Fike DuraQuench Installation, Operation And Maintenance Manual
Fike DuraQuench Installation, Operation And Maintenance Manual

Fike DuraQuench Installation, Operation And Maintenance Manual

Electric fire pump controller

Advertisement

Quick Links

 
 
INSTALLATION, OPERATION AND MAINTENANCE 
MANUAL 
 
 
 
DuraQuench™
ELECTRIC FIRE PUMP CONTROLLER 
 
 
 
Instructional Startup Video 
 
 
Doc. P/N 06‐791‐2 
Rev. 1
 
 
SOLUTIONS 
Fire Protection 
Explosion Protection 
Overpressure Protection 
Pressure Activation 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DuraQuench and is the answer not in the manual?

Questions and answers

Summary of Contents for Fike DuraQuench

  • Page 1     INSTALLATION, OPERATION AND MAINTENANCE  MANUAL        DuraQuench™ ELECTRIC FIRE PUMP CONTROLLER        Instructional Startup Video        Doc. P/N 06‐791‐2  Rev. 1   SOLUTIONS   Fire Protection   Explosion Protection   Overpressure Protection   Pressure Activation ...
  • Page 2 You  should  install  and  use  the  Fike  products  described  in  this  document  in  compliance  with  all  applicable  laws,  standards, and regulations. Fike assumes no liability for damages or losses occurring as a result of your noncompliance  with applicable laws and regulations.  It is the responsibility of the buyer or distributor of Fike products, who distributes, disposes of, or otherwise places the  product with a third party, to notify such third party in advance of the contents and conditions set forth in this document.  Fike assumes no responsibility for any losses incurred by you or third parties as a result of unauthorized use of Fike  products.  QUALITY NOTICE  Fike  is  an  ISO  9001:2015  certified  company.    Prior  to  shipment,  we  thoroughly  test  our  products  and  review  our  documentation to assure the highest quality in all respects.     ...
  • Page 3: Table Of Contents

    5. Menu Functions  ................................. 14  5.1. Functions on Main Menu ........................... 14  5.2. Functions on Alarm Status Menu ........................ 14  5.3. Function on System Status Menu  ........................ 15  5.4. Functions on Settings Menu  .......................... 15  6. Advanced Setup  ................................. 16  7. Setting Summary ............................... 18  8. Start‐up Procedure .............................. 19   9. Operating Instructions  ............................... 23  10. Downloading History .............................. 24  11. Maintenance ................................ 25  12. Replacement Parts List .............................. 26   Drawings  .................................. 27  External Wiring Diagram   Schematic Diagram  Piping Connection   P/N 06‐791‐2 (Rev. 1)   Page 1 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 4: Important Safety Information

    WARNING  DO NOT DEFEAT ANY INTERLOCKS OR SAFETY FEATURES OR EQUIPMENT OR CIRCUITRY.     WARNING  FOREIGN  VOLTAGE  MAY  BE  PRESENT.    CONTROLLERS  EQUIPPED  WITH  MODIFICATION  “SP1”  OR  “SP2”  UTILIZE AUXILIARY BRANCH CIRCUIT POWER WHICH IS NOT SWITCHED OR CONTROLLED BY THE ISOLATING  SWITCH (IS) OR CIRCUIT BREAKER (CB).  ALWAYS TURN OFF OR DISCONNECT THE EXTERNAL SOURCE OF  POWER BEFORE ATTEMPTING TO SERVICE THE CONTROLLER.     WARNING  BEFORE  ATTEMPTING  TO  MAINTENANCE  OR  SERVICE  THIS  EQUIPMENT,  BE  SURE  TO  FOLLOW  THE  PLACARD INSTRUCTIONS TO DE‐ENERGIZE BOTH THE TRANSFER SWITCH AND FIRE PUMP CONTROLLER.   Page 2   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 5: General Description And Installation

      1. GENERAL DESCRIPTION AND INSTALLATION  The combined Manual and Automatic Electric Fire Pump Controller is an integral component of the DuraQuench pump  skid.  It  meets  all  of  the  requirements  of  NFPA‐20,  Standard  for  the  Installation  of  Stationary  Fire  Pumps  for  Fire  Protection and FM Property Loss Prevention Data Sheet 3‐7, Fire Protection Pumps.  The controller provides across‐the‐line (direct‐on‐line) full voltage starting for the three phase motor driven fire pump  installed on the DuraQuench pump skid. The controller is used where local power limitations do not restrict the motor  starting in‐rush (locked rotor) current.  The controller is ordered with horsepower and voltage options to meet specific project requirements. Refer to Fike’s  pump skid data sheet for ordering format.  1.1. Standard Functions   • Pressure Start   • Remote Start   • Deluge Start   • Manual, Non‐Automatic Operation (Remote, Deluge, or Manual Start Only)   • Sequence Delay  ...
  • Page 6: Standard Product Specifications

      5  50  K  7 ½  60  H    7 ½   50  J  10  60  H    10 & up  50  H  15 & up  60  G          Remote Contacts – On the control unit (CU), the voltage free contacts are rated for 2 amps (resistive) at 30 VDC, or 1  amp (resistive) at 125 VAC.   Remote Contacts – On the programmable option chassis (POC), the voltage free contacts are rated for 6 amps (resistive)  at 30 VDC, 6 amps (resistive) at 250 VAC.  They also carry UL pilot duty ratings R300 and B300.   Pressure Rating – Standard controllers are rated for 300 PSI (20.7 BAR).  Higher ratings are available.   Plumbing – Standard controllers are provided with brass fittings.  Other materials are available.   Enclosure – Standard controllers are rated for NEMA type 2 or IP‐31.  Other enclosures are available.   Ambient Temperature – Rated for operation in a 50°C ambient provided the input and output cable has a temperature  rating of 105°C.  For a 40°C ambient, the temperature rating of the cable can be reduced to 90°C. No direct sunlight is  allowed on the enclosure.   Electromagnetic Compatibility – Tested to comply with EN 61000‐6‐2 for immunity and EN 61000‐6‐4 for emissions.   Page 4   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 7: Annotated Controller Illustration

      1.3. ANNOTATED CONTROLLER ILLUSTRATION  USB Waterproof Adapter  Audible Alarm  Color Display  Isolating Switch  (Isolating Means)  Circuit Breaker  (Disconnecting Means)  Start (Pushbutton)  Stop (Pushbutton)  Emergency Manual Operator Latch  Emergency Manual Operator  Pressure Sense Line Connection  Line Chassis Isolating Switch Control Unit Customer Terminal Bar 1 (TB1) Circuit Breaker Current Transformers  Contactors P/N 06‐791‐2 (Rev. 1)   Page 5 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 8: Installation

      2. INSTALLATION  The fire pump controller is an integral part of the DuraQuench pump skid. It is securely mounted and bolted to the pump  skid frame prior to shipment from the factory. The controller and all of its wiring and plumbing should be installed in  accordance  with  the  requirements  outlined  in  this  section  and  the  external  wiring  diagram(s)  near  the  end  of  this  manual. It should also be installed in accordance with the requirements of: NFPA‐20, Standard for the Installation of  Stationary Fire Pumps for Fire Protection; NFPA‐70, article 695, the National Electric Code; FM Property Loss Prevention  Data Sheet 3‐7, Fire Protection Pumps; as well as any local requirements.   CAUTION  Prior  to  installation,  check  that  the  system  voltage  and  the  motor  nameplate  voltage  and  horsepower ...
  • Page 9: Motor Circuit Conductors

      2.3. MOTOR CIRCUIT CONDUCTORS  The pump motor on the DuraQuench pump skid is pre‐wired to the controller prior to shipment from the factory. Circuit  conductors  are  secured  in  such  a  manner  so  they  will  not  move  or  interfere  or  rub  against  any  components  or  mechanisms with sharp edges or corners that are mounted on the pump skid or contained within the controller cabinet.  The output motor wiring is connected to the bottom of the controller’s Main Contactor M load side terminal lugs T1,  T2, and T3. Refer to the External Wiring diagram located near the end of this manual for details.  All motor circuit conductors are sized according to the National Electric Code (NFPA‐70) on a continuous duty basis.  Insulation for these conductors is chosen so it will not be affected by the surrounding environment and will have an  insulation temperature rating at least 90 degrees C for an ambient of 40C or at least 105C for an ambient of 50C.   The ampacity of the wire is based on 125% of the motor full load current (FLA) using the 60C column for 100 amps or  less and the 75C column in field wiring table 310.15(B)(16) of the 2011 edition of the NFPA 70 for higher currents.  Also,  applying the appropriate correction factors in accordance with 310.15(B)(1) through 310.15(B)(7).  NOTE  The  controller  is  Service  Entrance  Rated  so  a  dual  grounding  lug  is  provided  for  the  grounding  electrode ...
  • Page 10: Remote Inputs

    #12   1.588   15,700 Ft.   78,500 Ft.  #14   2.525   9,900   49,000  #16   4.016   6,200   31,000  #18   6.385   3,900   19,500  #20   10.15   2,500   12,500  #22   16.14   1,500   7,500  #24   25.67   940   4,700  #26  40.18   620   3,100  NOTE  Resistance and number of splices and contacts in circuit must be taken into consideration.  A single splice may  exceed the total resistance of 1,000 Ft. or more of wire.   Page 8   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 11: Initial Power Up

    The  Setup  Assistant  helps  you  to  setup  all  the  basic  settings  on  the  controller.  It  allows  you  to  set  the  Start/Reset  pressures, set the display for PSI or BAR, set the Phase Rotation for ABC or CBA, enable Deluge/Remote Start, enable  the Minimum Run Timer, set the Sequence starting delay, set the accelerate time, and enable the Auto Test Timer.   By default, the controller is setup to use the pressure sensing line connection provided on the unit. If Deluge Start is to  be used in lieu of using the pressure line activation, the pump must be setup for Manual Start Only, which prevents the  pump from being started on a pressure drop. Refer to the Fire Pump Controller Setup Form (P/N 06‐815) for complete  controller setup instructions for deluge operation.  NOTE  After  the  Initial  Power  Up,  you  will  need  to  Login  to  access  the  Setup  Assistant.  See  Logging  In  for  further  information.    NOTE  All settings are automatically updated once entered into the controller.       P/N 06‐791‐2 (Rev. 1)   Page 9 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 12   Page 1 of the Setup Assistant allows you to set the Start Pressure associated with the controller’s pressure sensing line  connection, if used. On the initial Power Up, the START PSI (BAR) and RESET PSI (BAR) settings will be zero. The pump  won’t start in this condition until the START PSI (BAR) is set. To set, simply press the START PSI (BAR) button and enter  the value desired. The Reset pressure will automatically set itself to 10 PSI (0.69 BAR) above the Start pressure.   DO NOT ENTER A START PRESSURE IF THE CONTROLLER’S DELUGE START OPTION IS TO BE USED TO START THE PUMP.  Doing so may cause the controller to immediately start the pump. Proceed to Page 2 of the Setup Assistant to enable  Deluge Start. Refer to the Fire Pump Controller Setup Form (P/N 06‐815) for complete instructions on how to setup the  controller for Deluge Start operation.  CAUTION  Before entering the start and reset pressures, make sure that the pressure sensing line is connected to the  controller and that the pump discharge pressure gauge is reading a higher pressure than the start pressure  setting.  If  the  discharge  pressure  is  too  low,  the  pump  will  start  immediately  upon  entering  the  start  pressure. If this should occur, press and hold the STOP button on the front of the controller and adjust the  start pressure setting accordingly.  If you need to adjust the Reset Pressure Setting, simply push the RESET PSI (BAR) button, and set it accordingly.  Press NEXT to continue to Page 2 of the Setup Assistant, where you will find all your options and settings, including  PHASE SEQUENCE, DELUGE START, REMOTE START, MIN RUN, SEQUENCE START DELAY, and ACCEL DELAY.   Page 10   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 13 The Deluge Start function will allow a maintained contact from a Deluge Valve to call for a start, if enabled. To use this  function, you must wire a normally closed contact to the controller that opens when the Deluge Valve trips. The start  function is delayed by Sequence Start delay setting.  To enable the Deluge Start from the screen, simply toggle the DELUGE START button to enable or disable as dictated by  your needs.  NOTE  If the Deluge Start function is used as the sole means of activating the controller, the controller must be setup  for Manual Start Only, which prevents the pump from being started on a pressure drop.  Remote Start   The Remote Start function will allow a remote manual pushbutton to call for a start, if enabled. To use this function, you  must wire a normally closed contact to the controller that opens when the Remote Start button is pressed. The start  function is immediate and will not be delayed by the Sequence Start delay setting.  To enable the Remote Start from the screen, simply toggle the REMOTE START button to enable or disable as dictated  by your needs.  Minimum Run     When enabled, the Minimum Run option will run the motor for at least 600 seconds. If there is no demand after that  time, the pump will shut off immediately – however if there is a demand, the pump will continue running until the  demand is reset. Typically, this occurs when the pressure recovers to a point above the Reset Pressure setting.  To enable the Minimum Run Timer, toggle the MIN RUN button to enable or disable as dictated by your needs.  Sequence Start   This function is used to start multiple pumps in sequence. For example, if you have 3 pumps, and you want a 5 second  delay between each one starting, you would set the controllers as follows:  Controller 1: 0 seconds  Controller 2: 5 seconds  Controller 3: 10 seconds  To enable the sequence start time delay, press the SEQUENCE START DELAY button and enter the appropriate time  delay. Press ENTER and your entry will automatically be updated.  Accelerate Time Delay   On reduced voltage controllers, the Accelerate Time Delay determines how much time the controller allows for the  motor to accelerate to full speed. The maximum setting is 10 seconds.  To set the Accelerate Time Delay from the screen, press the ACCEL DELAY button and input the time delay that fits your  needs. Press ENTER and your entry will automatically be updated.  Press NEXT to continue to page 3 of the Setup Assistant, where you may set the weekly or monthly test time. P/N 06‐791‐2 (Rev. 1)   Page 11 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 14   How to Set the Weekly or Monthly Test  To enable, press the AUTO TEST button. Then select either the monthly or weekly test, and enter the time you would  like the test to automatically occur.  To set the WEEKLY TEST, enter the following:  1. The day, 1‐7 with 1 representing Monday  2. The hour, in accordance with a 24 hour clock  3. The minute, 0‐59  For example, if you would like to set the weekly test to Tuesday at 9:00 am, you would enter the following:  Day: 2  Hour: 9  Minute: 00  To set the MONTHLY TEST you must enter the following:  1. A week 1‐4, with 1 representing the first week of the month  2. A day, 1‐7 with 1 representing Monday  3. The hour, in accordance with a 24 hour clock  4. The minute 0‐59  Alternatively, if you would like to set the monthly test to the 2nd Tuesday of each month at 2:15pm, you would enter  the following:  Week: 2  Day: 2  Hour: 14  Minute: 15  NOTE  All adjustments are automatically updated as soon as they are entered.  Page 12   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 15: Logging In

    To  change  settings  on  your  G4  interface,  you  must  first  login  with  the  associated  username  and  password.  Unless  changed, the factory default username and password is as follows:   Login Factory Defaults:  Username: USER  Password: USER   Or   Username: SERVICE  Password: SERVICE   To login from the Home Screen, press SETUP to access the Setup screen. Press LOGIN and then the blue box next to User  Name and Password and enter the appropriate information. Once entered, press LOGIN. The screen shows you logged  in as the Username. Then press EXIT to go back to the Setting screen. Now press SETUP ASSISTANT or ADVANCED SETUP.  You are now logged in until any screen is idle for more than 10 minutes.    Home Screen  Setup Menu    Enter Information and Press Login  Press Exit    P/N 06‐791‐2 (Rev. 1)   Page 13 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 16: Menu Functions

    SETUP Button: This button takes you to the SETTINGS screen. From here you can access the Setup Assistant, Advanced  Setup, Service Information, Pressure Drop Test button, Alarm Test button, and Setting Summary button.  5.2. Functions on Alarm Status Menu  PUMP RUNNING Alarm: When the pump is running, the Pump Running light illuminates and the Pump Running alarm  contacts transfers.  NOTE  The alarm is activated when the motor current is greater than 20% of the motor FLA.  AC FAILURE Alarm: When one or all phases are lost, the AC Failure alarm will illuminate and the AC Failure alarm contacts  will transfer.  NOTE  If only one phase is lost, the controller implements PhaseSmart lockout which prevents the motor from starting  until the phase is restored.  PHASE SEQUENCE Alarm: When the Phase Sequence on the incoming 3‐phase source differs from the last set sequence,  the Phase Sequence alarm light will illuminate, the Audible Alarm will sound, and the remote Phase Sequence contacts  will transfer.  NOTE  See the Setup Assistant section of this manual for more information on how to initially setup this alarm.  PUMP TROUBLE STATUS Button: This button takes you to the Pump House Trouble alarm screen. When a Pump House  Trouble  alarm  contact closes,  the  appropriate  indicating  light  illuminates,  the  Audible Alarm  sounds,  and  the  Pump  House Trouble alarm contacts transfer.  Page 14   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 17: Function On System Status Menu

      5.3. Functions on System Status Menu  AUTO PRESSURE START: Illuminates when the controller is started by a pressure drop.  AUTO DELUGE START: Illuminates when the controller is started by a deluge valve contact.  AUTO REMOTE START: Illuminates when the controller is started by a remote start button.  AUTO TEST START: Illuminates when the controller is started by Auto testing or the Pressure Drop Test button is pressed.  AUTO SP1/SP2 START: Illuminates when AC power is lost to SP1 or SP2.  MANUAL LOCAL START: Illuminates when the Start Pushbutton on the front of the controller is pressurized.  MANUAL OPERATOR START: Illuminates when the Emergency Manual Operator lever is operated.  GENERATOR START: Illuminates only on a transfer switch controller when the Normal Power is lost.   Illuminates when a Low Suction pressure alarm occurs.  LOW SUCT PRESSURE: LOW SUCT SHUTDOWN: Illuminates when a Low Suction pressure shutdown occurs.  LOW DISCH PRESSURE: Illuminates when a Low Discharge pressure alarm occurs.  BYPASS MODE: Illuminates only on a soft start controller when the ATL/Soft switch is in ATL position.  TRANSDUCER TEST: Illuminates on a transducer test failure. This could be anytime when the transducer output voltage  is less than 0.9 vdc or greater than 6.2 vdc. Or it could occur during an Auto test or a Pressure Drop test if the pressure  does not drop below 10 psi.  CB TRIP TIMING: Illuminates when the circuit breaker is timing to trip. This occurs when the motor current exceeds  330% of FLA.  5.4. Functions on Settings Menu  SETUP ASSISTANT: See the Initial Setup Section in this manual. This requires User Level password. See the Logging In  section in this manual for further details.  ADVANCED SETUP: This button takes you to the Advanced Setup screen where you can setup all controller functions.  This requires User/Service Level password. See the Advance Setup section in this manual for further details.  PRESSURE DROP TEST Button: Pressing the PRESSURE DROP TEST button opens the drain valve solenoid to initiate the  motor starting sequence by a pressure drop. This button should be used for routine starting.  ALARM TEST Button: This button takes you to the Alarm Test screen where every remote alarm contact can be tested  by function. Contacts automatically transfer back to normal when the screen is exited or when the screen times out and  returns to the main menu.  SETTING SUMMARY: See the Setting Summary section in this manual for further details.  P/N 06‐791‐2 (Rev. 1)   Page 15 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 18: Advanced Setup

    Reset Pressure – enter pressure  PSI or BAR scale – press to toggle  Phase Rotation – press to toggle ABC or CBA  Minimum Run Timer – press to enable or disable  Auto Test Button – See Setup Assistant for further details  Transducer Test – press to enable or disable  Timer Settings Screen  Sequence Delay – enter time  Accelerate Delay – enter time   High Zone Delay – enter time   Failure to Start Delay – enter time  Option Settings Screen   Option Enables ‐ Page 1  Auxiliary Alarm Relay Setup (Relays provided with Mod. Code POC)  Relay Number – press to set or change  Name ‐ press to set or change  Select Function ‐ press to continue  Functions desired – press to select (also see next screen)  Note: Multiple functions can be selected (except for AC Fail)  Pump Trouble Alarm Setup (Inputs provided with Mod. Code POC)  Input Number – press set or change    Name ‐ press to set or change   Deluge Start – press to enable or disable   Remote Start – press to enable or disable  Pump Lockout – press to enable or disable (note: not allowed per NFPA 20)  Motor Run Audible – press to enable or disable  Option Enables ‐ Page 2  Low Suction Pressure Setup (Suction transducer provided with Mod. Code 83LT)  Low Suction – press to enable or disable  Low Suction Trip Pressure – enter pressure   Low Suction Alarm Delay – enter time  Low Suction Reset Pressure – enter pressure  Low Suction Shutdown – press to enable or disable  Note: not allowed per NFPA 20  Low Suction Shutdown Delay – enter time  Page 16   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 19 Change Day – press to enter day of the week 1 through 7 (Monday is day 1)  Change Time – press to enter hour, minute, second  Change Date – press to enter Year, Month, Day  Daylight Savings Time On/Off – press to enable or disable  Hold to Clear Data Memory – press and hold to delete all history (factory PW)  Data Order New to Old or Old to New – press to toggle  If logged in under SERVICE/SERVICE, the Advanced Setup Screen enables an additional Service button. Here the  analog signals can be recalibrated.  CAUTION:  IMPROPER  CHANGES  TO  THE  ANALOG  SIGNAL  CALIBRATION  CAN  CAUSE  ERRONEOUS  READINGS  AND  DISABLE  THE  FIRE  PUMP  FROM  OPERATING  AS  INTENDED.  CONTACT  THE  FACTORY  FOR  FURTHER  INFORMATION.  P/N 06‐791‐2 (Rev. 1)   Page 17 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 20: Setting Summary

    Auto Test Time  Accelerate Time  Summary Page 3  Low Suct Trip Pressure  Low Suct Trip Delay  Shutdown Delay  Low Suct Reset Pressure  Shutdown Reset Delay  Summary Page 4  Load Shed  Low Disch Trip Pressure  Low Disch Trip Delay      Momentary/Maintained  Start Delay  Low Disch Reset Pressure  Summary Page 5  Demand Signal Delay  Supervisory Power  Manual Start Only  Transducer Test  Superv. Power Loss Start  Press Drop Test Setting  Summary Page 6  Serial Number  Manufactured Date  Jockey Settings  DR version    VI version  HMI version    CTL version    Page 18   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 21: Start-Up Procedure

    Remove  all  shipping  ties  and  packing  material  that  may not  yet  have been  removed.  In  particular,  check the contactor or contactors for full movement with the Emergency Manual Operator.   ____ 4. Check all control wires for tightness.   ____ 5. Check that all connectors are seated and latched.   ____ 6. Check all connections in the power path of the motor and any Ground or Grounded conductors for  tightness. Re‐torque any loose connections to the component manufacturer’s specifications.  Contact  Master Control Systems for additional information.   ____ 7. Check  that  the  limit  switch,  mounted  on  the  Emergency  Manual  Operator,  trips  before  the  power  contacts touch.   ____ 8. Make absolutely sure that the fire pump has been primed (filled with water) and ready operation prior  to starting the pump. Failure to prime the pump before running the motor will cause damage to the  motor bearings. Refer to Start‐UP Checklist for pump priming instructions.    P/N 06‐791‐2 (Rev. 1)   Page 19 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 22   START‐UP CHECKLIST  The following checklist is designed to verify basic operation and all field input and output connections between the  controller and the fire pump electric motor. It is recommended for each new installation and the annual fire pump test.  WARNING  TO PREVENT THE POSSIBILITY OF SERIOUS INJURY OR DEATH DUE TO AN ELECTRICAL FAULT, BE SURE THE  DOOR(S) IS CLOSED AND LATCHED BEFORE CLOSING THE ISOLATING SWITCH AND CIRCUIT BREAKER OR  OPERATING THE CONTROLLER.  I. PRIME THE PUMP  CAUTION  Be sure the isolation valve on the discharge side of the DuraQuench pump skid is closed and the fire pump  is primed (filled with water) and ready operation prior to starting the pump. Failure to prime the pump  before running the motor will cause damage to the motor bearings.    CAUTION  Pump motor should not be run unloaded or uncoupled from the pump at any time; damage to the motor  bearings will occur.  ____ 1. Close the discharge isolating valve on the pump skid to prevent water from flowing into the piping  network.  ____ 2. Close the water supply isolating valve on the pump skid to prevent water from flowing into the pump  skid.  ____ 3. Open the priming plug on the pump head. See figure below.  LOOSEN CENTER PLUG TO  VENT PUMP  Fire Pump Vent Plug  ____ 4. Gradually open the water supply isolating valve on the pump skid until a steady stream of airless water  runs out of the priming hole.  ____ 5. Close the plug and tighten securely.  ____ 6. Completely  open  the  water  supply  isolating  valve  on  the  pump  skid.  The  discharge  isolating  valve ...
  • Page 23 ____ 3. Completely open the test header isolating valve on the pump skid.  ____ 4. Close and latch the controller door.  ____ 5. Close the Isolating Switch (IS), then close the Circuit Breaker (CB) to apply power to the controller.   ____ 6. Check that the display begins to power up but do not begin the setup yet.  ____ 7. Check the pump rotation by jogging (bumping) the motor and observing the direction of rotation. Do  this by simultaneously pressing and holding both the Start and Stop pushbuttons. Then momentarily  release the Stop pushbutton. The pump should rotate counter‐clockwise when viewed from top of  pump. If the pump runs backwards, proceed to Step 8. If the pump rotates correctly, proceed to Step  15.  ____ 8. Remove power from the controller by opening the CB, then the IS.   ____ 9. Have a qualified electrician change the pump rotation by swapping two of the three motor leads on  the (M) contactor output terminals located inside the controller cabinet.  ____ 10. Close the controller door and re‐energize the controller by closing the Isolating Switch (IS), then close  the Circuit Breaker (CB).  ____ 11. Verify correct pump rotation (counter‐clockwise).  ____ 12. Remove power from the controller by opening the CB, then the IS.  ____ 13. Reinstall the coupling guard onto the pump.  ____ 14. Close the Isolating Switch (IS), then close the Circuit Breaker (CB) to apply power to the controller.   ____ 15. Now begin the setup by setting the clock.       P/N 06‐791‐2 (Rev. 1)   Page 21 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 24 ____ 3. Lift  up  on  the  Emergency  Manual  Operator  handle  to  unlatch  and  then  release  it.  Check  that  the    contactor drops out and the motor stops. IV. ENERGIZING THE CONTROLLER FOR STAND‐BY OPERATION  ____ 1. Pressurize the system using the Jockey Pump. ____ 2. Verify the Start setting of the jockey pump is higher than the Start setting of the fire pump. This is to  avoid starting the fire pump while in standby. ____ 3. Open the pump discharge valve and any other valves required for proper operation. ____ 4. Verify the fire pump does not start. ____ 5. Operate  the  Pressure  Drop  Test  button  to  drop  system  pressure  and  start  the  motor.  Also,  verify  Deluge Valve Start and Remote Start, if used. ____ 6. Check for a pressure start. ____ 7. Use the Stop pushbutton to stop the fire pump and leave it in service   Page 22   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 25: Operating Instructions

    Stand‐by Operation: The normal stand‐by configuration for the controller is for both the Isolating Switch (IS) and the  Circuit Breaker (CB) to be in the closed position, the color display to be energized, the motor to be off and the Audible  Alarm to be silent.   De‐energizing Controller: To de‐energize the controller, open the Circuit Breaker (CB) and then the Isolating Switch (IS).  If the controller is equipped with modification SP1 or SP2, the supervisory power source branch circuit breaker must  also be opened.  WARNING  FOREIGN  VOLTAGE  MAY  BE  PRESENT.    CONTROLLERS  EQUIPPED  WITH  MODIFICATION  “SP1”  OR  “SP2”  UTILIZE AUXILIARY BRANCH CIRCUIT POWER WHICH IS NOT SWITCHED OR CONTROLLED BY THE ISOLATING  SWITCH (IS) OR CIRCUIT BREAKER (CB).  ALWAYS TURN OFF OR DISCONNECT THE EXTERNAL SOURCE OF  POWER BEFORE ATTEMPTING TO SERVICE THE CONTROLLER.   Manual Electric Starting: Momentarily press the START pushbutton.   Manual Electric Stopping: Momentarily press the STOP pushbutton.  If a start demand exists, the motor will restart after  the STOP pushbutton is released and the restart time delay times out.   Emergency Manual Mechanical Starting: Pull up on the EMERGENCY MANUAL OPERATOR handle and slide the latch  under the operator handle lever.  To stop the fire pump motor, pull up on EMERGENCY MANUAL OPERATOR to release  the latch and then release the operator handle quickly.   NOTE  The Stop pushbutton will not stop the motor when started with the EMERGENCY MANUAL OPERATOR.    P/N 06‐791‐2 (Rev. 1)   Page 23 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 26: Downloading History

      10. DOWNLOADING HISTORY  To download data from the data recorder, open the waterproof cap and slide a USB memory stick into the socket. A  screen will pop up showing the USB status, a SAVE HISTORY button and a SAVE SYSTEM button. Press either button to  select the data desired. The USB status will show Active when downloading data. Once complete, the USB status will  show OK. The other SAVE button can then be pressed. If neither button is pressed within 10 seconds, the HISTORY file  will automatically be downloaded  USB Waterproof Adapter    To read the data from the USB, simply plug in the USB into any computer and open the CSV file with any spreadsheet  program.   The file name for the captured data has the following format:   SNxxxxxx_HIST_yyyymmdd_hhmmss, or SNxxxxxx_SYST_yyyymmdd_hhmmss  SN – always the beginning of the filename  xxxxxx – controller serial number  HIST or SYST – History or System data file  yyyy – Year data was downloaded  mm – Month data was downloaded   dd – Day data was downloaded  hh – Hour data was downloaded   mm – Minute data was downloaded   ss – Second data was downloaded  Page 24   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 27: Maintenance

    All  connections  in  the  power  path  for  tightness.  Re‐torque  any  loose  connections  to  the  component  manufactures’ specifications. Contact Master Control Systems, Inc. for further information.   •  For any indication of water marks on any of the components. Replace every component that has water marks  on it.   •  For any indication that the wire insulation is cracking.   If  any  operation  of  the  controller  does  not  function correctly,  or  the  inspection  reveals  any  of the above  problems,  contact Master Control Systems, Inc. for factory authorized service agent recommendations.  P/N 06‐791‐2 (Rev. 1)   Page 25 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 28 IS   Isolating Sw. Operating Handle w/Door Interlock   400922 (NEMA 3R,4)   800686 (NEMA 2,12)  CB   Circuit Breaker Operating Handle   800685 (NEMA 3R,4)   800686 (NEMA 2,12)  MC‐MO   Manual Mechanical Emergency Operator Handle   800685 (NEMA 3R,4)   MOLS   Manual Operator Limit Switch   801110     Surge Arrester 208 thru 480 VAC Controllers   303481     Surge Arrester 600 VAC Controllers   303482     Fuse, Surge Arrester, 480 VAC, 100kA ‐ Standard   204219     Fuse, Surge Arrester, 600 VAC, 200kA   204319       Plug‐In Relays  RY1 – RY4   DPDT 24 VDC Contactor Control Relay   617022   NOTE  When ordering replacement parts, you must supply the Serial Number and Model Number of the Controller  in which parts are to be used.  Page 26   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 29   P/N 06‐791‐2 (Rev. 1)   Page 27 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 30     Page 28   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 31         P/N 06‐791‐2 (Rev. 1)   Page 29 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 32     Page 30   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 33         P/N 06‐791‐2 (Rev. 1)   Page 31 704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 34                                                     This page intentionally left blank.    Page 32   P/N 06‐791‐2 (Rev. 1)  704 SW 10  Street, P.O. Box 610, Blue Springs, Missouri 64013‐0610 U.S.A. ● Phone: (816) 229‐3405 ● www.fike.com   ...
  • Page 35   REVISION HISTORY  : ............................ July, 2015  RIGINAL  ELEASE      EVISION    ESCRIPTION OF  HANGE EVISION  Rev 1 –  .................................  F ebruary, 2020  1. Revised to reflect changes made to Master Control Systems, Inc., document MC‐G4, Issue 02‐v03, 2019.07.11.  2. Revised per SR62155 to clarify controller setup for activation on pressure loss versus deluge (manual) start.     ...
  • Page 36     CONTACT US  Fike World Headquarters  704 SW 10  Street  Blue Springs, Missouri 64015 USA  Tel: +001 816‐229‐3405  Toll Free (US Only): 1‐800‐YES‐FIKE (1‐800‐937‐3453)  www.Fike.com  For a list of contact information for Fike offices around  the world, visit the Global Locations section of Fike.com   ...

Table of Contents