Table of Contents

Advertisement

Quick Links

 
 
DESIGN, INSTALLATION, OPERATION AND 
MAINTENANCE MANUAL 
 
 
 
DuraQuench™
WET PIPE SYSTEM WITH OH‐VSO NOZZLES FOR PROTECTION OF 
NON‐STORAGE OCCUPANCIES, HAZARD CATEGORY 1 (HC‐1) 
 
 
 
P/N 06‐791‐4 
 
Rev. 4 
 
SOLUTIONS 
Fire Protection 
Explosion Protection 
Overpressure Protection 
Pressure Activation 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DuraQuench and is the answer not in the manual?

Questions and answers

Summary of Contents for Fike DuraQuench

  • Page 1     DESIGN, INSTALLATION, OPERATION AND  MAINTENANCE MANUAL        DuraQuench™ WET PIPE SYSTEM WITH OH‐VSO NOZZLES FOR PROTECTION OF  NON‐STORAGE OCCUPANCIES, HAZARD CATEGORY 1 (HC‐1)        P/N 06‐791‐4    Rev. 4    SOLUTIONS   Fire Protection   Explosion Protection   Overpressure Protection   Pressure Activation ...
  • Page 2 You should install and use the Fike products described in this document within the range specified by Fike, especially  with  respect  to  the  product  application,  maximum  ratings,  operating  supply  voltage  range,  installation  and  other  product characteristics. Fike shall have no liability for malfunctions or damages arising out of the use of Fike products  beyond such specified ranges.  You  should  install  and  use  the  Fike  products  described  in  this  document  in  compliance  with  all  applicable  laws,  standards, and regulations. Fike assumes no liability for damages or losses occurring as a result of your noncompliance  with applicable laws and regulations.  It is the responsibility of the buyer or distributor of Fike products, who distributes, disposes of, or otherwise places the  product with a third party, to notify such third party in advance of the contents and conditions set forth in this document. ...
  • Page 3 HANGE  O  INGER  ALVE     9.  ADDED  ARIABLE  REQUENCY  RIVE  ONTROLLER OPTION  REORGANIZED SECTIONS   THROUGH  4  2020    EVISED  UMP  KID  ONFIGURATION  O  EFLECT ADDITION OF CIRCULATION  ELIEF  ALVE AND  EBRUARY     PDATED  UMP  KID  RDERING  NFORMATION     P/N 06‐791‐4 (Rev. 4)   Page I 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 4: Table Of Contents

    DESIGN  ..................................  3 8  3.1.  Design Documentation ............................  3 8  3.2.  Electrical Clearances ............................  3 9  3.3.  Alarm Check Valve ............................  3 9  3.4.  Pump Skid Test Header ............................  3 9  3.5.  Fire Department Connection ...........................  3 9  3.6.  Check Valves and Backflow Preventers ......................  3 9  3.7.  Pressure Maintenance (Jockey) Pump Connection ..................  4 0  3.8.  System Activation and Alarms .........................  4 0  Page II   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 5 Circulation Relief Valve Connection .................... 52  4.1.8.2.  Water Supply Connection ........................ 52  4.1.8.3.  Test Header Connection  ........................ 53  4.1.8.4.  Fire Department Connection  ...................... 54  4.1.8.5.  Pressure Maintenance (Jockey) Pump Connection  ................ 56  4.2.  System Piping and Components  ........................ 58    Electrical Potentials .......................... 58    Pipe Joints  ............................... 58    Pipe Supports ............................ 58    Frost Protection  ............................ 59  4.3.  Wet Alarm Control Valve .......................... 59  4.4.  Automatic Bypass Valve .......................... 59  P/N 06‐791‐4 (Rev. 4)   Page III 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 6 Nozzles ................................  6 3    Periodic Nozzle Testing ...........................  6 3    Spares  ..............................  6 3  8.  MAINTENANCE .................................  6 4  8.1.  Maintenance of Surrounding Areas .........................  6 4  9.  SYSTEM RESTORATION AFTER OPERATION ......................  6 4  9.1.  Restoring the System ............................  6 5  ANNEX A – AUTOMATIC PRESSURE RELIEF VALVE ADJUSTMENTS .................. 66  ANNEX B – BASKET STRAINER CLEANING PROCEDURE .................... 67  ANNEX C – OH‐VSO NOZZLE OBSTRUCTIONS  ........................ 68  ANNEX D – PUMP INFORMATION ............................ 72      Page IV   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 7 Figure 1: Wet Pipe System  .............................. 2  Figure 2: Wet Pipe System using CPVC Pipe ........................ 3  Figure 3: Wet Pipe System with Pressure Maintenance Pump mounted on the Skid  ............ 5  Figure 4: Wet Pipe System with Pressure Maintenance Pump mounted off the Skid ............ 6  Figure 5: OH‐VSO Nozzle .............................. 9  Figure 6: OH‐VSO Typical Nozzle Dimensions  ........................ 11  Figure 7: OH‐VSO Nozzle Spray Pattern  .......................... 11  Figure 8: OH‐Trim Ring .............................. 12  Figure 9: OH‐Trim Ring Dimensions  .......................... 12  Figure 10: Spanner Wrench .............................. 12  Figure 11: DuraQuench Pump Skid  ........................... 13  Figure 12: Typical Pump Skid Configuration ........................ 13  Figure 13: Pump Skid Configuration with Factory Installed Jockey Pump  ................ 14  Figure 14: WAC Valve ............................... 21  Figure 15: 02‐14875‐2 (1 ½” / DN 40) WAC Valve ...................... 22  Figure 16: 02‐14875‐1 (2” / DN 50) WAC Valve  ........................ 22  Figure 17: Check Valve  .............................. 23  Figure 18: Check Valve Dimensions .......................... 24  Figure 19: FPPI 2” & 2 1/2” Control Valves Grooved and Threaded  ................. 25  Figure 20: NIBCO 3” Control Valve Wafer Style  ........................ 25 ...
  • Page 8 Figure 52: Spanner Wrench  ...............................  6 0  Figure 53: Pressure Relief Valve Schematic  ........................  6 6  Figure 54: Basket Strainer ..............................  6 7  Figure 55: OH‐VSO Nozzle Spray Pattern ..........................  6 8  Figure 56: Obstructions of Single Pendent Nozzles  ......................  6 9  Figure 57: Obstructions of Multiple Pendent Nozzles  .......................  6 9  Figure 58: Motor Nameplate  .............................  7 2  Figure 59: Fire Pump Vent Plug ............................  7 3  Figure 60: Fire Pump Coupling Guard ..........................  7 4      Page VI   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 9: Introduction

      1. INTRODUCTION  1.1. General  DuraQuench is an FM Approved single fluid water mist system for the protection of non‐storage occupancies, Hazard  Category 1 (HC‐1). The primary components of the DuraQuench Wet Pipe system consists of a fire pump skid, patented  OH‐VSO fine water spray nozzles, ancillary FM Approved components (i.e., control valves, backflow preventers, isolation  valves,  etc.),  and  a  reliable  water  source  (i.e.,  public  mains,  gravity  tanks  or  other  suitable  water  sources).  These  components are connected together as a system to deliver water mist to the protected enclosure to control, suppress,  or extinguish fires. With a minimum operating pressure of 116 psi (8 bar) and a maximum operating pressure of 232 psi  (16 bar) at the system nozzles, the system is classified by NFPA 750, Standard on Water Mist Fire Protection Systems as  an intermediate pressure system.  1.2. System Description  When configured as a Wet Pipe System, DuraQuench is a fixed protection system in which the pipe system is filled with  pressurized water up to the nozzles during normal standby operation. A system check valve serves to maintain system  pressures in the piping network. Wet pipe systems may be installed in any structure that is reliably maintained above  40°F (4°C). Closed, heat‐sensitive, automatic nozzles located and spaced throughout the protected areas are used to  detect a fire. Optional smoke detectors can be installed in the protected area to provide advanced notification of a fire  event.  Upon activation of a nozzle due to heat from the fire, water will begin to flow immediately from the open nozzle and  will cause a drop in system pressure. Depending upon the system configuration, either the flow of water or the pressure ...
  • Page 10: Figure 1: Wet Pipe System

      Both  the  WAC  valve’s  water  flow  sensor  and  the  water  flow  switch  have  an  adjustable  time  delay  that  inhibits  the  initiation of a water flow signal in order to reduce the possibility of false alarms and false activation of the pump that  can be caused by pressure drops or fluctuations in the water supply.   Figure 1 shows the typical components and arrangements that make up a DuraQuench Wet Pipe system with an Alarm  Check Valve.    Figure 1: Wet Pipe System  1. Suction isolation valve (monitored)  16.  Riser stop valve (monitored)  2.  Suction flange  17.  Wet Alarm Check valve (WAC)  3.  Suction basket strainer  17a.  Drain valve (part of WAC valve)  4.  Suction pressure gauge  17b.  Water flow switch (part of WAC valve)  5.  Circulation relief valve (opens at 275 psi/19 bar)  17c.  Inlet pressure gauge (part of WAC valve)  6.  Centrifugal pump and motor  17d.  Outlet pressure gauge (part of WAC valve)  7.  Test header isolation valve (monitored) ...
  • Page 11: Straight Wet Pipe System Using Cpvc Pipe

    17.  Wet Alarm Check valve (WAC)  2.  Suction flange  17a.  Drain valve (part of WAC valve)  3.  Suction basket strainer  17b.  Water flow switch (part of WAC valve)  4.  Suction pressure gauge  17c.  Inlet pressure gauge (part of WAC valve)  5.  Circulation relief valve (opens at 275 psi/19 bar)  17d.  Outlet pressure gauge (part of WAC valve)  6.  Centrifugal pump and motor  18.  Water flow switch (pump activation)  7.  Test header isolation valve (monitored)  19.  Riser stop valve (monitored)  8.  Test header flange  20.  Pressure reducing valve (PRV)  9.  Pressure relief valve (opens at 245 psi/16.9 bar)  21.  Pressure relief valve  10.  Fire pump controller  22.  OH‐VSO water mist nozzles (closed head)  11.  Pump controller to motor electrical connection  23.  Remote test valve (monitored)   12.  Discharge pressure gauge  24.  Fire Alarm control panel  13.  Discharge isolation valve (monitored)  25.  Water flow alarm bell (electric)  14.  Discharge flange  26.  Monitor Module ‐ Pump controller monitoring  15.  Check Valve  27.  Relay Module ‐ Pump controller activation  16.  Riser stop valve (monitored)  28.  Monitor Module – device monitoring  Locate at most remote nozzle on the system. Used to verify system activation via water flow switch (items 17b and 18).      P/N 06‐791‐4 (Rev. 4)   Page 3 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 12: When Should A Pressure Maintenance Pump Be Used

    Section  3.11  for  water  supply  requirements)  be  relatively  free  from  pressure  fluctuations  and  the  pipe  network  be  designed to provide the water flow required to trip the flow switches used for pump activation and alarm notification,  based on the activation of a single OH‐VSO nozzle. Hydraulic calculations must be performed on the pipe network prior  to installation to confirm that the water supply is capable of providing the pressure required to obtain the water flows  required for pump activation. In addition, the installed system must be functionally tested using the remote test valve  and an OH‐VSO orifice test fitting to verify pump activation based on the activation of a single nozzle. If the water supply  is NOT capable of providing sufficient flow and pressure for pump activation, a pressure maintenance pump system, as  detailed in Section 1.2.2, must be installed.  Wet Pipe System with a Pressure Maintenance Pump  NOTE ‐ DuraQuench systems configured with a pressure maintenance pump are not within the scope of the system’s  FM Approval.   This  system  configuration  (see  Figures  3  and  4)  incorporates  a  pressure  maintenance  (jockey)  pump  into  the  DuraQuench system. The jockey pump can be mounted directly onto the pump skid or field installed off the pump skid.  The jockey pump installation will include a separate jockey pump controller and its own independent pressure sensing  line connection.  The purpose of the jockey pump is two‐fold. The first purpose is to maintain a higher pressure on the system side of the  Fike Wet Alarm Check Valve (WAC) than the standard water supply can reach. The higher pressure holds the clapper of  the WAC valve and Water Flow switch closed even when the water supply pressure fluctuates. This eliminates false ...
  • Page 13: Figure 3: Wet Pipe System With Pressure Maintenance Pump Mounted On The Skid

    18d.  Outlet pressure gauge (part of WAC valve)  4.  Suction pressure gauge  19.  Riser stop valve (monitored)  5.  Circulation relief valve (opens at 275 psi/19 bar)  20.  OH‐VSO water mist nozzles (closed head)  6.  Centrifugal pump and motor  21.  Remote test valve (monitored)  7.  Test header isolation valve (monitored)  22.  Fire Alarm control panel  8.  Test header flange  23.  Water flow alarm bell (electric)  9.  Pressure relief valve (opens at 245 psi/16.9 bar)  24.  Monitor Module ‐ Pump controller monitoring  10.  Fire pump controller  25.  Monitor Module – device monitoring  11.  Pump controller to motor electrical connection  26.  Jockey pump isolation valve  12.  Fire pump pressure sensing line  27.  Jockey pump and motor  13.  Discharge pressure gauge  28.  Check valve  14.  Discharge isolation valve (monitored)  29.  Jockey pump line discharge flange  15.  Discharge flange  30.  Jockey pump isolation valve  16.  Check Valve  31.  Jockey pump controller  17.  Riser stop valve (monitored)  32.  Jockey pump pressure sensing line  18.  Wet Alarm Check valve (WAC)  33.  Electrical connection – jockey pump motor to controller  18a.  Drain valve (part of WAC valve)        P/N 06‐791‐4 (Rev. 4)   Page 5 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 14: Figure 4: Wet Pipe System With Pressure Maintenance Pump Mounted Off The Skid

    18d.  Outlet pressure gauge (part of WAC valve)  4.  Suction pressure gauge  19.  Riser stop valve (monitored)  5.  Circulation relief valve (opens at 275 psi/19 bar)  20.  OH‐VSO water mist nozzles (closed head)  6.  Centrifugal pump and motor  21.  Remote test valve (monitored)  7.  Test header isolation valve (monitored)  22.  Fire Alarm control panel  8.  Test header flange  23.  Water flow alarm bell (electric)  9.  Pressure relief valve (opens at 245 psi/16.9 bar)  24.  Monitor Module ‐ Pump controller monitoring  10.  Fire pump controller  25.  Monitor Module – device monitoring  11.  Pump controller to motor electrical connection  26.  Jockey pump isolation valve  12.  Fire pump pressure sensing line  27.  Jockey pump and motor  13.  Discharge pressure gauge  28.  Check valve  14.  Discharge isolation valve (monitored)  29.  Jockey pump isolation valve  15.  Discharge flange  30.  Jockey pump controller  16.  Check Valve  31.  Jockey pump pressure sensing line  17.  Riser stop valve (monitored)  32.  Electrical connection – jockey pump motor to controller  18.  Wet Alarm Check valve (WAC)    18a.  Drain valve (part of WAC valve)        Page 6   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 15: Water Mist Principle

    As  the water  spray  is  converted  to steam,  it  expands  approximately  1,700  times  forcing  oxygen  away  from  the  vicinity  of  the  droplet.  This  results  in  dilution  of  the  air  (oxygen)  supply  within  the  protected enclosure. If the amount of oxygen necessary to support combustion is reduced below a critical level (14% –  13%), the energy output of the oxidation process fails to become close to the energy input the fire requires to sustain  the chemical fire process which will cause the fire to burn inefficiently making it easier to extinguish.  Blocking of Radiant Heat  As water mist is released into the protected enclosure, the fine water droplets block the radiant heat generated by the  fire from getting to unignited fuel surfaces and reduces the radiant heat flux between the flame and the fuel surface.  1.4. Water Mist Versus Traditional Sprinkler System  Water mist has several advantages over conventional sprinkler systems. One of the key benefits of the DuraQuench  system is that it typically uses 75% less water than a sprinkler system. With a water mist system, the majority of the  water droplets are evaporated by the heat and hot gases generated by the fire resulting in much less water damage to  the protected property and a dramatic reduction in downtime for cleanup. In light hazard applications, the reduced  downtime means that the facility will be able to resume normal operations very quickly after a fire event.  In contrast, traditional sprinkler systems spread large water droplets over the protected enclosure to absorb heat and  cool the room. Due to the large size and relatively small surface area of sprinkler water droplets, they will not absorb  enough energy to evaporate and quickly fall to the floor as water. This results in limited cooling of the fire and greater  water damage to the protected property causing a large increase in facility downtime due to the fire event.  P/N 06‐791‐4 (Rev. 4)  ...
  • Page 16: Approvals

      1.5. Approvals  The DuraQuench wet pipe water mist system is FM Approved to FM5560 Appendix G for the protection of non‐storage  occupancies, Hazard Category 1 (HC‐1).   Applications include but are not limited to the following:    Apartments  Meeting rooms in convention centers and hotels    Atriums  Metalworking shops with non‐hydraulic cutting operations    Churches  Mineral processing (i.e.: glass, cement, ore treating, gypsum processing, etc.)    Concealed Spaces  Museums    Gymnasiums  Nursing or convalescent homes    Hospitals  Offices    Hotel rooms  Restaurant seating areas    Institutions  Schools and university classrooms   ...
  • Page 17: Equipment

      2. EQUIPMENT  The DuraQuench wet pipe water mist system consists of a number of OH‐VSO nozzles and wet pipe alarm check valve  connected by a piping network to a continuous pressure pump skid unit, which is connected to a suitable water source  (i.e., public mains, gravity tanks, reservoirs, etc.).  This section provides a description of the components that can be used to construct the DuraQuench wet pipe water  mist system.  2.1. Sourcing System Components  The DuraQuench pump skid unit and the OH‐VSO nozzles are the only two components that must be purchased from  Fike in order to maintain FM Approval. The remaining system components including wet alarm check valve, detection  and control panel, control valves, piping, switches, etc. can be sourced from other suppliers. The operating pressure  requirement of the DuraQuench system allows the use of traditional FM Approved sprinkler components and wet pipe  system valves.  Components selected for use on the DuraQuench system shall be FM Approved for use in wet pipe sprinkler systems. All  system  components  should  be  a  part  of  an  FM  Approval  follow  up  service.  It  is  very  important  to  verify  that  the  components are suitable for use in the DuraQuench system regarding:   Component materials ...
  • Page 18   Ordering  02‐14870‐A‐B‐C‐D‐E  A (Material): 1 = Brass; 2 = SST  B (Threads): 1 = ½ NPT; 2 = ½ BSP  C (Cover Plate): 1 = Chrome Plated; 2 = White (RAL 9010)  D (Temperature): 1 = 57°C (135°F)*; 2 = 68°C (154°F); 3 = 79°C (174°F); 4 = 93°C (199°F)  E (Drop Pipe Length)**  FM Approved release temperature.  Optional dry unit extension for use on wet pipe systems where pipe connections are exposed to a temperature below 32°F (0°C).  NOT FM Approved for use with the DuraQuench wet pipe system protecting HC‐1 hazards. Refer to data sheet W.1.30.01 for details.  Specifications  General  Weight   0.46 lbs. (0.211 kg )  Housing Material  Brass (NiSn coating)  Strainer Material  Stainless Steel 316L  Thread Type  ½” NPT or ½” BSP  Chrome or White  Cover Plate Finish  (other RAL colors available)  Minimum Water Pressure   116 psi (8 bar)   Maximum Working Pressure   232 psi (16 bar)   1.16 (gal/min/√psi)  K‐factor  16.7 (l/min/√bar)   Droplet Size    < 300 μm  FM Approved Nominal Release Temperature  135°F (57°C)  Ambient Installation Temperature Range  40°F to 100°F (4°C to 38°C)  Application  Maximum Ceiling Height  16’‐5” (5 m) ...
  • Page 19: Figure 6: Oh-Vso Typical Nozzle Dimensions

      Dimensional Information    Figure 6: OH‐VSO Typical Nozzle Dimensions  OH‐VSO Nozzle Spray Pattern    Figure 7: OH‐VSO Nozzle Spray Pattern      P/N 06‐791‐4 (Rev. 4)   Page 11 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 20: Oh-Trim Ring

    OH‐VSO nozzle after the nozzles have been correctly fitted in the pipe system.  Specifications  02‐14879‐1 (Stainless Steel Plating)  Figure 8: OH‐Trim Ring  02‐14879‐2 (RAL 9010)  Part Number  02‐14879‐3 (Stainless Steel Plating, lock screws)  02‐14879‐4 (RAL 9010, lock screws)  Material  316 Stainless Steel  Weight  0.39 oz (12 g)  Finish  Raw material or RAL‐9010 (other RAL colors available)  Dimensional Information    Figure 9: OH‐Trim Ring Dimensions   2.4. Spanner Wrench  The spanner wrench is designed for fast, correct and safe installation of the OH‐VSO nozzle. The nozzle to be installed is  placed in the spanner and is screwed into the pipe system. The nozzle is correctly positioned when the circular spanner  mark is flush to the ceiling surface. The spanner requires an installation hole of 1 7/8” (48mm) Ø.    Figure 10: Spanner Wrench  Specifications  Part Number  02‐15267  Materials  DIN 2391 / C35 Chrome Plate  Weight  17.7 oz (550 g)  Dimensions  8.78” x 1.42” (223 mm x 36 mm)  Page 12   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 21: Pump Skid

      2.5. Pump Skid  The pump skid unit is the primary control center for Fike’s DuraQuench  water  mist  system  providing  the  necessary  flow  and  pressure  to  the  system pipe network and spray nozzles. The compact skid unit is factory  assembled,  pre‐wired,  pre‐piped  and  functionally  tested  prior  to  shipment from the factory which reduces the time and labor required  for field installation. The skid unit is designed to meet the requirements  of NFPA 750, Standard on Water Mist Fire Protection Systems, NFPA 20,  Standard for the Installation of Stationary Pumps for Fire Protection and    FM Datasheet 3‐7, Fire Protection Pumps.   The primary components of the pump skid unit include a full service fire  pump  controller  wired  to  an  electric  motor  coupled  to  a  centrifugal ...
  • Page 22: Figure 13: Pump Skid Configuration With Factory Installed Jockey Pump

    11  Test Header Isolation Valve  Allows the water supply from the fire pump to be routed to a connected test header  (butterfly)  for the purpose of measuring the system flow rate during acceptance testing and  during annual testing.  12  Test Header Pipe Connection  Pipe flange allows easy connection of test header piping to the pump skid. See  System Piping Connections for flange sizes.  13  Pump Controller  Provides a means to start the fire pump automatically or manually in response to a  fire event. Provides remote alarm connections for fire pump monitoring (i.e., pump  running, AC power failure, phase reversal, etc.). Controller can be activated via a  normally closed remote contact from a releasing control panel (deluge system) or  via a pressure sensing line connection (wet pipe system).  14  Motor Bracing Strap  Provides bracing of pump motor.    Pump Skid with Pressure Maintenance Pump Components  For installations where a jockey pump is required, a pressure maintenance (jockey or make‐up) pump kit (P/N 02‐15270)  can be ordered from Fike. The kit includes a jockey pump controller dual rated for 50/60 Hz and a 3.5 GPM centrifugal  pump coupled to a 50/60 Hz motor. If initially ordered as part of the pump skid, the jockey pump and required check  and isolation valves will be factory mounted onto the DuraQuench pump skid, as shown in Figure 13. The jockey pump  controller (included with the kit) must be mounted off the pump skid. The pressure sensing line and pump motor control  wiring connections form the jockey pump to the jockey pump contller must be filed installed in accordance with the  requiremnts of NFPA 20.  NOTE ‐ DuraQuench systems configured with a pressure maintenance pump are not within the scope of the DuraQuench  FM approval.      Figure 13: Pump Skid Configuration with Factory Installed Jockey Pump    Page 14   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 23 Provides a path for continuous water flow through the pump when the pump is  operating in churn (no flow) condition.  13  Relief Valve  Allows the diversion of water through the recirculation loop to limit excess pressure in  the system.  14  Test Header Isolation Valve  Allows the water supply from the fire pump to be routed to a connected test header  (butterfly)  for the purpose of measuring the system flow rate during acceptance testing and  during annual testing.  15  Test Header Pipe Connection  Pipe flange allows easy connection of test header piping to the pump skid. See System  Piping Connections for flange sizes.  16  Pump Controller  Provides a means to start the fire pump automatically or manually in response to a fire  event. Provides remote alarm connections for fire pump monitoring (i.e., pump  running, AC power failure, phase reversal, etc.). Controller can be activated via a  normally closed remote contact from a releasing control panel (deluge system) or via a  pressure sensing line connection (wet pipe system).  17  Motor Bracing Strap  Provides bracing of pump motor.  18  Jockey Pump Controller (not  Provides a means to start and stop the jockey pump automatically in response to  shown)  a drop in pressure in the system piping. Jockey pump controller shall be located as  close as practical to the pump skid.        P/N 06‐791‐4 (Rev. 4)   Page 15 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 24   Pump Skid Ordering Format  The DuraQuench pump skid can be ordered with different pump controller and pump combinations. When ordering the  pump skid, it is extremely important to verify the voltage and frequency (50/60 Hz) of the power feed supplying the  pump skid before selecting the appropriate pump skid part number. The voltage and frequency of the pump controller  and the pump selected must be compatible with the available power supply.  The fire pump controller is available in the following configurations:  1) Standard  single  source  pump  controller  provides  across‐the‐line  full  voltage  starting  for  the  three  phase  motor  driven pump. No transfer switch included.  2) Dual source pump controller incorporates a transfer switch directly into the standard pump controller enclosure.  The transfer switch provides for automatic transferring of the pump load from one power source to another (self‐ acting).  3) Variable  speed  fire  pump  controller  provides  a  variable  frequency  drive  (VFD)  built  into  the  standard  pump ...
  • Page 25 1 (Standard)  2,6  02‐14909‐3‐1‐29‐2  3 (111 gpm/420 lpm)  1 (60 Hz)  29 (460 V/ dual source)  2 (Soft)  2,7  02‐14909‐4‐2‐2‐1  4 (75 gpm/284 lpm)  2 (50 Hz)  2 (208 V/single source)  1 (Standard)  1,4,6  02‐14909‐4‐2‐2‐2  4 (75 gpm/284 lpm)  2 (50 Hz)  2 (208 V/single source)  2 (Soft)  1,4,7  02‐14909‐4‐2‐6‐1  4 (75 gpm/284 lpm)  2 (50 Hz)  6 (380 V/single source)  1 (Standard)  1,6  02‐14909‐4‐2‐6‐2  4 (75 gpm/284 lpm)  2 (50 Hz)  6 (380 V/single source)  2 (Soft)  1,7        P/N 06‐791‐4 (Rev. 4)   Page 17 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 26 2,7  02‐14909‐5‐2‐22‐1  5 (133 gpm/503 lpm)  2 (50 Hz)  22 (208 V/ dual source)  1 (Standard)  2,4,6  02‐14909‐5‐2‐22‐2  5 (133 gpm/503 lpm)  2 (50 Hz)  22 (208 V/ dual source)  2 (Soft)  2,4,7  02‐14909‐5‐2‐27‐1  5 (133 gpm/503 lpm)  2 (50 Hz)  27 (400 V/ dual source)  1 (Standard)  2,6  02‐14909‐5‐2‐27‐2  5 (133 gpm/503 lpm)  2 (50 Hz)  27 (400 V/ dual source)  2 (Soft)  2,7  Notes:  Single power source controller.  Dual power source controller with integral automatic transfer switch.  Variable frequency drive controller. Transfer switch, if required, must be ordered separately.  Pump motor has been tested for operation at 208 V.  Jockey pump, if required, must be ordered separately on all skids using P/N 02‐15270.  Controller provides Standard Across the Line motor starting.  Controller provides motor soft starter.      Page 18   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 27 100 psi  100 psi  100 psi  100 psi  100 psi  100 psi  Pressure***  (6.9 bar)  (6.9 bar)  (6.9 bar)  (6.9 bar)  (6.9 bar)  (6.9 bar)  ‐4 to +248 °F  ‐4 to +248 °F  ‐4 to +248 °F  ‐4 to +194 °F  ‐4 to +248 °F  ‐4 to +248 °F  Liquid Temp. Range  (‐20 to +120 °C)  (‐20 to +120 °C)  (‐20 to +120 °C)  (‐20 to +90 °C)  (‐20 to +120 °C)  (‐20 to +120 °C)  *Usable at 208 Volts.  **The motor’s inrush current, also known as locked‐rotor amps or LRA, can be calculated by inserting the KVA/HP value into the following formula:  LRA = KVA/HP x Motor HP x 1000 / 1.732 x Motor Voltage  ***Current inlet pressure + churn (no flow) pressure must always be lower than the maximum permissible system operating pressure to prevent  potential damage to the bearing in the motor or reduced life of the shaft seal.  ****Pump speed on which data is based.        P/N 06‐791‐4 (Rev. 4)   Page 19 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 28 Specific name plated  Horsepower Rating  Specific name plated motor horsepower rating  motor horsepower rating  Motor Service Factor  1.15 maximum  1.15 maximum  Voltage free contacts rated for 2 amps (resistive) at 30  Remote Contacts  NA  VDC, or 1 amp (resistive) at 125 VAC  Pressure Rating  300 PSI (20.7 bar) standard  300 PSI (20.7 bar) standard  Pressure Sensing Line  ½” nominal, brass  ¼”‐18 NPT, brass  Enclosure  NEMA Type 2 with drip lip  NEMA Type 2 with drip lip  122° F (50° C) provided input and output cable has a  temperature rating of 221°F (105°C)  Ambient Operating  104° F (40° C) provided input and output cable has a    Temperature  temperature rating of 194°F (90°C)  No direct sunlight allowed on the enclosure.  Electromagnetic  Tested to comply with EN 61000‐6‐2 for immunity and    Compatibility  EN 6100‐6‐4 for emissions      Page 20   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 29: Wet Alarm Check Valve (Wac)

      2.6. Wet Alarm Check Valve (WAC)  The Wet Alarm Check (WAC) valve is a clapper and wafer style check alarm valve  designed to be installed in wet pipe water mist systems downstream from the  system pump where the valve is fitted between two flanges. The valve is capable  of  detecting  the  small  water  flows  which  are  common  in  the  DuraQuench  system. The valve has built in inlet and outlet pressure gauges, a drain valve, an  inductive  alarm  sensor  and  Anti‐False  Alarm  (AFA)  unit.  The  valve’s  inductive  alarm sensor provides an electrical means to detect water flow through the valve    without direct contact with moving parts.   The AFA is connected to the WAC valve and monitors the inductive alarm sensor  for indication of water flow. The AFA provides a factory set time delay of 8 – 10  seconds, which reduces the risk of false alarms coming from pressure shocks in  the pipe system. The unit provides a relay contact that provides a means to send  a  signal  to  the  alarm  panel for  activation of  a  water  flow  alarm  bell.  The  unit ...
  • Page 30: Figure 15: 02-14875-2 (1 ½" / Dn 40) Wac Valve

      Dimensions    Figure 15: 02‐14875‐2 (1 ½” / DN 40) WAC Valve    Figure 16: 02‐14875‐1 (2” / DN 50) WAC Valve  Page 22   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 31: Check Valve

      2.7. Check Valve  The ARGCO Check Valve is used in a DuraQuench system to prevent the reversal of  water flow. In the fully‐open position the clapper is held tightly against the valve  body,  out  of  the  flow  stream,  to  provide  maximum  flow  area  and  prevention  of  clapper flutter.  The clapper design produces quick, non‐slam closure before flow reversal can occur  while meeting FM requirements for anti‐water hammer valve rating.    Each valve is hydrostatically tested for leak tightness to 500 PSI.   Specifications  02‐14915‐1 (2”)  02‐14915‐2 (2 1/2”)  Part Number  Figure 17: Check Valve  02‐14915‐3 (3”)  Working Pressure   300 psi (20.7 bar)   Maximum Test Pressure   500 psi (34.5 bar)   Working Temperature  250°F (120°C) maximum  8 lbs. (3.63 kg)(2” & 2 1/2”)  Weight  11 lbs. (4.99 kg)(3”) ...
  • Page 32: Figure 18: Check Valve Dimensions

    2” (50.8 mm)  D  1‐3/4”(44.5 mm)  1‐1/4” (31.8 mm)  1‐11/16” (42.9 mm)  E  4‐1/2” (114.3 mm)  3‐11/16” (93.7 mm)  4‐1/4” (108.0 mm)  F  3‐1/16” (77.8 mm)  3‐5/8” (92.1 mm)  3‐11/16” (93.7 mm)  G  4‐5/8” (117.5 mm)  3‐1/2” (88.9 mm)  4‐11/16” (119.1 mm)          F      G    C  B    D  A    E  Figure 18: Check Valve Dimensions   Page 24   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 33: Control Valves

      2.8. Control Valves  The butterfly control valves are used on the DuraQuench water mist system  for  the  following  functions:  Suction  (supply)  Isolation  Control  Valve,  Test  Header Isolation Valve, Discharge Isolation Control Valve, Riser Inlet Isolation  Valve and Riser Outlet Isolation Valve.  These valves are designed to be installed in any orientation and monitored to  signal if the valve is opened or closed. The valves are designed to open and  close  slowly  to  prevent  water  hammer.  They  are  FM  Approved  for  Fire  Protection Use.  Each valve is equipped with a tamper switch assembly suitable for indoor or  outdoor use. The tamper switch features two switches. Switch 1 can be used  for  connection  to  a  supervisory  circuit  of  a  listed  fire  alarm  control  panel. ...
  • Page 34: Figure 23: Nibco 3" Wafer Style Control Valve

    2” & 2 1/2” Grooved Control Valve  Valve  “A”  “B”  “C”  2” Grooved  6.07” (154 mm)  4.65” (118 mm)  4.09” (104 mm)  2 1/2” Grooved  6.58” (167 mm)  4.65” (118 mm)  4.49” (114 mm)  2” Threaded  6.13” (156 mm)  4.65” (118 mm)  3.25” (83 mm)  2 1/2" Threaded  6.58” (167 mm)  4.65” (118 mm)  4.49” (114 mm)      Figure 23: NIBCO  3” Wafer Style Control Valve    Valve  “A”  “B”  “C”  3” Wafer  14” (356 mm)  7.95” (202 mm)  1.81” (46 mm)    Page 26   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 35: Backflow Preventer

    IPS Groove for Steel Pipe AWWA C606  End Connections  Flange Adapters ANSI B16.1 Class 124  38 lbs./17 kg (2 1/2”)  Weight  40 lbs./18 kg (3”)  MATERIALS  Valve Housing  304 Stainless Steel  Valve Cover  304 Stainless Steel  SOV Disks  EPDM/304 Stainless Steel  SOV Shafts  304 Stainless Steel  SOV Bearings  Teflon/Bronze  Non Wetted Bolts  Grade 8 Zinc Plated  Wetted Fasteners  18‐8 Stainless Steel  Check Disks  Silicone (NSF)  Check Springs  17‐7 Stainless Steel  Check Pins  17‐7/18‐8 Stainless Steel  Check Seats  Noryl Polymer (NSF)  O‐Rings  Buna‐N (NSF)  Listing / Approval  FM Approved      P/N 06‐791‐4 (Rev. 4)   Page 27 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 36: Figure 25: Backflow Preventer Flow Performance Chart

    L  Ec  D  H  W  Sc  in (mm)  in (mm)  in (mm)  in (mm)  in (mm)  in (mm)  in (mm)  in (mm)  NPT  2 1/2” (65)  7.1 (180)  2.9 (74)  18.7 (475)  2 1/2 (65)  0.0 (0)  10.0 (254)  11.0 (279)  1/2”  3” (80)  7.4 (188)  2.9 (74)  18.7 (475)  3 (80)  0.0 (0)  10.3 (262)  11.0 (279)  1/2”      Page 28   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 37: Waterflow Alarm Switch

    The  VSR  switches  and  retard  device  are  enclosed  in  a  general  purpose,  die‐cast  housing. The cover is held in place with two tamper resistant screws which require a  special key for removal. A field installable cover tamper switch is available as an option    which may be used to indicate unauthorized removal of the cover.   Figure 27: Pressure Switch  Specifications  02‐15337‐1 (2”)   Part Number   02‐15337‐2 (2 1/2”)   02‐15337‐3 (3”)   Service Pressure   450 psi (31 bar)   Flow Sensitivity Range for Signal   4‐10 gpm  (15‐38 lpm)   Maximum Surge   18 fps (5.5 m/s)   10.0 Amps at 125/250VAC   Contact Ratings   2.0 Amps at 30VDC Resistive  (Two sets of SPDT (Form C))   10 mA min. at 24VDC  Conduit Entrances   Two knockouts provided for 1/2" conduit   Enclosure Rating   NEMA 4 / IP54 (indoor or outdoor)   Temperature Range   40°F – 120°F, (4.5°C – 49°C)   FM Approved   UL Listed   Listing / Approval   LPCB Approved   VdS Approved     P/N 06‐791‐4 (Rev. 4)   Page 29 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 38: Waterflow Bell

    6  24VDC  16 to 33VDC  DC‐31.1mA / FWR‐53.5mA  82  20‐130‐156  8  24VDC  16 to 33VDC  DC‐31.1mA / FWR‐53.5mA  80  20‐130‐157  10  24VDC  16 to 33VDC  DC‐31.1mA / FWR‐53.5mA  81  20‐130‐158  6  120VAC  96 to 132VAC  53mA  85  20‐130‐159  8  120VAC  96 to 132VAC  53mA  82  20‐130‐160  10  120VAC  96 to 132VAC  53mA  82  Page 30   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 39: Fire Department Connection

    2 1/2” inlet.  A fire department connection shall be provided on all water mist systems, except as  outlined in NFPA 750.  Specifications   Figure 29: FDC  02‐14931 (FDC)  Part Number  02‐15244 (Cap), must be ordered separately  Material  Cast Brass  Inlet – 2 1/2” (Qty. 2)  Size   Outlet – 4”  Lettering  AUTO. SPKR.  Listing / Approval  FM Approved  Dimensions  Figure 30: Cap  5 1/4”  6 3/4”  10”    Figure 31: FDC Dimensions  P/N 06‐791‐4 (Rev. 4)   Page 31 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 40: Pressure Relief Valve

      2.13. Pressure Relief Valve  The AGF Manufacturing Inc. Pressure Relief Valve is used in a DuraQuench system  to relieve excess system pressure caused by surges or temperature changes. This  valve  complies  with  NFPA‐13  which  stipulates  that  a  pressure  relief  valve  be  installed on all gridded systems and downstream of all pressure reducing valves. This  valve has a bronze body, stainless steel spring, and flushing handle to remove debris.  Specifications  02‐14932‐1 (1/2”)  Part Number  02‐14932‐2 (3/4”)  185 psi (12.8 bar) – ½”  Pressure Rating  250 psi (17.24 bar) – ¾”  Temperature Range  33° ‐ 140°F (1° ‐ 60°C)  Figure 32: Relief Valve  1/2” MIPT Inlet & FIPT Outlet  Connections  3/4" MIPT Inlet & FIPT Outlet  MATERIALS  Body  Bronze  Spring  Stainless Steel  Listing / Approval  FM Approved  Dimensions ...
  • Page 41: Pressure Reducing Valve

    Valve Size  L  A  B  C  D  Kv/Cv     Kg/lb  2.30 mm  77.5 mm  155 mm  77 mm  120 mm  80  5 m  19.3  2”/DN50  [9.1 in.]  [3 in.]  [6.1 in.]  [3.03 in.]  [4.69 in.]  [92]  [16 ft.]  [42.5 lb.]  Notes:  [1] Kv/Cv values given for a fully opened valve.    [2] Leq (Equivalent Pipe Length) refers to a fully opened valve with turbulent flow in new steel pipe schedule 40. Values given for general    consideration only.     P/N 06‐791‐4 (Rev. 4)   Page 33 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 42: Identification Signs

    These  signs  are  manufactured  from  0.020”  white  coated aluminum, screen printed with a fade‐resistant red ink and shipped with a clear  protective  coating  to  prevent  scratching  of  finish  during  shipment  and  installation  which can be removed after installation.  DESCRIPTION  PART NUMBER  SIGN SIZE  Drain Valve Sign  02‐15230  6” x 2” (152 x 51mm)  Fire Alarm Sign  02‐15231  9” x 7” (229 x 178mm)  Blank Sign  02‐15232  6” x 2” (152 x 51mm)  Normally Open Sign  02‐15233  6” x 2” (152 x 51mm)  Hydraulic System Sign  02‐15234  8 1/2” x 11” (216 x 279mm)  Inspection Test Sign  02‐15235  6” x 2” (152 x 51mm)  Page 34   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 43: Test Connection

    A test connection shall be provided on all water mist system, as outlined in NFPA  750.   Specifications   Part Number  02‐14942  Material  Polished Brass  Inlet  2‐1/2” female NPT  Outlet  Male hose thread snoot with cap and chain  Figure 37: Test Connection  Lettering  8” plate “HYDRANT”  Listing / Approval  FM Approved  Dimensions  8”  1 7/8”    Figure 38: Test Connection Dimensions  P/N 06‐791‐4 (Rev. 4)   Page 35 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 44: Test Header Flow Meter

    Part Number  02‐15264  Material  Carbon steel ASTM A53 / Carbon Steel Insert  Valves  ¼” MSAE Flare Brass Ball  1/8” FNPT CS Weld Fitting  150#  Identification Tag  Polycarbonate  Temperature  250°F (120°C) maximum  Pressure  300 PSIG (21 bar)  Pipe Size  2 ½”  End Connection  Grooved  6” (150 mm) Dial Size  270° Arc  Standard Diaphragm  Pressure Gauge  ±1.75% Accuracy, Full Scale  180°F (80°C) Temperature  Brass/Bronze  Hoses  Nylon  Flow Rate  50 – 200 GPM (189 – 757 lpm)  Dimensions  6” (152 mm) end to end  Weight  3 lbs (1.4 kg)  Listings / Approvals  FM Approved  Page 36   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 45: Piping Network

    ASTM B‐75/B‐88  Welded, Brazed, Flared, Compression  CAUTION  To prevent clogging of the system nozzles, it is prohibited to use components with black iron, hot galvanized  or  electro  galvanized  pipe  and  system  components  used  in  traditional  sprinkler  systems,  because  of  corrosion and risk of loose zinc flakes.  When using CPVC pipe on a wet pipe system, the pipe and fittings must be approved per FM 1635, Approval Standard  for Plastic Pipe and Fittings for Automatic Sprinkler Systems.  CPVC pipe is not permitted to be used in seismically active  areas in accordance with FM Global Loss Prevention Data Sheet 2‐8. CPVC pipe must be shielded from the fire area by a  non‐removable barrier having a fire rating equal to or greater than 1 hour. A pressure reducing valve (See Section 2.14)  MUST be installed in the system pipe network just prior to transitioning to CPVC. The PRV is required to regulate the  inlet pressure supplied to the CPVC distribution piping to a maximum service pressure of 175 psi (12 bar) in order to  prevent over‐pressurization. Refer to FM Datasheet 3‐11 for the use of the PRV.   NOTE: From this point forward, where the word pipe is used it shall imply tubing as well.  Fittings  Fittings shall have a minimum rated system design working pressure equal to or greater than the maximum operating  pressure of the water mist system at 130°F (54°C) and shall have corrosion resistance at least equivalent to wrought  copper fittings conforming to ASME/ANSI B16.22, Wrought Copper and Alloy Solder Joint Pressure Fittings.  Galvanic Corrosion  To avoid galvanic corrosion from occurring in the water mist system, all component materials incorporated into the  system shall be compatible so no galvanic reaction can take place, or as a minimum be electrically insulated from the  pipe materials to the satisfaction of FM Approval and the authorities having jurisdiction.  P/N 06‐791‐4 (Rev. 4)   Page 37 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 46: Design

      3. DESIGN  This section details the steps necessary to design a DuraQuench water mist system for wet pipe operation. It is the  responsibility of the system designer to ensure that the DuraQuench water mist system is:  1. Fully designed in accordance with the design guidelines of this manual as well as the applicable guidelines and  requirements of FM Global, NFPA 750, NFPA 13, and the requirements of the authorities having jurisdiction.  2. Fully documented to the satisfaction of FM Global and the authorities having jurisdiction (AHJ). Design shall be  reviewed and accepted by the authorities having jurisdiction prior to the installation.  3. Applied using system components of good quality and reliable products, which are accepted and approved by  FM Global and the AHJ, and that are suitable for their particular use in the system. See Section 2.1.  4. Designed to fully match the location and application to be fire protected.  5. Hydraulically  designed  from  water  supply  to  water  mist  nozzles.  The  hydraulic  design  shall  ensure  that  minimum  requirements  of  water  flow  and  water  pressure  on  all  nozzles  meets  the  design  criteria  and  is ...
  • Page 47: Electrical Clearances

    All  water  mist  system  components  (e.g.,  nozzles,  piping,  detectors,  etc.)  shall  be  located  to  maintain  minimum  clearances from unenclosed and uninsulated energized electrical components in accordance with NFPA 70, National  Electrical  Code.  Refer  to  NFPA  750,  Standard  on  Water  Mist  Fire  Protection  Systems  for  further  information  and  clearance data.  3.3. Alarm Check Valve  Fike recommends using the Wet Alarm Check (WAC) valve in conjunction with the DuraQuench system; however, any  FM Approved wet alarm check valve can be used as long as it complies with the following criteria:  1. Valve must be capable of handling the maximum working pressure created by the DuraQuench system 232 psi  (16 bar).  2. Valve must be capable of handling the water flow requirements required by the DuraQuench system.  3. Valve must be constructed of corrosion resistant materials in order to minimize the risks of clogging the water  mist nozzles.  4. Friction losses associated with the valve must be compatible with the performance criteria of the system.  5. Valve must be FM Approved and be capable of sounding an alarm upon activation of one OH‐VSO nozzle.  Where the WAC valve is used, refer to Fike document 06‐791‐5. Otherwise, refer to the documentation supplied with ...
  • Page 48: Pressure Maintenance (Jockey) Pump Connection

    If  an  existing  detection  system  is  used  in  a  new  water  mist  system,  the  detection  system  shall  be  evaluated  for  compliance with the standards identified above and the requirements outlined in this document.  Detector Requirements  The  detector  requirements  for  each  DuraQuench  water  mist  system  will  vary  according  to  the  specific  hazard  requirements. Selection of the type of detector to use for releasing of the system shall be based on a thorough review  of the project requirements. ...
  • Page 49: Protected Enclosure

    Planning  shall  include  considerations  for  equipment  access,  heating,  lighting,  emergency  lighting  and  ventilation.  The  pump  room  shall  provide  protection  for  both  the  pump  operator  and  pumping  equipment  during  a  fire  event.  Consideration should be given to locating the pump room at grade level, with direct access to the exterior of the building,  to provide quick and easy egress for the pump operator and access to the pumping equipment for fire department  personnel. Where the pump room cannot be located on grade with direct access from the outside of the building, a fire  rated and protected space must be provided. The space must be accessible through an enclosed passageway from an  exterior exit from an enclosed stairway.  3.11. Water Supply  The water supply source for the DuraQuench system shall meet the requirements of NFPA 750, NFPA 13, and FM Global,  with exceptions to the water density, water flows, and pipe system materials described in this manual. The water supply  source shall comply with the overall design of water supply systems for wet pipe sprinkler systems for fire protection of  similar locations.  Water Supply Source  The water supply shall be supplied by one of the following sources:  1. A connection to a reliable waterworks system (public service main) capable of providing the necessary water  flow, water pressure, and quantity of water needed for the operation of the water mist system. Adequacy and  dependability of the water source shall be fully determined from a water flow test or other approved method ...
  • Page 50: Water Quality

    4. No additives allowed for an FM approved system.  Water Supply Capacity  The  water  supply,  when  operating  under  reasonable,  anticipated,  worst‐case  conditions  must  be  capable  supplying  150% of the pump’s rated flow for the required duration of the water demand at the minimum inlet pressure (NPSHR)  required by the pump in accordance with the requirements of NFPA 20, Standard for the Installation of Stationary Pumps  for Fire Protection and FM Property Loss Prevention Data Sheet 3‐7, Fire Protection Pumps.  The water supply must also be capable of maintaining a positive pump suction pressure at the pump inlet while providing  the maximum fire protection system demand at residual pressure. Maintaining a positive suction pressure at the pump  inlet helps to reduce the potential for cavitation within the pump, which can reduce the efficiency or even cause damage  to the fire pump.   If the water supply cannot provide 150% of the rated flow of the pump, but can provide the maximum flow demand of  the system, it shall be deemed to be adequate; however, a sign shall be placed in the pump room indicating the minimum  suction pressure that the fire pump is allowed to be tested at and also indicating the required flow rate.  The minimum NPSHR for the pumps used on the DuraQuench system can be obtained from the pump curves provided  in Annex C. The minimum NPSHR shall be selected at the highest flow the pump will be delivering plus a safety margin  of 2.0 feet (0.61m).  CAUTION  Do not exceed the manufacturer’s set limits for the pump with regards to maximum inlet pressure and  maximum operating pressure. See Motor and Pump Specifications on Page 19.  The water supply capacity shall meet the hydraulically calculated design flow requirements and the minimum system  flow duration requirements of the actual system as listed in the following table.  Applicable Standard  Minimum System Discharge Duration  30 minutes to the hydraulically most remote nine automatic nozzles or all automatic  NFPA 750 (Light  nozzles within a 1,500 ft  (140 m...
  • Page 51: Design Process

      3.12. Design Process  The basic design principals of the DuraQuench wet pipe water mist system are identical to that of traditional sprinkler  wet pipe systems. The following process shall be used to properly design a DuraQuench wet pipe water mist system for  protection of non‐storage occupancies.  Determine Nozzle Layout  The  OH‐VSO  nozzles  shall  not  be  installed  in  locations  containing  materials  which  may  produce  violent  reactions  or  significantly hazardous materials when reacting with water and should be installed in locations where the nozzle is not  likely to sustain physical damage.  The nozzles shall be installed within the protected enclosure in a homogenous grid  covering the whole area of the enclosure. Spacing of the nozzles shall be in accordance with the requirements listed  below.   Maximum ceiling height 16.42 ft. (5 m)   Minimum ceiling height 6.6 ft. (2 m)   Maximum nozzle spacing 14.75 ft. x 14.75 ft. (4.5 m x 4.5 m)   Minimum nozzle spacing 7.42 ft. x 7.42 ft. (2.25 m x 2.25 m)   Maximum nozzle distance to wall 7.33 ft. (2.25 m)   Minimum nozzle distance to wall 3.17 ft. (1.125 m) ...
  • Page 52: Nozzle Obstructions

      Nozzle Obstructions  Care should be given when installing the OH‐VSO nozzles adjacent to major obstructions. A major obstruction is defined  shall be defined as an object which obstructs a significant portion of the spray from the OH‐VSO nozzle.  If the area to be protected houses one or more major obstructions (i.e., beams, walkways, ductwork, etc.) additional  nozzles shall be installed adjacent to the obstructions. If it is not possible to protect the area underneath or next to the  obstruction, depending upon the elevation of the obstruction, additional OH‐VSO nozzles shall be installed beneath the  obstruction in order to provide a homogenous distribution of the water mist in the enclosure.  For more on obstructions, see Annex C.  NOTE ‐ Systems with nozzles installed as described in this section are not part of the DuraQuench system FM Approval.  Determine Nozzle Flow Rate  Use the following formula to calculate the flow rate from each OH‐VSO nozzle using the given K‐factor for the nozzle  (1.16 (gal/min/√psi or 16.7 (l/min/√bar). The K‐factor is a constant that gives the ratio between the flow rate and the  pressure at the nozzle. System pressure (P) at the nozzle will vary between 116 to 232 psi (8 – 16 bar). The most favorable  condition shall be considered.  Q = K * P  Where:  Q = Flow from the nozzle (gal/min or l/min.)  K = Nozzle K factor (gal/min/psi or l/min/bar)  P = Pressure at the nozzle (psi or bar)    Determine System Flow Rate  The system shall be capable of supplying water to the hydraulically most remote nine nozzles or all nozzles within a  1,500 ft  (140 m ) demand area, whichever is greater. If the demand area is less than 1,500 ft  (140 m ) in area, the  system shall be capable of supplying water to all nozzles in the protected area.  To calculate the total flow rate for the system, multiply the calculated nozzle flow rate by the total number of nozzles  serving the remote demand area.   = Q * N   Where:   = Total flow for the demand area (gal/min or l/min.)  Q = Flow from the nozzle (gal/min or l/min)   = Total number of nozzles    Page 44   P/N 06‐791‐4 (Rev. 4) ...
  • Page 53: Determine Size Of Fire Pump Required

     = Q / q  PUMPS MAX  Where:   = Number of pumps  PUMPS  = Total flow for area (gal/min or l/min) + safety factor (10% NFPA or 20% FM)  q = Flow rate output of selected pump unit    NOTE  ‐  Using  the  formula  above,  in  most  cases,  will  result  in  the  selection  of  a  fire  pump  that  is  oversized  for  the  application. Hydraulic calculations shall be performed in order to determine the actual required capacity of the  fire pump.  P/N 06‐791‐4 (Rev. 4)   Page 45 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 54: Ambient Temperature And Altitude

        Figure 40: Relationship between motor output (P ) and ambient temperature/altitude Example: From Figure 40 it appears that P2 must be reduced to 88% when a pump with NEMA premium efficiency ML  motor (Fike pumps) is installed 15,584 feet above sea level.  At an ambient temperature of 167°F, P2 of a standard  efficiency motor must be reduced to 74% of rated output.  In cases where both the maximum temperature and the maximum altitude are exceeded, the derating factors must be  multiplied. Example: 0.89 x 0.89 = 0.79.  Determine Distribution Piping Layout  The piping system for the DuraQuench wet pipe water mist system shall be designed in accordance with the basic design  principals used by traditional wet pipe sprinkler systems. The piping system must be sized to suit the application design  in order to achieve the correct design parameters for both water flow and pressure drop.  Hydraulic Calculations  The pipe network shall be hydraulic pressure loss calculated in accordance with the requirements of NFPA 750 and the  requirements and regulations adopted by the authority having jurisdiction using the following formulas.  Hydraulic calculations for systems with working pressures not exceeding 175 psi (12 bar) shall be performed using the  Hazen‐Williams  calculation  method.  If  the  system  working  pressure  exceeds  175  psi  (12  bar)  the  system  shall  be  hydraulic calculated using the Darcy‐Weisbach calculation method.  The hydraulic design shall ensure the presence of  the necessary water flow, water pressure and quantity of water needed for the full system operation time.  For  FM  Approved  installations,  the  system  shall  be  hydraulic  pressure  loss  calculated  from  the  most  remote  nine ...
  • Page 55: Installation

      4. INSTALLATION  This section provides installation instructions for the major components that make up the DuraQuench wet pipe water  mist system. Each subsection provides detailed instructions on how to install a specific component of the system. All  installation steps shall be completed before the applicable component can be considered installed and operational.  The  components  shall  be  checked  that  they  live  up  to  the  specifications  listed  in  the  system  plans  and  to  the  requirements listed in this manual and component manuals and subsequent standards. When handling the components  and  pipes  the  handler  shall  be  cautious  not  to  compromise  the  components  by  dropping,  bumping  or  otherwise ...
  • Page 56: Mounting

      Mounting  The pump skid is constructed with the following features that enable it to be easily maneuvered to its final installation  location and secured in place.  1. The skid is equipped with fork lift slots at each end of the skid to allow it to be easily lifted using a standard forklift  with adjustable forks. See Figure 41.  2. Two lifting eyes are provided at each end of the skid to allow it to be lifted using lifting devices such as a crane or  hoist. See Figure 41.  3. Optional rolling casters (P/N 02‐15334) can be ordered and mounted to the skid in the field to allow the unit to be  rolled into its mounting location. See Figure 42.    Figure 41: Pump Skid Lifting and Mounting Points    Figure 42: Pump Skid with Casters Installed  Pump skid unit shall be installed and anchored on a suitable foundation (provided by others) using the four mounting  holes provided on the pump skid. See Figure 41. Pump skid unit must be leveled and piping connection locations verified  prior to installation of the skid to ensure piping mates up with the pump flanges without strain.      Page 48   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 57: Pump Skid Dimensions

    [18]  [37]  [218]  [18]  [36]  [180]  [177.80  [24]  86  22  30  7  14.75  90  7  14  71  82.71  9.5  02‐14909‐5  [218]  [56]  [76]  [18]  [37]  [229]  [18]  [36]  [180]  [210.10]  [24]  *Dimensions are rough and will vary slightly due to manufacturing tolerances.        P/N 06‐791‐4 (Rev. 4)   Page 49 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 58: Power Supply Connection To Pump Controller

    (NFPA  750;  6.9.2.2).  However,  power  feed  shall  be  arranged  so  that  if  the  power  supply  within  the  protected facility itself must be disconnected during a fire, the power supply to the pump feeder circuit will not be  interrupted (NFPA 750: 6.9.2.3).  Power Supply Capacity  Power supply shall be capable of carrying indefinitely the sum of the locked‐rotor current of the fire pump motor(s) and  pressure maintenance pump motor(s) and the full‐load current of the associated fire pump accessory equipment. The  following formula can be used to calculate the pump’s motor inrush current, also known as locked‐rotor amps or LRA.  Simply insert the motor’s KVA/HP, HP rating, and Voltage values into the formula.  LRA = (KVA/HP x Motor HP x 1000) / (1.732 x Motor Voltage)  Detection and Releasing Panel Connections to Pump Controller  The buyer is responsible for material and labor required to connect the detection and releasing panel to the pump skid  controller for pump activation and monitoring purposes, where required. Refer to documentation supplied with the  pump controller for connection requirements.   Fike recommends that the fire detection control panel and associated control modules used to monitor and control the  pump skid be located outside the water mist protected area so they are not subject to the effects of the fire, which  could render them inoperable.      Page 50   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 59: Pipe Connections

    3” NPS  2” NPS  2” NPS  1” NPS  (420 lpm)  1,758 lbs.  02‐14909‐3‐X‐(21‐30)   (797 kg)  1,619 lbs.   02‐14909‐4‐X‐(1‐10)  (734 kg)  75 gpm  3” NPS  2” NPS  2” NPS  1” NPS  (284 lpm)  1,734 lbs.  02‐14909‐4‐X‐(21‐30)   (787 kg)  1,768 lbs.  02‐14909‐5‐X‐(1‐10)   (802 kg)  133 gpm  3” NPS  2” NPS  2” NPS  1” NPS  (503 lpm)  1,883 lbs.  02‐14909‐5‐X‐(21‐30)   (854 kg)        P/N 06‐791‐4 (Rev. 4)   Page 51 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 60: Circulation Relief Valve Connection

      Circulation Relief Valve Connection  Each DuraQuench pump skid is equipped with a circulation relief valve. The valve is designed to provide cooling water  when  the  pump  is  operating at churn  (no flow) conditions.  The  valve  is set  to  automatically open  when  the  system  pressure reaches 275 psi (19 bar). The valve provides a 1” NPT female outlet for connection of a drain pipe that must be  routed outdoors or to a floor drain where the discharge can be observed by the pump operator.  Water Supply Connection  To facilitate easy connection of the DuraQuench pump skid to the system water supply, Fike provides the necessary  components to install the required suction isolation valve and connect the water supply to the pump skid. The supplied  components vary depending upon the inlet size of the pump skid. See Figures 44 and 45.      Figure 44: 2” (DN50) Pump Skid  Water Supply Connection    Item  Figure 45: 3” (DN80) Pump Skid  No.  Description  P/N  Water Supply Connection  1  Pump skid inlet flange  N/A  2  2” NPT threaded flange  02‐17225* ...
  • Page 61: Test Header Connection

    In  order  to  prevent  water  damage,  the  discharge  from  the  test  header  connection  shall  be  piped  to  a  safe  discharge  location  where  there  is  adequate  drainage  for  the  pressurized  water  discharge. A flanged outlet and an isolation valve are provided on the DuraQuench pump skid to allow easy connection  and isolation of the test header components. See Figure 46.   ...
  • Page 62: Fire Department Connection

    1. Where the system’s design pressure is less than or equal to 175 psi (12 bar), the FDC connection shall be made  after the fire pump on the supply side of the pump skid, as shown in Figure 47. Installation of the FDC in this  manner requires that a strainer or filter be installed in the FDC supply line.    Figure 47: Fire Department Connection for System Design Pressure <= 175 psi (12 bar)  1. Suction flange  10.  Discharge isolation valve (monitored)  2. Suction basket strainer   11.  Discharge flange  3. Suction pressure gauge   12.  Discharge check valve  4. Circulation relief valve (opens at 275 psi/19 bar)  13. Isolation valve  5. Centrifugal pump and motor  14. Strainer or filter  6. Pressure relief valve (opens at 245 psi/16.9 bar)  15.  Check valve  7. Test header stop valve (monitored)  16. Drain valve (piped to drain)  8. Test header flange  17. Fire department connection  9. Discharge pressure gauge      Page 54   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 63: Figure 48: Fire Department Connection For System Design Pressure >175 Psi (12 Bar)

      2. Where the system’s design pressure is greater than 175 psi (12 bar), the FDC connection shall be made on the  suction side of the fire pump, as shown in Figure 48.    Figure 48: Fire Department Connection for System Design Pressure >175 psi (12 bar)  1. Suction flange  9. Discharge pressure gauge  2. Suction basket strainer   10.  Discharge isolation valve (monitored)  3. Suction pressure gauge   11.  Discharge flange  4. Circulation relief valve (opens at 275 psi/19 bar)  12.  Supply isolation valve (monitored)  5. Centrifugal pump and motor  13.  Check valve  6. Pressure relief valve (opens at 245 psi/16.9 bar)  14. Drain valve  7. Test header stop valve (monitored)  15. Fire department connection  8. Test header flange          P/N 06‐791‐4 (Rev. 4)   Page 55 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 64: Pressure Maintenance (Jockey) Pump Connection

      Pressure Maintenance (Jockey) Pump Connection  When  a  jockey  pump  is  utilized,  a  pressure  sensing  line  connection  to  the  pump  controller  is  required  for  pump  activation. This piping connection enables the pump controller to sense a pressure drop in the piping network due to  the opening of a single nozzle triggering activation of the fire pump. There are two options for connecting a jockey pump  to the DuraQuench pump skid as described below.  Option 1:  If initially ordered as part of the pump skid, the jockey pump and required isolation valves are factory‐installed onto the  pump skid prior to shipment. See Figure 49. The jockey pump controller (item 22), pressure sensing line connection  (item 23) and electrical connection between the jockey pump motor and the jockey pump controller (item 24) must be  field installed. A pipe flange (item 20) is factory installed on the pump skid to facilitate easy connection of the field piping  to the pump skid.    Figure 49: Wet Pipe System with Pressure Maintenance Pump mounted on the Skid  1. Suction isolation valve (monitored)  13.  Discharge pressure gauge  2.  Suction flange  14.  Discharge isolation valve (monitored)  3.  Suction basket strainer  15.  Discharge flange  4.  Suction pressure gauge  16.  Check Valve ...
  • Page 65: Figure 50: Wet Pipe System With Pressure Maintenance Pump Mounted Off The Skid

    (item  5)  must  be  temporarily removed and a pipe tee must be installed to allow connection of both the jockey pump and circulation relief  valve.     Figure 50: Wet Pipe System with Pressure Maintenance Pump mounted off the Skid  1. Suction isolation valve (monitored)  13.  Discharge pressure gauge  2.  Suction flange  14.  Discharge isolation valve (monitored)  3.  Suction basket strainer  15.  Discharge flange  4.  Suction pressure gauge  16.  Check Valve  5.  Circulation relief valve (opens at 275 psi/19 bar)  17.  Jockey pump isolation valve  6.  Centrifugal pump and motor  18.  Jockey pump and motor  7.  Test header isolation valve (monitored)  19.  Check valve  8.  Test header flange  20.  Jockey pump isolation valve  9.  Pressure relief valve (opens at 245 psi/16.9 bar)  21.  Jockey pump controller  10.  Fire pump controller  22.  Jockey pump pressure sensing line  11.  Pump controller to motor electrical connection  23.  Electrical connection – jockey pump motor to controller  12.  Fire pump pressure sensing line          P/N 06‐791‐4 (Rev. 4)   Page 57 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 66: System Piping And Components

    All  system  components  shall  be  secured  to  rigid  construction  elements  using  FM  Approved,  or  FM  accepted  pipe  hangers in accordance with the requirements of NFPA 13 and FM Global for sprinkler fire protection systems.  CAUTION  Pipe  hangers  for  stainless  steel  pipes  should  be  made  of  stainless  steel,  or  steel  material  should  be  galvanically insulated from the stainless steel pipes.      Page 58   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 67: Frost Protection

    Water filled pipes and reservoirs located in locations with risks of frost shall be trace heated, and the trace heating  system shall be monitored by an FM Approved alarm system. The pipes leading up to the water mist nozzles shall be  installed in a frost free location.  4.3. Wet Alarm Control Valve  The Wet Alarm Check valve (WAC) shall be installed as shown on the system design documentation, and in accordance  with the manufacturer’s instructions. Where the WAC valve is used, refer to Fike document 06‐791‐3 for installation  instructions. The valve shall be installed so it is accessible for operation, inspection, and maintenance, but shall not be  installed where it will be subject to damage that would prevent proper operation.  4.4. Automatic Bypass Valve  Every DuraQuench pump skid is equipped with an automatic bypass valve that ensures a continuous flow through the  pump when running by diverting a portion or all of the pump discharge back to the pump suction based on the process  flow. The bypass valve is closed when the process flow is greater than the control set point (that is, minimum flow rate  required), opens gradually as the process flow is reduced and pressure increases, and is fully open when the process  flow is reduced or stopped resulting in an increase in pressure greater than the bypass valve’s set point.   NOTE: The bypass valve is factory set to begin opening when the inlet pressure to the valve reaches 250 psi (17.2 bar).  Should the operating set point or opening and closing speed of the bypass valve need to be adjusted, refer to  Appendix A for instructions.  4.5. Nozzles  The  OH‐VSO  nozzles  shall  be  installed  in  strict  accordance  with  the  design  documentation  prepared  for  the  specific  installation  and  in  accordance  with  the  following  guidelines.  Any  required  deviations  must  be  approved  prior  to ...
  • Page 68: Signage

    Install  permanently  marked,  weatherproof,  metal  or  rigid  plastic  identification  signs  at  all  control,  drain,  and  test  connection valves. The signs shall be secured with corrosion resistant wire, chain, or other approved means.  A system design information sign shall be attached to the pump skid and shall include the following information:  1. Location of the design area or areas  2. Design area of water application or volume of space protected.  3. Nozzle manufacturer and model number  4. Area per nozzle  5. Total number of nozzles in design area  6. Minimum rate of water application (density)  7. Total water requirement as calculated  8. Description of hazard protected  9. Description of any compartment or enclosure characteristics that are essential to system performance  10. Name of installing contractor and contact information  Page 60   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 69: System Acceptance And Commissioning

      5. SYSTEM ACCEPTANCE AND COMMISSIONING  The DuraQuench water mist system shall successfully meet all system acceptance and commissioning procedures and  should be documented with copies provided to the system owner and manufacturer. All acceptance and commissioning  procedures shall be reviewed by FM Global. FM Global can request changes prior to granting the approval.  Refer to the following Fike documents for system Startup and Testing procedures:  1. 06‐814 – Centrifugal Fire Pump Acceptance Test Form  2. 06‐815 – Fire Pump Controller Start‐Up Form  3. 06‐816 – Water Mist System Acceptance Test Form  5.1. Commissioning Requirements  Acceptance and commissioning testing should include the following:  1. Acceptance procedures shall be in accordance with: FM Global Property Loss Prevention Data Sheet Number 4‐2,  Water  Mist  Systems;  NFPA  750,  Standard  on  Water Mist  Fire  Protection  Systems;  NFPA  25,  Standard  for  the  Inspection, Testing and Maintenance of Water‐Based Fire Protection Systems; or equivalent national code of  the country of use.  2. An appropriate Authority having Jurisdiction representative should be given advance notice of such testing and  be present for commissioning of the system.  3. A trained manufacturer’s representative should be present to properly test and reset the system following the ...
  • Page 70: Operation

      6. OPERATION  Subject to the specific project requirements, the DuraQuench wet pipe water mist system will be arranged to operate  automatically as described in this section.  6.1. Wet Pipe System with an Alarm Check Valve  Upon activation of an OH‐VSO nozzle in response to a fire event, the following events shall occur:  1. Water will begin to flow through the activated OH‐VSO nozzle.  2. Water will begin to flow through the wet alarm check valve, activating the valve’s integral water flow sensor  which is monitored by the fire detection and releasing panel.  3. Upon receipt of the water flow signal, the fire detection and releasing panel shall:  Initiate a fire alarm signal to the fire brigade.  b. Activate an exterior water flow alarm bell.  Activate interior alarm notification appliances for building occupant notification.  Upon activation of a water flow switch, the following events shall occur:  1. Initiate an electrical signal to the fire detection and releasing panel.  2. Upon receipt of the water flow signal, the fire detection and releasing panel shall:  Initiate an electrical signal to the fire pump controller to initiate start‐up of the fire pump.  3. The system will discharge on a continuous basis through the pipe distribution system to the water spray nozzles  until the fire pump is manually stopped at the fire pump controller.  6.2. Wet Pipe System with Maintained Excess Pressure  Upon activation of an OH‐VSO nozzle in response to a fire event, the following events shall occur:  1. Water will begin to flow through the activated OH‐VSO nozzle.  2. Water will begin to flow through the wet alarm check valve, activating the valve’s integral water flow sensor  which is monitored by the fire detection and releasing panel.  3. Upon receipt of the water flow signal, the fire detection and releasing panel shall:  Initiate a fire alarm signal to the fire brigade.  b. Activate an exterior water flow alarm bell. ...
  • Page 71: Inspection And Testing

      7. INSPECTION AND TESTING  The DuraQuench water mist system shall be inspected and tested in accordance with the requirements of the following  documents and standards to verify that it functions as intended:   FM Global Property Loss Prevention Data Sheet Number 4‐2, Water Mist Systems   FM  Global  Property  Loss  Prevention  Data  Sheet  Number  2‐8,  Fire  Protection  System  Inspection,  Testing  and  Maintenance.   NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water‐Based Fire Protection Systems   NFPA 750, Standard on Water Mist Fire Protection Systems   Local code requirements  7.1. Nozzles  Water mist nozzles shall be inspected from the floor level annually. Any nozzles that show signs of any of the following  shall be replaced:  1. Leakage  2. Corrosion  3. Physical damage ...
  • Page 72: Maintenance

    Clean or replace as required  After system operation  System components should be maintained as follows:   In accordance with the recommendations of the component manufacturer.   System strainers should be emptied and cleaned after each pump system test.   Water reservoir level control should be regularly checked and if necessary maintained.   The DuraQuench system should be regularly maintained and when faults are found they should be rectified as  soon as possible.   Check for the presence of spare components.  CAUTION  When  unscrewing  system  components  for  inspection  or  maintenance  it  is  important  to  clean  the  inside  connecting threads for sealants before refitting components to the female threads. This should be rigorously  conducted to avoid introducing debris into the pipe network.  8.1. Maintenance of Surrounding Areas  Should  the  area  surrounding  the  OH‐VSO  nozzles  need  maintenance,  it  is  important  to  protect  the  nozzles  from  any ...
  • Page 73: Restoring The System

    2. Notify remote monitoring entity and fire brigade that the water mist system is going to be taken out of service.  3. Power down the fire pump controller by closing the Circuit Breaker Switch and then the Isolating Switch. Verify  loss of AC power to the controller is indicated on the Detection and Releasing panel.  4. For system equipped with a pressure maintenance (jockey) pump, power down the jockey pump by switching  the selector switch on the jockey pump controller to the OFF position.  5. Close the isolation valve located on the water supply, suction side of the pump skid and verify that a supervisory  signal is indicated at the Detection and Releasing panel.  6. Clean the pump skid strainer per the procedure outlined in Annex B.  7. The activated nozzles shall be removed and returned to FIKE, the thread sealant removed and new nozzles shall  be installed in their place. It is recommended that activated nozzles be replaced by nozzles of same make and  build as to make certain that the correct spacing and height of nozzle is achieved.  8. Nozzles in the adjacent areas of the activated zone/nozzles shall be visually inspected. This requires the nozzles  to have intact bulbs with a sufficient amount of liquid within, no signs of any leakages and retaining a small  spherical concentration of air within the liquid at room temperatures, i.e. 25° C ±5 (≈68° F ±10). Nozzles which  do not comply with above mentioned requirements shall be returned to FIKE and new nozzles shall be installed  in  their  place.  Depending  on  the  situation  and  circumstances  which  actuated  the  fire  protection  system,  nozzles, which have not been activated, in the vicinity of the activated nozzles may have been contaminated  or soiled as a result of fire or other chemical reactions in the vicinity of the nozzles. Because of the sensitive ...
  • Page 74   ANNEX A – AUTOMATIC LOW FLOW BYPASS VALVE ADJUSTMENTS  The pressure relief valve on the DuraQuench pump skid is factory set to open when the inlet pressure reaches 245 psi  (16.9  bar)  to  allow  excess  pressure  in  the  system  piping  to  be  relieved  to  the  pump  suction  inlet.  When  a  variable  frequency drive pump controller is used, the pressure set point of the relief valve must be field adjusted to a minimum  of 10 psi (0.68 bar) above the set (operating) pressure of the variable speed frequency drive (VFD).  CAUTION:  Pressure relief valve adjustment is only to be performed by experienced personnel who understand the  impact of adjusting the pressure relief setting and who take full responsibility for the relief setting.  1. Prime the pump following the procedure outlined in  Appendix D.2.  2. Perform pump startup following the procedure outlined  in Appendix D.3.  3. Confirm that the discharge isolating valve on the pump  skid is closed.  4. Confirm that the test header isolating valve on the ...
  • Page 75: Annex B - Basket Strainer Cleaning Procedure

    The pump skid basket strainer must be cleaned as described below after activation of the fire pump. See Figure 55.  1) Close the Suction isolation valve and Supply isolation valve on  the pump skid.  2) Loosen T‐bolt on top of strainer and swing yoke clear of cover.  3) Remove the strainer cover making sure O‐ring remains intact.  4) Lift strainer basket from the strainer body.  5) Invert the basket and wash out debris by directing a stream of  air or water against the basket exterior.  NOTE ‐ Do not allow basket contents to dry as this will make cleaning  most difficult.  6) Inspect basket strainer at each cleaning for holes or tares and  replace as required.  7) Place clean or new basket squarely on the basket seat. Be sure  basket handle is sufficiently high to be compressed by strainer  cover.  8) Inspect O‐ring and seal surface.  Clean seat or replace O‐ring as  necessary.  9) Replace strainer cover making sure O‐ring is in place.  Figure 54: Basket Strainer  10) Swing the yoke over the cover and make full contact with the  yoke stud.  11) Tighten the center T‐bolt.  12) Perform pump skid startup procedure.  P/N 06‐791‐4 (Rev. 4)   Page 67 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 76: Annex C - Oh-Vso Nozzle Obstructions

    If  any  uncertainty  should  arise  regarding  the  placement  of  OH‐VSO  nozzles  adjacent  to  obstructions,  the  person  or  persons in charge shall consult the local authority having jurisdiction. Should the uncertainty remain after consulting the  local authorities having jurisdiction, Fike shall be contacted for advice on the subject.  In  order  to  simplify  the  process  of  determining  whether  an  object  is  an  obstruction  for  the  OH‐VSO,  the  subject  of  obstructions has been divided into two subdivisions; Ceiling‐fixed Obstructions and Pendent Obstructions. ...
  • Page 77: Figure 56: Obstructions Of Single Pendent Nozzles

    ) is not to exceed 25% of the area of the spray pattern at the top of the obstruction (A ).  If the area of an obstruction (A ) exceeds 25% of the spray pattern area at the top of obstruction (A ), additional nozzles  shall  be  installed  beneath  or  adjacent  to  the  obstruction  so  the  obstruction  is  protected.  Additional  nozzles  shall  therefore be installed beneath or adjacent to the obstruction, if the following statement is true: (A  / A ) ◦ 100 ≥ 25%.    Figure 56: Obstructions of Single Pendent Nozzles  Obstructions of Multiple Pendent Nozzles:  Obstructions shall be exempted from the above mentioned requirements only if the obstructions are situated in the  spray pattern of two or more nozzles and that they do not obstruct more than 30% of the spray pattern area at the top  of the obstruction (A ) of each of the involved nozzles.    Figure 57: Obstructions of Multiple Pendent Nozzles    P/N 06‐791‐4 (Rev. 4)   Page 69 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 78 π  Area of Circle: r π  Distance from Nozzle: 0.65 m   Distance from Nozzle: 0.65 m  r of A  = 1.87 m    r of A  = 1.8 m  2     = r π = 1.8 π = 10.986  = r π = 1.8 π = 10.986       2     = πab = π1.11 x 0.625 = 2.18 m  = πab = π1.35 x 0.735 = 3.12 m     (2.18/10.986) x 100 = 19.84%    (3.12/10.986) x 100 = 28.4%    The elliptical obstruction above is therefore acceptable.  The elliptical obstruction above is therefore  unacceptable and additional nozzles shall be  installed.  Page 70   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 79 Distance from Nozzle: 0.5 m  r of A  = 1.67 m    r of A  = 1.67 m  2     = r π = 1.67 π = 8.76  = r π = 1.67 π = 8.76       2     = s  x s  = 0.8 x 0.32 = 0.256 m  = s  x s  = 2 x 1.87 = 3.56 m     (0.256/8.76) x 100 = 2.93%    (0.256/8.76) x 100 = 40.64%    The obstruction above is therefore acceptable.  The obstruction above is therefore  unacceptable and additional nozzles shall be  installed.  P/N 06‐791‐4 (Rev. 4)   Page 71 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 80: Annex D - Pump Information

    Production number  3  Head in Feet at Rated Flow  444.9  500.3  4  Rated Motor hp (P2)  15  25  5  Head at Zero Flow (max)  554.5  638.5  6  Rated rpm  2924  2934  7  Rated Flow (gpm)  74.85  132.09  8  Rated Frequency (Hz)  50  50  Maximum Pressure / Maximum  9  363 / 194  435 / 194  Liquid Temperature  10  Direction of Rotation  CCW  CCW    Page 72   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 81: Figure 59: Fire Pump Vent Plug

      D.2. Priming the Pump  CAUTION:  Be sure the isolation valve on the discharge side of the DuraQuench pump skid is closed and the fire pump  is primed (filled with water) and ready operation prior to starting the pump. Failure to prime the pump  before running the motor will cause damage to the motor bearings.    CAUTION:  Pump motor should not be run unloaded or uncoupled from the pump at any time; damage to the motor  bearings will occur.  1. Close the discharge isolating valve on the pump skid to prevent water from flowing into the piping network.  2. Close the water supply isolating valve on the pump skid to prevent water from flowing into the pump skid.  3. Open the priming plug on the pump head. See Figure 60.  LOOSEN CENTER PLUG TO  VENT PUMP  Figure 59: Fire Pump Vent Plug  4. Gradually open the water supply isolating valve on the pump skid until a steady stream of airless water  runs out of the priming hole.  5. Close the plug and tighten securely.  6. Completely open the water supply isolating valve on the pump skid. The discharge isolating valve should  remain closed until testing of the pump is complete.  7. Pump is now ready for functional testing.    P/N 06‐791‐4 (Rev. 4)   Page 73 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 82: Figure 60: Fire Pump Coupling Guard

    10. Re‐close the controller cabinet door then close the IS and CB to re‐energize the controller.  11. Jog (bump) the motor again to verify correct direction of rotation (counter‐clockwise).  12. Once the correct direction of rotation has been visually verified, open the CB and the IS to remove power  from the controller.  13. Replace the coupling guard on the fire pump; then re‐apply power to the controller. Do not attempt to  reinstall the coupling guard while power is applied to the controller.  14. Check that the display is powered up with no Alarms present.  CAUTION  Motors  should  not  be  run  unloaded  or  uncoupled  from  the  pump  at  any  time;  damage  to  the  motor  bearings will occur. Do not start the pump before priming or venting the pump. Never let the pump run  dry.      Page 74   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 83   D.4. Pump Performance Curves  02‐14909‐1, 53 gpm (200 l/min) / 60 Hz Pump  02‐14909‐2, 53 gpm (200 l/min) / 60 Hz Pump (increased pressure)  ‐14 (02‐14909‐2‐X‐X)   ‐12 (02‐14909‐1‐X‐X)         P/N 06‐791‐4 (Rev. 4)   Page 75 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 84   02‐14909‐3, 111 gpm (420 l/min) / 60 Hz Pump  ‐10 (02‐14909‐3‐X‐X)         Page 76   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 85   02‐14909‐4, 75 gpm (284 l/min) / 50 Hz Pump  ‐12 (02‐14909‐4‐X‐X)         P/N 06‐791‐4 (Rev. 4)   Page 77 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 86   02‐14909‐5, 133 gpm (503 l/min) / 50 Hz Pump  ‐10   <(02‐14909‐5‐X‐X)         Page 78   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 87   D.5. Factory Pump Performance Curves  02‐14909‐1, 53 GPM / 60 Hz Fire Pump    P/N 06‐791‐4 (Rev. 4)   Page 79 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 88     02‐14909‐2, 53 GPM / 60 Hz Fire Pump   Page 80   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 89     02‐14909‐3, 111 GPM / 60 Hz Fire Pump P/N 06‐791‐4 (Rev. 4)   Page 81 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 90     02‐14909‐4, 75 GPM / 50 Hz Fire Pump     Page 82   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 91     02‐14909‐5, 133 GPM / 50 Hz Fire Pump           P/N 06‐791‐4 (Rev. 4)   Page 83 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 92                                 This page intentionally left blank.    Page 84   P/N 06‐791‐4 (Rev. 4)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 93      ...
  • Page 94                                   CONTACT US  Fike World Headquarters  704 SW 10  Street  Blue Springs, Missouri 64015 USA  Tel: +001 816‐229‐3405  Toll Free (US Only): 1‐800‐YES‐FIKE (1‐800‐937‐3453)  www.Fike.com  For a list of contact information for Fike offices around  the world, visit the Global Locations section of Fike.com   ...

Table of Contents