Cover Installation; Sqm5X.xxxxxzx Actuators - Maxitrol 325 Series Manual

Appliance pressure regulators
Table of Contents

Advertisement

Technical Instructions
Document No. 155-517P25
May 3, 2010

Cover Installation

Features of
SQM5x.xxxxxZx
Actuators
Multiple Input Signals
Multiple Output Signals
Page 16
1.
Lift the two screws on the cover corners and slide the cover end into the grooves at
the gear end of the actuator. See Figure 14.
2.
Press the cover into place and then press the screws inward and tighten. See
Figure 15.
Figure 14.
SQM5xx.xxxxxZx actuators contain the AGA56.9A
circuit board provides the following features:
The AGA56.9A
circuit board accepts the following input signals:
Line voltage
Power to A drives the actuator open to the setting of switch cam I (Maximum).
Power to ZL drives the actuator closed to the setting of switch cam III (Minimum).
Power to Z drives the actuator closed to the setting of switch cam II (Economy).
4 to 20 mA (Signal to Y3, common to M)
0 to 135
(Slide wire signal to Y0, potentiometer connected to M and U4)
0 to 10 Vdc (Signal to Y1, common to M)
0 to 20 mA (Signal to Y2, common to M)
The AGA56.9A
circuit board provides the following output signals:
4 to 20 mA (Signal from U3, common to M)
0 to 10Vdc (Signal from U1, common to M)
0 to 20mA (Signal from U2, common to M)
Double potentiometers ASZ22
multi function circuit board. This
provide additional output signals.
Siemens Building Technologies, Inc.
SQM5
Reversing Actuators
Figure 15.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

325-3325-5a325-7a325-3b325-5ab325-7ab

Table of Contents