 Apply voltage terminal (CNA02, CNA102, CNA202, CNA302)
When a power supply must be provided at the input device you want to connect, use
the Apply voltage terminal (CNA02, CNA102, CNA202, CNA302)
DC power sup-
ply 12 - 24V
-
Load
resistance
*c
connected unit
*1: Make the power supply DC12 to 24V. Select a power supply capacity with an
ample surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-3.
*c: The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*d: The polarity is [+] for pin 1 and [-] for pin 3. Connect correctly.
When connected to Apply voltage terminals of multiple RB units with a connected
unit, be sure to make a branch outside the RB unit using a pull box, etc. as shown on
below example.
DC power sup-
ply 12 - 24V
Load
resistance
connected unit

9.2. Cooling/heating priority function

 "Edge" input only
Connector
Input signal
OFF → ON
CNA01 or CNA02
ON → OFF
On
CNA01 or CNA02
Off
Heating
Priority mode
Cooling
*1
PC board
+
+
1
2
CNA02
-
3
*d
PC board
CNA
02
PC board
CNA
02
Command
Heating priority
Cooling priority

10. MERGING 2 OR 4 BRANCHES

An indoor unit with a capacity exceeding 8.0 kW can be connected by
merging 2 or 4 indoor-unit-side outlet branches.
This chapter should be read only if 2- or 4-branch merging is planned.
To connect an indoor unit with a capacity exceeding 8.0 kW, use the option-
ally available separation tube kit.
For the installing of the separation tube kit, refer to the installation manual
for the kit.
10.1. Connection specifi cations
Typical examples
O.U.
I.U.
I.U.
Separation tube kit
(UTP-EX096A)
Connection specifi cations
Maximum capacity of
2-branch merging
connectable indoor
units per branch (Q)
4-branch merging
RB unit
I.U.
I.U.
I.U.
It is not possible to connect multiple indoor units downstream of the point where 2 or 4
branches are merged together.

10.2. Pipe installation (pipe selection)

Suction gas pipe
Liquid pipe
Discharge gas
Gas pipe
Select the connection
pipe from Table 1 ,
based on the capacity
of the indoor unit con-
nected.
Table1 ) Indoor unit capacity and connection pipe sizes
Indoor unit capacity
(kW)
Gas pipe
15.88(5/8'')
9.0, 10.0
+Reducer
11.2, 12.5, 14.0, 18.0
19.05(3/4'')
22.4, 25.0, 28.0
22.22(7/8'')
RB unit
Separation
I.U.
tube kit
(UTP-
EX060A)
8 < Q ≤ 18 KW
18 < Q ≤ 28 KW
I.U.
I.U.
RB unit
Liquid pipe
I.U.
I.U.
Downstream of RB unit
Outside diameter [mm(in)]
Liquid pipe
9.52(3/8'')
9.52(3/8'')
12.70(1/2'')
En-12