Start-Up; Operating Limits; Air Coil Cleaning; Start Up System - Carrier AQUAZONE 50HQP072-120 Installation And Service Instructions Manual

Horizontal water source heat pumps with puron refrigerant (r-410a) 50 hz
Table of Contents

Advertisement

MECHANICAL NIGHT SET BACK — When NSB input is
connected to ground C, all thermostat inputs are ignored. A
thermostat set back heating call will then be connected to the
OVR input. If OVR input becomes active, then the Deluxe D
control will enter Night Low Limit (NLL) staged heating
mode. The NLL staged heating mode will then provide heating
during the NSB period.
WATER VALVE (SLOW OPENING) — If relay is config-
ured for Water Valve (slow opening), the relay will start 60 sec-
onds prior to starting compressor relay.
OUTSIDE AIR DAMPER (OAD) — If relay is configured
for OAD, the relay will normally be ON any time the Fan
Enable relay is energized. The relay will not start for 30 min-
utes following a return to normal mode from NSB, when NSB
is no longer connected to ground C. After 30 minutes, the relay
will start if the Fan Enable is set to ON.

START-UP

CAUTION
To avoid equipment damage, DO NOT leave system filled
in a building without heat during the winter unless anti-
freeze is added to system water. Condenser coils never
fully drain by themselves and will freeze unless winterized
with antifreeze.
Use the procedure outlined below to initiate proper unit
start-up.
NOTE: This equipment is designed for indoor installation only.
WARNING
When the disconnect switch is closed, high voltage is pres-
ent in some areas of the electrical panel. Exercise caution
when working with the energized equipment.

Operating Limits

ENVIRONMENT — This equipment is designed for indoor
installation ONLY. Extreme variations in temperature, humidi-
ty and corrosive water or air will adversely affect the unit per-
formance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of name-
plate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — All units can start and
operate in an ambient of 7.2 C with entering-air at 10.0/7.2 C
(db/wb), entering water at –1.1 C and with both air and water at
the flow rates used. All other conditions are the same as shown
in Table 10.
NOTE: These operating conditions are not normal or continu-
ous operating conditions. It is assumed that such a start-up is
for the purpose of bringing the building space up to occupancy
temperature.
To obtain maximum performance,
Air Coil Cleaning —
the air coil should be cleaned before start-up. A 10% solution
of dishwasher detergent and water is recommended for both
sides of the coil. A thorough water rinse should follow. Ultra-
violet based anti-bacterial systems may damage e-coated air
coils.

Start Up System

1. Restore power to system.
2. Turn thermostat fan position to ON. Blower should start.
3. Balance airflow at registers.
4. Adjust all valves to the full open position and turn on the
line power to all heat pump units.
5. Operate unit in the cooling cycle. Room temperature
should be approximately 7.2 to 43.3 C dry bulb. Loop
water temperature entering the heat pumps should be
between 10.0 and 43.3 C.
NOTE: Three factors determine the operating limits of a
unit: (1) entering-air temperature, (2) water temperature and
(3) ambient temperature. Whenever any of these factors are
at a minimum or maximum level, the other two factors must
be at a normal level to ensure proper unit operation. See
Table 10. Extreme variations in temperature and humidity and/
or corrosive water or air will adversely affect unit perfor-
mance, reliability, and service life.
Table 10 — Operating Limits
AIR LIMITS
Minimum Ambient Air db
Rated Ambient Air db
Maximum Ambient Air db
Minimum Entering Air db/wb
Rated Entering Air db/wb
Maximum Entering Air db/wb
WATER LIMITS
Minimum Entering Water
Normal Entering Water
Maximum Entering Water
Normal Water Flow
LEGEND
db
Dry Bulb
wb —
Wet Bulb
Scroll Compressor Rotation —
certain compressor is rotating in the proper direction. To
determine whether or not compressor is rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Turn off power to the unit. Install disconnect tag.
2. Reverse any two of the unit power leads.
3. Reapply power to the unit and verify pressures are correct.
The suction and discharge pressure levels should now move
to their normal start-up levels.
When the compressor is rotating in the wrong direction, the
unit makes an elevated level of noise and does not provide
cooling.
After a few minutes of reverse operation, the scroll com-
pressor internal overload protection will open, thus activating
the unit lockout. This requires a manual reset. To reset, turn the
thermostat on and then off.
NOTE: There is a 5-minute time delay before the compressor
will start.

Unit Start-Up in Cooling Mode

1. Adjust the unit thermostat to the warmest position.
Slowly reduce the thermostat position until the compres-
sor activates.
2. Check for cool air delivery at unit grille a few minutes
after the unit has begun to operate.
3. Verify that the compressor is on and that the water flow
rate is correct by measuring pressure drop through the
heat exchanger using pressure/temperature plugs. Check
the elevation and cleanliness of the condensate lines; any
dripping could be a sign of a blocked line. Be sure the
condensate trap includes a water seal.
22
COOLING (C)
HEATING (C)
7
4
27
20
43
29
16/10
10
27/19
20
35/24
27
–1
–6.7
10 to 43
–1 to 21
49
32
1.6 to 3.2 L/m per kW
It is important to be

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquazone 50hqp072Aquazone 50hqp096Aquazone 50hqp120

Table of Contents