Fan Performance 48Tf006 — Vertical Discharge Units, Standard Motor; Fan Performance 48Tf006 — Vertical Discharge Units, Alternate Motor - Carrier 48TF004-007 Installation, Start-Up And Service Instructions Manual

Single-package rooftop heating/cooling units
Table of Contents

Advertisement

Table 14 — Fan Performance 48TF006 — Vertical Discharge Units, Standard Motor
48TF006 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Low Speed
Airflow
208 V
(Cfm)
Esp
Bhp
Watts
1500
0.69
0.67
750
1600
0.49
0.70
780
1700
0.29
0.73
810
1800
0.09
0.75
839
1900
2000
2100
2200
2300
2400
2500
LEGEND
Bhp — Brake Horsepower Input to Fan
Esp
— External Static Pressure (in. wg)
FIOP — Factory-Installed Option
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
Table 15 — Fan Performance 48TF006 — Vertical Discharge Units, Alternate Motor
48TF006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
Airflow
0.1
(Cfm)
Rpm
Bhp
Watts
1500
729
0.36
368
1600
770
0.42
429
1700
811
0.50
511
1800
852
0.58
593
1900
893
0.68
695
2000
935
0.78
797
2100
977
0.89
910
2200
1019
1.02
1042
2300
1061
1.16
1185
2400
1103
1.30
1328
2500
1145
1.46
1492
48TF006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
Airflow
1.2
(Cfm)
Rpm
Bhp
Watts
1226
1.19
1216
1500
1600
1242
1.28
1308
1700
1270
1.39
1420
1300
1.52
1553
1800
1900
1329
1.64
1676
2000
1355
1.77
1809
2100
1381
1.91
1952
2200
1413
2.08
2126
2300
1449
2.26
2310
2400
1485
2.47
2524
2500
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range is 900 to 1300 rpm. All other rpms require a field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
230,460,575 V
208 V
Esp
Bhp
Watts
Esp
Bhp
1.01
0.71
791
1.00
0.70
0.85
0.74
824
0.85
0.74
0.70
0.77
857
0.70
0.77
0.54
0.80
891
0.55
0.81
0.39
0.83
924
0.40
0.84
0.23
0.86
957
0.25
0.88
0.08
0.89
990
0.10
0.91
External Static Pressure (in. wg)
0.2
Rpm
Bhp
Watts
Rpm
Bhp
788
0.42
429
896
0.56
826
0.49
501
930
0.64
864
0.57
582
964
0.72
903
0.66
674
999
0.82
942
0.76
777
1035
0.92
982
0.87
889
1070
1.04
1022
0.99
1012
1107
1.17
1063
1.12
1145
1144
1.30
1104
1.26
1288
1182
1.47
1145
1.41
1441
1220
1.61
1186
1.57
1604
1259
1.78
1.4
Rpm
Bhp
Watts
Rpm
1301
1.46
1492
1380
1318
1.49
1523
1392
1335
1.58
1615
1408
1361
1.71
1747
1423
1391
1.80
1891
1448
1420
1.99
2034
1477
1449
2.14
2167
1474
2.30
2350
Medium Speed
230,460,575 V
Watts
Esp
Bhp
Watts
782
1.20
0.76
821
1.06
0.79
861
0.93
0.83
900
0.80
0.86
940
0.67
0.90
979
0.54
0.93
1035
1018
0.41
0.96
1073
0.28
1.00
1111
0.15
1.03
1149
0.02
1.07
1187
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for Additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
0.4
0.6
Watts
Rpm
Bhp
Watts
572
981
0.69
654
1015
0.78
736
1051
0.88
838
1085
0.98
1001
940
1119
1.10
1124
1063
1153
1.22
1247
1196
1187
1.35
1380
1328
1222
1.49
1523
1502
1258
1.65
1686
1645
1293
1.80
1860
1819
1329
2.00
2044
1.6
Bhp
Watts
1.69
1757
1.78
1800
1.80
1850
1.91
1952
2.05
2095
2.21
2258
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 1.30 for single-phase units and 2.40
for 3-phase units and the maximum continuous watts are 2120.
Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
24
High Speed
208 V
Esp
Bhp
Watts
Esp
845
1.22
0.79
875
1.28
883
1.09
0.82
913
1.17
921
0.97
0.85
950
1.06
959
0.84
0.89
988
0.95
997
0.72
0.92
1025
0.84
0.59
0.95
1063
0.73
0.46
0.99
1101
0.62
0.34
1.02
1138
0.51
0.21
1.06
1176
0.40
0.09
1.09
1213
0.29
0.18
0.8
Rpm
Bhp
Watts
Rpm
705
1070
0.85
869
1144
797
1098
0.94
961
1173
899
1124
1.03
1053
1203
1155
1.13
1155
1231
1191
1.26
1288
1288
1227
1.40
1431
1287
1260
1.54
1574
1323
1294
1.70
1737
1359
1328
1.80
1901
1393
1362
2.03
2074
1426
1397
2.22
2269
1460
230,460,575 V
Bhp
Watts
0.85
949
0.89
988
0.92
1027
0.96
1066
0.99
1105
1.03
1144
1.06
1183
1.10
1222
1.13
1261
1.17
1300
1.20
1340
1.0
Bhp
Watts
1.01
1032
1.11
1134
1.21
1237
1.32
1349
1.43
1461
1.57
1604
1.72
1758
1.89
1931
2.07
2115
2.26
2310
2.45
2504

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48tf00448tf00548tf00648tf007

Table of Contents