Ta ble 1 :
WAT ER RAT ING S AND S PEC IFI CATI O NS
Description
DOE Heating Capacity (MB H)
IBR Net Water rating (MB H)
Fir ing Ra te (gal/hr)
Noz zle Spec ifi cation
Stack Dia meter (inch)
Nu mber of Tub es
Boiler Water Cap. (gal.)
Supply S ize (FPT)
Return S ize (FPT)
Tankles s Heater S ize (gal/mi n)
Chimn ey S ize (mi n)
Approx. S hipping Wt. (lb.)
DIM ENSIO NS
A Overall Width (in.)
B Overall Len gth Boiler (in.)
C J ack et Height (in.)
D J acket Length (in.)
E Jacket Width (in.)
F S moke Outlet Height (in.)
G Over all Leng th w/Burner (in.)
Notes:
Figure 1: HF Packaged Boiler (HF-98/HF-173)
HF- 98
104
90
.85
.75 x 45° B
6
12
20
4 (5 Optiona l)
8" x 8" x 15'
450
M ax. W orki ng P ressu re: 30 PSI (W ater O nly)
18-1/8
24-1/2
37-3/4
18
18-1/8
25-1/4
33
1.
Firing rates based on 140,000 BTU per gallon of oil
2.
IBR net water ratings based on a pick-up allowance of 1.15
3.
Manufacturer should be consulted before selecting a boiler for installations having
unusual piping and pick-up requirements.
4.
Firebox draft setting: -.02 inches water column
5.
Ratings based on 13.0% CO
HF- 122
132
115
1.10
.90 x 45° B
6
12
20
4 (5 Optiona l)
8" x 8" x 15'
450
18-1/8
24-1/2
37-3/4
18
18-1/8
25-1/4
33
2
5
HF- 147
HF- 173
154
184
134
160
1.25
1.50
1.00 x 45° B
1.25 x 45° B
7
7
18
18
40
40
2
2
2
2
5
5
8" x 8" x 15'
8" x 8" x 15'
720
720
24
24
31-3/4
31-3/4
46-3/4
46-3/4
21-3/4
21-3/4
22
22
30
30
39
39