SQM5
Reversing Actuators
Switch Adjustment,
Continued

Shaft Adjustment

See Figure 6.

Cam Drum Adjustment

See Figure 6.
Position Indicating Dial
Adjustment

Wiring

Electrical Connection

Grounding

Siemens Building Technologies, Inc.
NOTE:
If a potentiometer is installed, the adjustable range of the switches depends on
the range of the potentiometer.
SQM5x.xxxxxAx actuators may be adjusted between 0 and 160 .
SQM5x.xxxxxx3 actuators have a 90 potentiometer and the switches must be
adjusted only between 0 and 90 .
SQM5x.xxxxxx4 actuators have a 135 potentiometer and the switches must
be adjusted only between 0 and 135 .
The actuator shaft can be disengaged by pressing the silver shaft release button. The
button is located above the grounding screw, under the hinged terminal protection cover,
and to the right of the auto/manual switch. After pressing the shaft release button in and
slightly upward, the shaft can be manually rotated. After the shaft has been manually
aligned to the closed position, re-engage the shaft by pushing the shaft release button
downwards.
Once the shaft has been set, the cam drum must be manually aligned by pressing and
holding the black cam drum release button (see Figure 6). Rotate the cam drum until the
"0" mark on the actuator position scale (left scale on the cam drum) is aligned with the
gray actuator position indicating pointer.
The actual position of the SQM5
indicating pointer (see Figure 6). The position is also displayed by the indicating dial
through the housing's window. Ensure that the actuator position indicating dial is aligned
with the actuator position scale. If necessary, rotate the dial in the clockwise direction.
CAUTION:
Turning the dial in the counterclockwise direction may loosen the
potentiometer locking screw.
SQM5
actuators are equipped with two removable conduit connection plates located
on the upper corner of the gear housing. Each plate is provided with two threaded
connections for 1/2" NPSM conduit connectors. The use of flexible stranded wire is
recommended.
CAUTION:
To avoid electro-magnetic interference, the SQM5
grounded.
The ground terminal is located to the right of the auto/manual switch.
Disconnect the circuit board wire marked 51 during high voltage testing.
Reconnect it to the grounding terminal after the test.
actuator is indicated by the gray actuator position
Technical Instructions
Document No. 155-517P25
May 3, 2010
actuators must be
Page 9