Water connection

Water dimensions
Standard variant with factory fitted valves:
Length
Cooling
(mm)
Return
800, 1100, 1400
DN15 external
thread
Standard variant without factory fitted valves:
Length
Cooling
(mm)
Supply and return
Plain pipe
800, 1100, 1400
(Cu) Ø 12 x 1,0 mm
23,5
92,5
Water connection on right side "R"
Cooling and heating on right side "R", all sizes
A2
A1
Cooling "R", all sizes
A2
A1
Water connection on right side (R).
A1 = Cooling water, supply
A2 = Cooling water, return
B1 = Heating water, supply
B2 = Heating water, return
222,5
146,6
23,5
Heating
Return
DN15 external
thread
Heating
Supply and return
Plain pipe
(Cu) Ø 12 x 1,0 mm
315
92,5
B2
B1
22/11/2021

Connecting water

Connect the water pipes using push-on couplings or
compression ring couplings when the product is ordered
without valves. Note that compression ring couplings
require support sleeves inside the pipes.
Do not use solder couplings to connect the water pipes.
High temperatures can damage the unit's existing soldered
joints. Flexible connecting hoses for water are available for
flat-end pipes and valves, and can be ordered separately.
 
Water connection on left side "L"
Cooling and heating on left side "L" all sizes
A2
A1
Cooling "L" all sizes
A2
A1
Water connection on left side (L).
A1 = Cooling water, supply
A2 = Cooling water, return
B1 = Heating water, supply
B2 = Heating water, return
Swegon reserves the right to alter specifications.
PARAGON VAV
B2
B1
7