Checking the CO content
content
(cont.)
2
1. Press "-"
mented to "0" (lower heating output).
2. Note
The CO
between 7.5 and 10.5 %.
Check the CO
content must be 0.3 % lower in partial load than it
is in full load.
Rated heating
output in kW
400
500
630
3. If the CO
4. Record the actual value in the report (on
page 54).
!
Rechecking the values
Regulate to the upper and lower heating output
again using the programming unit in the burner
control unit. If the values do not match the permis-
sible CO
page 12, repeat the steps for the upper and lower
heating output.
5. Press "S"
burner continues at the original modulation level at
which status "d" (= control stop) was initiated. The
burner then returns to operating mode.
Commissioning, inspection, maintenance
until the service display has decre-
D
content for all natural gases must be
2
content at the flue pipe. The CO
2
Permissible CO
%
8.3
0.3
±
8.3
0.3
±
8.3
0.3
±
content needs adjusting:
2
Undo cover
B
.
Turn adjusting screw
in small increments
A
(Torx 40) until the CO
content lies within the
2
specified range:
Turning clockwise
CO
content rises
2
Turning anti-clockwise
CO
content falls
2
Please note
The CO
content must always be lower in
2
partial load than it is in full load.
content according to the table on
2
and "-"
simultaneously. The
E
D
2
content in
2
13