Converting The Boiler Door Opening - Viessmann Vitogate 300 Installation Instructions Manual

Table of Contents

Advertisement

Siting and levelling the boiler
Note
Remove transport protectors.
3. Level the boiler using the adjusting
screws.
Note
We recommend installing the boiler on
adjustable anti-vibration feet C (see
page 5) or anti-vibration boiler sup-
ports D/E (see page 5).
Adjustable anti-vibration feet
Insert adjusting feet into the base rails
from below.

Converting the boiler door opening

A
B
C
D
(cont.)
Anti-vibration boiler supports
Any unevenness in the floor should be
max. 1 mm, to ensure the spring ele-
ments are evenly loaded.
Position the boiler supports underneath
the boiler. For this, locate them centrally
underneath the base rails.
When setting the boiler down less than
square on, a boiler support can tempo-
rarily be overloaded. This can be pre-
vented by laying timbers (□ 35 mm)
under the front, centre and back of each
boiler support.
B
9