Program Step
1
Left tower status
drying
Right tower status
regen.
Left tower
closed
pressure switch
Right tower
closed
pressure switch
Left inlet solenoid
off
(see NOTE 1)
Left purge solenoid
off
Right inlet solenoid
off
(see NOTE 1)
Right purge solenoid
off
Inlet shuttle valve
(see NOTE 2)
Left inlet valve
open
(see NOTE 1)
Left purge valve
closed
Right inlet valve
open
(see NOTE 1)
Right purge valve
closed
Temperature display -
none
thermistor location
NOTE 1: Standard Pressure Models 4100 & 5400 ONLY. High Pressure Models 40 through 450 ONLY.
NOTE 2: Standard Pressure Models 40 through 3000 ONLY.
2
3
drying
drying
regen.
regen.
closed
closed
closed at start,
closed
open at end
off
off
off
off
on
on
off
on
open to left chamber
open
open
closed
closed
closed
closed
closed
open
upper left
lower right
Table 8-2
Cycle Sequence Steps
— 39 —
4
5
drying
regen.
regen.
drying
closed
closed
open at start,
closed
closed at end
off
off
off
off
on
off
off
off
open
open
closed
closed
closed
open
closed
closed
upper left
none
upper right
6
7
regen.
regen.
drying
drying
closed at start,
closed
open at end
closed at end
closed
closed
on
on
off
on
off
off
off
off
open to right chamber
closed
closed
closed
open
open
open
closed
closed
lower left
8
regen.
drying
open at start,
closed
on
off
off
off
closed
closed
open
closed
upper right

Hide quick links: