especially important in areas where painting, plastering, or
spraying of fireproof material, etc. is not yet complete. Foreign
material that is allowed to accumulate within the units can pre-
vent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to
examine each pipe, fitting, and valve, and remove any dirt or
foreign material found in or on these components.
CAUTION
DO NOT store or install units in corrosive environments or
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
units in an upright position. Tilting units on their sides may
cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Do not remove the packaging until the unit is ready for
installation.
UNIT 50HQP
COMPRESSOR QUANTITY*
Number of Circuits (Compressors)
Factory Charge HFC-410A (kg) per circuit
BLOWER MOTOR
Blower Motor Quantity
Standard Motor (kW)
BLOWER
No. of Blowers
Blower Wheel Size D x W (cm)
WATER CONNECTION SIZE
FPT (in.) [mm]
COAX VOLUME
Volume (liters)
CONDENSATE CONNECTION SIZE
FPT (in.) [mm]
AIR COIL DATA
Air Coil Dimensions H x W (cm)
Air Coil Total Face Area (sq m)
Air Coil Tube Size (cm)
Air Coil Fin Spacing (fins per cm)
Air Coil Number of Rows
MISCELLANEOUS DATA
Filter Standard - Throwaway (qty) (cm)†
Weight - Operating (kg)
Weight - Packaged (kg)
*All units have grommet and spring compressor mountings, and
2.2 mm and 3.5 mm electrical knockouts.
†51 mm filters are available as field-installed accessory.
Table 1 — Physical Data — 50HQP072-120 Units
072
1.70
0.75
6.13
50.8 x 137.16
0.70
265.8
283.9
3. Verify that the unit's refrigerant tubing is free of kinks or
dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Be sure connections are
clean and tight at their terminations.
5. Loosen compressor bolts until the compressor rides freely
on springs. Remove shipping restraints.
6. Remove the four 6 mm (
pressor support plate (two bolts on each side) to maxi-
mize vibration and sound alternation.
Failure to remove shipping brackets from spring-mounted
compressors will cause excessive noise and could cause
component failure due to added vibration.
7. Remove any blower support cardboard from inlet of the
blower.
8. Locate and verify any accessory kit located in compressor
and/or blower section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
096
Scroll
2
2.15
1
1.49
1
30.48 x 30.48
1
1
/
[31.8]
4
6.85
3
/
[19.1]
4
0.953
5.5
3
40.64 x 50.80 x 2.54
292.1
310.3
NOTE: Use the lowest maximum pressure rating when multiple
options are combined:
OPTION
Base Unit
3
1
/
in.) shipping bolts from com-
4
CAUTION
120
2.27
2.24
1
1
/
[38.1]
2
9.08
50.8 x 162.56
0.83
316.6
334.8
MAXIMUM PRESSURE (kPa)
3100