Automatic Voltage Regulator

7. INSTALLATION

Attention! Before connecting the regulator, make sure that all consumer devices con-
nected to it are off.
Before installing the AVR, please make sure that total power of all voltage consumers is lower
than AVR power. Taking into account the starting load and power factor of voltage consumers, it is
necessary to apply power margin factor of 1.2–1.5; for such equipment as air conditioners, fridges
and other electric motors it should be 1.5–2.
Attention! When choosing an AVR, it is necessary to know that reduction of input voltage
Such dependence is shown in the graph below:
output power, %
of nominal
100
75
50
25
0
100 1 10 120 130
Note. Adhere strictly to such dependence. If the condition stated above is not adhered to,
warranty servicing becomes void!
Plug the stabilizer power cord
Turn on stabilizer with switch
If the AVR operates properly, green LED
time the digital indicator
on the "DELAY" button "RESET/ OFF"
digital indicator
will show the output voltage of the regulator. And only after that you can turn on
the connected devices, consumers.
When the mains voltage exceeds the allowable rate (lower threshold is 150 V, upper threshold is
270 V) the red LED
Attention! It is recommended to switch off the AVR and every connected consumer device
when the power supply is dropped.

8. PAUSE FUNCTION

The Pause mode feature is designed to protect equipment in case of frequent drops of the mains
supply. This is particularly important for consumer appliances with electric motors or compressors.
After power supply has been recovered, the AVR switches on within 6 or 180 seconds, depending
on the " DELAY " button " RESET/ OFF " position.
9. PROTECTION FUNCTION AGAINST HIGH AND LOW INPUT VOLTAGE, OVERLOAD AND
OVERHEAT
The stabilizer is equipped with an circuit overvoltage and undervoltage protection. In the case of
time red LED
illuminates. When the input voltage range returning to 150-270 V the stabilizer
automatically resumes operation.
In case of overload or short-circuit AVR power switch
cause or short circuits, press AVR power switch
operation.
4
Technical support: www.real-el.com
140 150 160 170 180 190 200 210 220 230 240 250 260 270
in the wall outlet.
(RESET position).
will show the input voltage. The total delay makes 6 or 180 s depending
position. After the delay time yellow LED
illuminates, the AVR disconnects the load automatically.
illuminates, and yellow LED
will triggered. After elimination overload