4.2.5
View from above
4.2.6
Dimensions, fixing bracket
25
32
4.3
Observing the requirements for the
installation site
4.3.1
Observing the requirements for the
product's installation site
The product can be installed in dwellings, cellar spaces, stor-
age or utility rooms, and in attics. The product is wall-moun-
ted only.
Observe the current applicable national construction reg-
ulations.
Ensure that the installation site is dry and is frost-proof
throughout.
Ensure that the installation site is aerated and ventilated.
Install the supply air pipeline so that there is sufficient
distance to the exit air pipeline, exhaust air pipeline and
outflow purging.
Check the load-bearing capacity of the wall.
Load-bearing capacity: ≥ 41 kg
Check whether the supplied fixing elements are sufficient
for the selected installation site.
Ensure that the installation site is not located higher than
max. 2000 metres above sea level.
0020159949_07 recoVAIR Installation and maintenance instructions
300
595
270
204
32
25
Minimum clearances and installation clearances
30
400
Observe the minimum clearances and installation clear-
ances.
Plan sufficient space for installing the ventilation system.
In order to minimise pressure losses, ensure that the dis-
tances between the header line of the ventilation system
and the product are as short as possible.
After installation, ensure that the pipelines and the ventil-
ation system are easily accessible.
Ensure that the mains plug/circuit breaker (depending on
the country) is always accessible after the installation.
Ensure that there is sufficient space to install the con-
densate siphon and condensate drain pipework.
4.3.2
Observing the requirements for the
installation site of the remote control (step
switch/control)
Ensure that the remote control is always accessible at
the installation site.
Ensure that there is sufficient space to install and operate
the remote control.
4.3.3
Observe the requirements for silencers and
for installing ducts and the product
If the opening for the exit air pipeline is too close to the inlet
opening of the outside air pipeline, the exit air can recircu-
late.
Prevent exit air from being sucked in through the outside
air opening, supply air from being sucked in through the
exhaust air opening, and transfer air from being sucked
in directly through leaks/cable feedthroughs.
If required, connect the product to the pipelines using a
sound-absorbing hose in order to minimise noise pollu-
tion caused by structure-borne noise.
Install silencers in order to minimise noise pollution via
the duct system.
If you install the product in an attic, select an installation
site that is not above living spaces.
Set-up 4
400
30
300
7