Outside Air - Dansons Group CC2 Owner's Manual

Vulcan v series
Hide thumbs Also See for CC2:
Table of Contents

Advertisement

Outside air is REQUIRED ON ALL MOBILE HOME INSTALLATIONS.
Outside air is strongly recommended for all other installations. Failure to install intake air may result
in improper combustion as well as the unit smoking during power failures.
Metal pipe, ONLY, either solid or flexible, must be used in all outside air installations.(B)
NOTE: Non-metallic material MUST NOT BE USED for outside air installations.
A wind shield, (C), over the termination of the outside air pipe or a 90 degree elbow or bend directed
away from the prevailing winds MUST be used when an outside air pipe is installed through the side
of a building. Keep the outside air pipe termination at least 1 foot away from the exhaust system
termination.
When outside air is taken from an existing chimney the exhaust system must not terminate in the
same chimney.
The outside air pipe on your stove is 2" OD. The outside air connecting pipe must be at least 2" ID
The outside air connecting pipe must be as short and free of elbows as possible, and must fit over,
(A), not inside, the outside air pipe on your stove.
Through The Wall Kits Include
3
FOOT PACKAGE
PART
1 – 2" Galvanized Hood c/w screen
1 – 2" Aluminum Flex Duct –
compressed 15" length, extends to 30" – 36"
2 – 2" Worm Gear Clamps
NOTE: Available from your local Authorized Dealer or Dansons Group Inc. 1-877-303-3134
Figure 11
Copyright 2005
Canadian Comfort Industries
O
UTSIDE
:
#
03
ACFAKT
www.stovesunlimited.com
A
IR
10
– P
FOOT PACKAGE
1 – 2" Galvanized Hood c/w screen
1 – 2" Aluminum Flex Duct –
compressed 4' length, extends to 120"
2 – 2" Worm Gear Clamps
13
#
10
ART
ACFAKT
Vulcan V SERIES
Owner's Manual
Dansons Group Inc.