area of Circle: r π Distance from Nozzle: 0.65 m Distance from Nozzle: 0.65 m r of A = 1.87 m r of A = 1.8 m 2 = r π = 1.8 π = 10.986 = r π = 1.8 π = 10.986 2 = πab = π1.11 x 0.625 = 2.18 m = πab = π1.35 x 0.735 = 3.12 m (2.18/10.986) x 100 = 19.84% (3.12/10.986) x 100 = 28.4% The elliptical obstruction above is therefore acceptable. The elliptical obstruction above is therefore unacceptable and additional nozzles shall be installed. Page 70 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Page 79
Distance from Nozzle: 0.5 m r of A = 1.67 m r of A = 1.67 m 2 = r π = 1.67 π = 8.76 = r π = 1.67 π = 8.76 2 = s x s = 0.8 x 0.32 = 0.256 m = s x s = 2 x 1.87 = 3.56 m (0.256/8.76) x 100 = 2.93% (0.256/8.76) x 100 = 40.64% The obstruction above is therefore acceptable. The obstruction above is therefore unacceptable and additional nozzles shall be installed. P/N 06‐791‐4 (Rev. 4) Page 71 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Production number 3 Head in Feet at Rated Flow 444.9 500.3 4 Rated Motor hp (P2) 15 25 5 Head at Zero Flow (max) 554.5 638.5 6 Rated rpm 2924 2934 7 Rated Flow (gpm) 74.85 132.09 8 Rated Frequency (Hz) 50 50 Maximum Pressure / Maximum 9 363 / 194 435 / 194 Liquid Temperature 10 Direction of Rotation CCW CCW Page 72 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
D.2. Priming the Pump CAUTION: Be sure the isolation valve on the discharge side of the DuraQuench pump skid is closed and the fire pump is primed (filled with water) and ready operation prior to starting the pump. Failure to prime the pump before running the motor will cause damage to the motor bearings. CAUTION: Pump motor should not be run unloaded or uncoupled from the pump at any time; damage to the motor bearings will occur. 1. Close the discharge isolating valve on the pump skid to prevent water from flowing into the piping network. 2. Close the water supply isolating valve on the pump skid to prevent water from flowing into the pump skid. 3. Open the priming plug on the pump head. See Figure 60. LOOSEN CENTER PLUG TO VENT PUMP Figure 59: Fire Pump Vent Plug 4. Gradually open the water supply isolating valve on the pump skid until a steady stream of airless water runs out of the priming hole. 5. Close the plug and tighten securely. 6. Completely open the water supply isolating valve on the pump skid. The discharge isolating valve should remain closed until testing of the pump is complete. 7. Pump is now ready for functional testing. P/N 06‐791‐4 (Rev. 4) Page 73 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
10. Re‐close the controller cabinet door then close the IS and CB to re‐energize the controller. 11. Jog (bump) the motor again to verify correct direction of rotation (counter‐clockwise). 12. Once the correct direction of rotation has been visually verified, open the CB and the IS to remove power from the controller. 13. Replace the coupling guard on the fire pump; then re‐apply power to the controller. Do not attempt to reinstall the coupling guard while power is applied to the controller. 14. Check that the display is powered up with no Alarms present. CAUTION Motors should not be run unloaded or uncoupled from the pump at any time; damage to the motor bearings will occur. Do not start the pump before priming or venting the pump. Never let the pump run dry. Page 74 P/N 06‐791‐4 (Rev. 4) 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com ...
Page 94
CONTACT US Fike World Headquarters 704 SW 10 Street Blue Springs, Missouri 64015 USA Tel: +001 816‐229‐3405 Toll Free (US Only): 1‐800‐YES‐FIKE (1‐800‐937‐3453) www.Fike.com For a list of contact information for Fike offices around the world, visit the Global Locations section of Fike.com ...
Need help?
Do you have a question about the DuraQuench and is the answer not in the manual?
Questions and answers